5. Data Report
Data report configuration and sending period are as following:
Min. Interval
(Unit:second)
Max. Interval
(Unit:second)
Reportable Change
Current Change≥
Reportable Change
Current Change
<
Reportable Change
Any number between
30~65535
Any number between
Min.~65535
Can not be 0.
Report
per Min. Interval
Report
per Max. Interval
The device will immediately send a version packet report along with an uplink packet including current,
illuminance and battery
voltage.
The device sends data in the default configuration before any configuration is done.
Default setting:
Max Interval = 0x0E10 (3600s)
Min Interval = 0x0E10 (3600s)
CurrentChange:0x0064 (100 mA) // Subject to factory settings
IlluminanceChange: 0x0064 (100 Lux) // Subject to factory settings
Current and Illuminance Detection:
When the function key is manually triggered, the CT needs a 5-second sampling time. After sampling, the device reports
three-phase current value and illuminance value.
(An interval of 5 seconds is required to repeat the manual trigger so as to avoid operation failure. Or, please wait till the
configured report time.)
Note:
(1)
The device report interval will be programmed based on the default firmware which may vary.
(2)
The interval between two reports must be the minimum time.
Please refer Netvox
LoRaWAN Application Command document
and
Netvox Lora Command Resolver
http://cmddoc.netvoxcloud.com/cmddoc to resolve uplink data.