Sleeping Mode

 

 

The device is on and in the 

network 

Sleeping period: Min Interval. 

When the reportchange exceeds setting value or the state changes: send a data report according to Min Interval.   

The device is on but not in   

the network 

First two mins: wake up every 15 seconds to send request. 

After two mins: enter sleeping mode and wake up every 15 minutes to send request. 

Note: Suggest to remove batteries if the device is not used.   

          Suggest to check device verification on gateway. 

 

Low Voltage Warning 

Low Voltage 

3.2V 

 
 

  5. Data Report   

When the device is turned on, it will immediately send a version package and a cluster report data.   
Data will be reported once per hour by default setting. 
Maximum time: 3600s 
Minimum time: 3600s (Detect the current voltage value every 3600s by default setting) 
Default reportchange:   

 

Batteryvoltagechange ---- 0x01(0.1V) 

  Acceleratedspeedchange ---- 0x03(m/s²) 

 
Remarks:   
1. The device data sending cycle depends on the burning configuration before shipment. 
2. The interval between two reports must be the minimum time. 

 

·

R718E to report three-axis acceleration and speed

 

 
The device's three-axis acceleration exceeds the set active threshold and a report is issued immediately. After reporting the three-axis acceleration and 
speed, the three-axis acceleration of the device needs to be lower than the set static threshold and the duration is longer than 5 seconds (not modifiable) 
before the next detection can be started. If vibration continues to occur during this process. The timing starts again. 
The device sends two packets of data, one for three-axis acceleration, one for three-axis speed and temperature, and interval between two packets are 
10 seconds.   
 
Note: MinInterval is the sampling period for the Sensor. Sampling period >= MinInterval.   
 
he reported data is decoded by the Netvox LoRaWAN Application Command document and 

http://www.netvox.com.cn:8888/page/index

 

 

Data report configuration and sending period are as following:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Configure device parameters MinTime = 1min, MaxTime = 1min, BatteryChange = 0.1v, Acceleratedspeedchange = 1m/s2 

       Downlink: 011C003C003C0100010000 

       Device returns: 

Description 

Device 

CmdID 

DeviceTy

pe 

NetvoxPayLoadData 

ConfigReportRe

R718E 

 

0x01 

0x1C 

MinTime(2

bytes 

Unit:s) 

MaxTime(2by

tes Unit:s) 

BatteryChange

(1byte 

Unit:0.1v) 

Acceleratedspe

edchange 

(2byte 

Unit:m/s2) 

Reserved     

ConfigReportRs

0x81 

Status(0x00

_success) 

Reserved (8Bytes,Fixed 0x00) 

ReadConfigRepo

rtReq 

0x02 

Reserved (9Bytes,Fixed 0x00) 

ReadConfigRepo

rtRsp 

0x82 

MinTime(2

bytes 

Unit:s) 

MaxTime(2by

tes Unit:s) 

BatteryChange

(1byte 

Unit:0.1v) 

Acceleratedspe

edchange 

(2byte 

Unit:m/s2) 

Reserved     

Содержание R718E

Страница 1: ...Model R718E Three Axis Digital Accelerometer NTC Thermistor Three Axis Digital Accelerometer NTC Thermistor R718E User Manual...

Страница 2: ...1 Table of Content 1 Introduction 2 2 Appearance 2 3 Main Features 3 4 Set up Instruction 3 5 Data Report 4 6 Example Application 7 7 Installation 7 8 Important Maintenance Instruction 7...

Страница 3: ...tance and low power consumption Compared with other communication methods LoRa spread spectrum modulation method greatly increases to expand the communication distance Widely used in long distance low...

Страница 4: ...ashes for 20 times Power off Remove Batteries Note 1 Remove and insert the battery the device is at off state by default 2 On off interval is suggested to be about 10 seconds to avoid the interference...

Страница 5: ...er reporting the three axis acceleration and speed the three axis acceleration of the device needs to be lower than the set static threshold and the duration is longer than 5 seconds not modifiable be...

Страница 6: ...teger and is configured as 16 Example of threshold configuration Assuming that the active threshold is set to 10m s2 the value to be set is 10 9 8 0 0625 16 32 The last value obtained is an integer an...

Страница 7: ...H Example 3 based on MinTime 15 Minutes MaxTime 1 Hour Reportable Change i e BatteryVoltageChange 0 1V MaxTime sleeping sleeping 0H 15th M 30th M 45th M 1H 1H 10th M 1H 25th M 1H 40th M 1H 55th M 2H 1...

Страница 8: ...ic threshold is 104m s2 The specific configuration needs to be based on actual conditions The configuration of the active threshold and the static threshold can be found in the Netvox LoRaWAN Applicat...

Отзывы: