8
Data report configuration and sending period are as following:
Example of data configuration:
FPort
:
0x07
Bytes
1
1
Var(Fix =9 Bytes)
CmdID
DeviceType
NetvoxPayLoadData
CmdID
– 1 bytes
DeviceType
– 1 byte – Device Type of Device
NetvoxPayLoadData
– var bytes (Max=9bytes)
(1) Configure device parameters MinTime = 1min, MaxTime = 1min, BatteryChange = 0.1v
Downlink: 014F003C003C0100000000
The device returns:
814F000000000000000000 (configuration succeeded)
814F010000000000000000 (configuration failed)
Min Interval
(Unit: second)
Max Interval
(Unit: second)
Reportable Change
Current Change
≥
Reportable Change
Current Change
<
Reportable Change
Any number between
1~65535
Any number between
1~65535
Can not be 0.
Report
per Min Interval
Report
per Max Interval
Description
Device
Cmd
ID
Device
Type
NetvoxPayLoadData
Config
ReportReq
R311FA
0x01
0x4F
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
BatteryChange
(1byte
Unit:0.1v)
Reserved
(4Bytes,Fixed
0x00)
Config
ReportRsp
0x81
Status
(0x00_success)
Reserved
(8Bytes,Fixed 0x00)
ReadConfig
ReportReq
0x02
Reserved
(9Bytes,Fixed 0x00)
ReadConfig
ReportRsp
0x82
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
BatteryChange
(1byte
Unit:0.1v)
Reserved
(4Bytes,Fixed
0x00)