Hot-adding a disk shelf to an existing loop
8
Set the loop speed:
◆
The 1-Gb loop speed setting must be used if the system is an
FAS270.
◆
The 2-Gb loop speed setting must be used if there is any
component on any part of the loop that is only capable of 2-Gb
operation. Examples of these components are the DS14mk2FC,
SFPs, HBAs, or drives.
◆
For the 4-Gb loop speed setting to be used, all components on
any part of the loop must be of 4-Gb capable. Examples of these
components are this disk shelf model, SFPs, HBAs, or drives.
Attention
An incorrectly set loop speed causes the system to panic.
9
Connect the two disk shelf power cords of each disk shelf that you
are adding to a power source.
Attention
Do not turn on the power to the disk shelf yet.
Step
Action