25
SafeGuard Controller User Manual
MAN-0115 Rev 0
R2
R1
ANALOG INPUTS
R3
R4
R7
R6
R5
+EXC-
DC PWR
TB2
R8
JP1
ST-71 ANALOG INPUT BOARD
0010-1115 ASSY# 10-0158
J2
J1
J1 & J2 are interchangable I2C
connectors used to add option
PCB assemblies to the ST-71.
JP1 determines if this 8 channel
Analog Input PCB provides inputs
for CH’s 1-8 or 9-16. 2 PCB
assemblies are required for 16
channels.
Socketed precision resistors R1-R8
are 100 ohm terminations for 4-20mA
inputs. 0-2 VDC voltage inputs may
be accepted by removing resistor.
TB2 is for powering bulk power to transmitters
or other powered input devices. EXC+ is
wired internally to channel “EXC’s” and EXC-
to channel “LO’s”.
CH1/9
EXC
HI
CH7/15
HI
EXC
CH3/11
EXC
LO
HI
LO
CH5/13
LO
HI
EXC
LO
CH2/10
HI
EXC
CH8/16
CH4/12
EXC
LO
HI
LO
EXC
CH6/14
EXC
LO
HI
LO
HI
8 Channel Analog Input Option #10-0158
EXC
LO
HI
2 Wire 4-20mA
Transmitter
+Pwr
Sig
3 Wire 4-20mA
Transmitter
EXC
LO
HI
+Pwr
Sig
Com
Typical 2 & 3 wire 4-20mA
transmitter wiring (connect
correct power, 24VDC or
other, to TB2).
CH # (1-8)
CH # (1-8)
Figure 3.3
3.1.2 OPTIONAL
DISCRETE RELAY PCB # SG10-0195
An optional
Discrete Relay PCB
, shown in Figure 3.4, adds eight 5 amp (resistive) form
C relays per sixteen channel alarm group (2 PCB’s required when utilizing more than 8
channels). Each PCB may be configured via rotary switch S1 to function for ALARM 1,
ALARM 2 or ALARM 3/FAULT for channels 1-8 or 9-16. A one (1)-minute time delay
after power, is provided to inhibit relay actuation until the system has had time to
stabilize. Alarm groups, or zones, may be created by connecting adjacent channels
together using JP4 as shown. This creates a wire
OR
function with selected channels,
causing
any
alarm included within the zone to actuate
ALL
zone relays.
Failsafe
operation of SG10-0195 discrete relays may be programmed in the
system
menu as
J1 & J2 are interchangeable I2C
connectors used to add option PCB
assemblies to the SafeGuard
Controller.
PART # SG10-0158 SafeGuard
Analog Input board.
8 channel Analog Input Board Part # SG10-0158
Содержание SAFEGUARD CONTROLLER
Страница 1: ...MAN 0115 REV 0 August 13 2009 SAFEGUARD CONTROLLER User Manual Revision 4 4 Firmware 6 03 later...
Страница 33: ...30 SafeGuard Controller User Manual MAN 0115 Rev 0 Figure 4 2 Note The Printer Option is not used at this time...
Страница 41: ...38 SafeGuard Controller User Manual MAN 0115 Rev 0 Figure 6 3...