12
SafeGuard Controller User Manual
MAN-0115 Rev 0
reads this value and records it as the channel’s
Sensor Life
.
Sensor Life
is stored in the
SafeGuard Controller’s modbus database and displayed as a bar-graph in the Sensor Info
screen (see section 2.3.6). It is a useful tool for planning sensor replacement schedules.
2.2.5 LINEARIZATION
MENU
The linearization menu allows each channel to have its own linearization curve stored in
the SafeGuard Controller’s non-volatile memory. Input versus output points must be
entered in
percent of full scale
values. This means if the range is 0-200 ppm H2S then
100 ppm is 50% of full scale. Zero input will provide a zero output and 100% input a
100% output. Nine intermediate points may be entered to define the curve.
EDIT
NEXT
Entry menu
C h a n n e l X X
Me a s u r e me n t N a me
Linearization menu
C h a n n e l X X
L i n e a r i z a t i o n
% I n p u t
% Ou t p u t
10 . 0 0
2 0 . 0 0
3 0 . 0 0
4 0 . 0 0
5 0 . 0 0
6 0 . 0 0
7 0 . 0 0
8 0 . 0 0
9 0 . 0 0
10 . 0 0
2 0 . 0 0
3 0 . 0 0
4 0 . 0 0
5 0 . 0 0
6 0 . 0 0
7 0 . 0 0
8 0 . 0 0
9 0 . 0 0
A l a r m 1
A l a r m 2
A l a r m 3
D a t a F r o m
C a l i b r a t e
L i n e a r i z e
C o n f i g u r e
Figure 2.6
2.2.6 CONFIGURE
MENU
From the entry level setup menu in Figure 2.7 the CONFIGURE menu may be entered
for setting variables defining how the SafeGuard Controller presents monitored data to
the various graphic displays.
Figure 2.7
2.2.6a EUNITS / MEASUREMENT NAME ASCII DATA FIELDS
The first two items in this menu are for entering the 6 character
engineering unit
and 16
character
Measurement Name
ASCII fields. Eunits should define the units of measure for
what this channel is to display.
Measurement Name
should describe the source of this
data in the user’s terminology. Section 2.1.1 of this manual describes how to use the
front keypad to modify these fields.
Entry menu
C h a n n e l X X
Me a s u r e me n t N a me
A l a r m 1
A l a r m 2
A l a r m 3
D a t a F r o m
C a l i b r a t e
L i n e a r i z e
C o n f i g u r e
EDIT
NEXT
Input / Copy To: menu
C h a n n e l X X
C ON F I GU R A T I O N
Me a s u r e me n t N a me
E u n i t s
Z e r o
S p a n
D e c i ma l P o i n t s
P C T L E L
0 . 0 0 0
C o p y N o w ?
10 0 . 0
C h a n n e l O n ?
0
Y E S
C o p y T o
X X