background image

Net Safety Monitoring Inc

Modbus Controller & 4-20 Fire Head

3

STEP 3 — W

IRE

F

IELD

 I

NSTALLATION

WARNING:

 

Wiring codes and regulations may vary. Compliance with regulations is the 
responsibility of the installer. Wiring must comply with applicable regulations 
relating to the installation of electrical equipment in a hazardous area. If in 
doubt, consult a qualified official before wiring the system.

• If the 4-20 mA output signal is not used, connect a jumper between the 4-20 

terminal and the Common terminal.

• The use of shielded cable is highly recommended for signal, input, output and 

power wires to protect against interference caused by extraneous electrical or 
electromagnetic 'noise'. 

• In applications where the wiring cable is installed in conduit, the conduit 

must not be used for wiring to other electrical equipment. 

• The maximum distance between the Sensor and Controller is limited by the 

resistance of the connecting wiring, which is a function of the gauge of the 
wire being used. 

• When developing a RS-485 chain of devices, the last device in the chain 

requires end of line termination.

• RS-485 connection 2-wire, multipoint serial line.

S

EAL

• Water-proof and explosion-proof conduit seals are recommended to prevent 

water accumulation within the enclosure. 

• Seals should be located as close to the device as possible and not more than 

18 inches (46 cm) away. 

• Explosion-proof installations may require an additional seal where conduit 

enters a non-hazardous area. Ensure conformity with local wiring codes.

• When pouring a seal, use a fibre dam to assure proper formation of the seal. 

Seals should never be poured at temperatures below freezing.

• The jacket and shielding of the cable should be stripped back to permit the 

seal to form around the individual wires. This will prevent air, gas and water 
leakage through the inside of the shield and into the enclosure.

• It is recommended that explosion-proof drains and conduit breathers be used. 

In some applications, alternate changes in temperature and barometric 
pressure can cause 'breathing' which allows moist air to enter and circulate 
inside the conduit. Joints in the conduit system are seldom tight enough to 
prevent this 'breathing'.

Connecting Wires 

1. Use a small screw driver to gently press down 

and hold the spring connector open.

2. Insert appropriate wire into open connector 

hole.

3. Release screw driver to secure wire.

Figure 3:  

Internal PCB Boards

Option Board/RS-485 Modbus RTU 
Communication Board
(refer to Figure 4 fo
details).

Sensor Board 
(refer to Figure 4 for 
details).

Terminal Board
(refer to Figure 4 for 
details).

Содержание MAN-0069

Страница 1: ...4 20 mA FIRE HEAD with Analog RS 485 Modbus AD CONTROLLER User Manual Part Number MAN 0069 Rev 2 May 2006...

Страница 2: ......

Страница 3: ...ed inspected and calibrated prior to shipment Failures can occur which are beyond the control of the manufacturer Failures can be minimized by adhering to the operating and maintenance instructions he...

Страница 4: ...sitions Current Output 5 MODBUS Termination 6 Figure 8 Modbus Termination Jumpers 6 Step 4 Operate 7 Figure 9 Controller Functionality 7 The Main Menu 8 Accessing the Main Menu 8 Calibration Button 8...

Страница 5: ...ps B C and D for hazardous applications It was designed for either a 1 man intrusive calibration or 2 man non intrusive calibration The Manual The manual has been designed to make installation of the...

Страница 6: ...Figure 2 Components Note Refer to the specific Fire Head manual for components LOCATE CONTROLLER FIRE HEAD Fire Head Locate Fire Heads as per the manual provided with the specific product Controller T...

Страница 7: ...eals are recommended to prevent water accumulation within the enclosure Seals should be located as close to the device as possible and not more than 18 inches 46 cm away Explosion proof installations...

Страница 8: ...be used for separations up to 2000 feet Consult the factory if a greater separation distance is required Ensure the appropriate wire is used for Class 1 Division 1 hazardous applications Note If the...

Страница 9: ...ote Unless otherwise specified all models ship with non Isolated current output Figure 7 Jumper Positions Current Output RST 24V COM 4 20 ISO Power to Monitor Supply Terminal Board Power Terminal Stri...

Страница 10: ...ad 6 MODBUS TERMINATION Devices are networked in a daisy chain The device located at the end of the chain requires end of line termination Place both jumpers over the pins as shown in Figure 8 for end...

Страница 11: ...s messages and prompts Refer to Table 4 Current Output LEDs and Display Messages on page 10 Pull Here knob unscrew the two screws and gently pull to remove faceplate Removal allows access to the PCB b...

Страница 12: ...lock position to make a selection select YES Main Menu Functionality 1 Ensure that the Controller has been turned on and no fault is present 2 Hold the magnet against the Reed Switch or press and hold...

Страница 13: ...3 Wait for the prompt New Address YES and press the Calibration Button or use the Reed Switch to select Step 4 Use the Calibration Button or Reed Switch to select each of three numbers in the new add...

Страница 14: ...u l t Start Delay 90 seconds 3 0 mA Blip S t a r t D e l a y M i l l e n n i u m Normal Operation 4 0 mA Blip N O R M Background radiation source UV 6 0 mA Flash U V P r e s e n t Background radiatio...

Страница 15: ...re specific you are regarding the problem the quicker our Service department can determine and correct the problem 3 A company name contact name and telephone number 4 A Purchase Order from your compa...

Страница 16: ...ver 2 Turn the power to the detector off 3 Unscrew both the knobs marked Pull Here 4 Lift Controller faceplate from Housing and allow to hang from ribbon cable 5 Unscrew the two metal standoffs 6 Care...

Страница 17: ...for an indefinite period of time followed by a sudden failure To eliminate potential ESD damage review the following guidelines Handle boards by metal shields taking care not to touch electronic comp...

Страница 18: ...1 09 0 63 1250 12 70 7 99 5 03 3 16 1 99 1 25 0 79 1500 15 20 9 58 6 02 3 79 2 38 1 50 0 94 1750 17 80 11 20 7 03 4 42 2 78 1 75 1 10 2000 20 30 12 80 8 03 5 05 3 18 2 00 1 26 2250 22 80 14 40 9 03 5...

Страница 19: ...at units power terminals Enclosure Material Powder coated Copper Free Cast Aluminum Certifications CSA and NRTL C certified for hazardous locations Class I Division 1 Groups B C and D Temperature T5...

Страница 20: ...Net Safety Monitoring Inc 2721 Hopewell Place NE Calgary Alberta Canada T1Y 7J7 Telephone 403 219 0688 Fax 403 219 0694 E mail netsafe net safety com www netsafety com Distributed by...

Отзывы: