background image

Net Safety Monitoring Inc

Modbus Controller & 4-20 Fire Head

10

STEP 5 — M

ONITOR

There are a variety of ways to indicate the status of the connected detectors: 
current output, LEDs and Display Messages.

Table 4:  

Current Output, LEDs and Display Messages 

RTU R

EGISTERS

Register 40001 = RTU Output (read only)
Register 40002 = RTU Status (read only)
Register 40101 = Reset latched relays (write)

Note:

Many registers are used by the controller. Please do not write outside 
the three registers.

LED Status

Current 

O/P

Status LED

(red)       (green)

Display Messages

Internal Power Fault or 
system power out of range

1.0 mA

Fast 

Flash

-

S e n s o r   F a u l t

Automatic or manual VI 
Test Failure

2.0 mA

Fast 

Flash

-

V I   F a u l t

Start Delay (90 seconds)

3.0 mA

Blip

-

S t a r t   D e l a y  
M i l l e n n i u m

Normal Operation

4.0 mA

-

Blip

N O R M

Background radiation 
source UV

6.0 mA

Flash

-

U V   P r e s e n t

Background radiation 
source IR

8.0 mA

Flash

-

I R   P r e s e n t

Early Warning - 
Intermittent radiation 
detected

16.0 mA Flash

-

W a r n i n g ! !

Fire confirmed

20.0 mA Flash

-

F I R E   ( f l a s h e s )

Writing to memory

-

-

Solid

B U S Y

Table 5:  

RTU Output Register (40001) Read Only (binary)

RTUfire_power_up

0x0001

power up delay

RTUfire_vi_fault

0x0002

failed self test

RTUfire_normal

0x0004

normal operation

RTUfire_fault

0x0008

fire head fault

RTUfire_ir_present

0x0010

background IR

RTUfire_uv_present

0x0020

background UV

RTUfire_warning

0x0040

Warning Fire

RTUfire_alarm

0x0080

Fire present

Table 6:  

RTU Status Register (40002) Read Only (binary)

RTUstat_fault

0x0001

fault (sensor...)

RTUstat_mem_error

0x4000

memory error

Содержание MAN-0069

Страница 1: ...4 20 mA FIRE HEAD with Analog RS 485 Modbus AD CONTROLLER User Manual Part Number MAN 0069 Rev 2 May 2006...

Страница 2: ......

Страница 3: ...ed inspected and calibrated prior to shipment Failures can occur which are beyond the control of the manufacturer Failures can be minimized by adhering to the operating and maintenance instructions he...

Страница 4: ...sitions Current Output 5 MODBUS Termination 6 Figure 8 Modbus Termination Jumpers 6 Step 4 Operate 7 Figure 9 Controller Functionality 7 The Main Menu 8 Accessing the Main Menu 8 Calibration Button 8...

Страница 5: ...ps B C and D for hazardous applications It was designed for either a 1 man intrusive calibration or 2 man non intrusive calibration The Manual The manual has been designed to make installation of the...

Страница 6: ...Figure 2 Components Note Refer to the specific Fire Head manual for components LOCATE CONTROLLER FIRE HEAD Fire Head Locate Fire Heads as per the manual provided with the specific product Controller T...

Страница 7: ...eals are recommended to prevent water accumulation within the enclosure Seals should be located as close to the device as possible and not more than 18 inches 46 cm away Explosion proof installations...

Страница 8: ...be used for separations up to 2000 feet Consult the factory if a greater separation distance is required Ensure the appropriate wire is used for Class 1 Division 1 hazardous applications Note If the...

Страница 9: ...ote Unless otherwise specified all models ship with non Isolated current output Figure 7 Jumper Positions Current Output RST 24V COM 4 20 ISO Power to Monitor Supply Terminal Board Power Terminal Stri...

Страница 10: ...ad 6 MODBUS TERMINATION Devices are networked in a daisy chain The device located at the end of the chain requires end of line termination Place both jumpers over the pins as shown in Figure 8 for end...

Страница 11: ...s messages and prompts Refer to Table 4 Current Output LEDs and Display Messages on page 10 Pull Here knob unscrew the two screws and gently pull to remove faceplate Removal allows access to the PCB b...

Страница 12: ...lock position to make a selection select YES Main Menu Functionality 1 Ensure that the Controller has been turned on and no fault is present 2 Hold the magnet against the Reed Switch or press and hold...

Страница 13: ...3 Wait for the prompt New Address YES and press the Calibration Button or use the Reed Switch to select Step 4 Use the Calibration Button or Reed Switch to select each of three numbers in the new add...

Страница 14: ...u l t Start Delay 90 seconds 3 0 mA Blip S t a r t D e l a y M i l l e n n i u m Normal Operation 4 0 mA Blip N O R M Background radiation source UV 6 0 mA Flash U V P r e s e n t Background radiatio...

Страница 15: ...re specific you are regarding the problem the quicker our Service department can determine and correct the problem 3 A company name contact name and telephone number 4 A Purchase Order from your compa...

Страница 16: ...ver 2 Turn the power to the detector off 3 Unscrew both the knobs marked Pull Here 4 Lift Controller faceplate from Housing and allow to hang from ribbon cable 5 Unscrew the two metal standoffs 6 Care...

Страница 17: ...for an indefinite period of time followed by a sudden failure To eliminate potential ESD damage review the following guidelines Handle boards by metal shields taking care not to touch electronic comp...

Страница 18: ...1 09 0 63 1250 12 70 7 99 5 03 3 16 1 99 1 25 0 79 1500 15 20 9 58 6 02 3 79 2 38 1 50 0 94 1750 17 80 11 20 7 03 4 42 2 78 1 75 1 10 2000 20 30 12 80 8 03 5 05 3 18 2 00 1 26 2250 22 80 14 40 9 03 5...

Страница 19: ...at units power terminals Enclosure Material Powder coated Copper Free Cast Aluminum Certifications CSA and NRTL C certified for hazardous locations Class I Division 1 Groups B C and D Temperature T5...

Страница 20: ...Net Safety Monitoring Inc 2721 Hopewell Place NE Calgary Alberta Canada T1Y 7J7 Telephone 403 219 0688 Fax 403 219 0694 E mail netsafe net safety com www netsafety com Distributed by...

Отзывы: