In some applications, it is necessary for the Controller to be mounted in a non-
standard orientation. To accommodate such installations and ensure that the
display will appear at the correct angle for viewing, the PCB Assembly can be
rotated inside the Controller.
Figure 10:
Non-standard Orientation
Note:
Ensure orientation allows for connections and excess wire within Controller
Housing.
WARNING:
See Appendix D, "Electrostatic Sensitive Device (ESD)", on
page 13 for handling instructions of electronic components.
Rotate PCB Assembly
1. Remove the Controller’s Housing Cover.
2. Turn the power to the detector off.
3. Unscrew both the knobs marked "Pull Here".
4. Lift Controller faceplate from Housing and allow to hang from ribbon
cable.
5. Unscrew the two metal standoffs.
6. Carefully remove the PCB Assembly from the Housing.
7. The Rotator plate is secured to the bottom of the Housing and is accessible
after the PCB Assembly has been removed.
8. Rotate the PCB Assembly to desired position and line up the standoffs with
the mounting holes.
9. Insert standoffs in the appropriate horizontal or vertical mounting holes.
10. Tighten standoffs to secure PCB Assembly.
11. Replace faceplate and tighten "Pull Here" knobs.
12. Return power to detector and replace Housing Cover.
Figure 11:
Rotate PCB Assembly
Standoffs
PCB Assembly
Faceplate
Ribbon cable
Vertical Mounting Holes
(Insert Standoffs)
Horizontal Mounting
(Insert Standoffs)
Holes