background image

Net Safety Monitoring Inc

Modbus Controller & 4-20 Fire Head

4

W

IRING

C

ONTROLLER

WARNING:

 

Power to the unit must be OFF before wiring.

1. Once the Controller’s Housing Cover is removed, connect the Fire Head to 

the Junction Box, the Junction Box to the Controller and the Output 
Terminals to the output signal wires.

2. Replace the Controller’s Housing Cover and turn Controller On.
3. Ensure display reads 

Start Delay

, Status LED is Red Slow Flash and 

current output displays 3.0 mA. This is the start-up delay sequence which 
will last approximately 90 seconds.

Shielded copper instrument wire (minimum 18 AWG) should be used for 
separations up to 500 feet. Shielded copper instrument wire (minimum 
16 AWG) should be used for separations up to 2000 feet. Consult the factory if a 
greater separation distance is required. Ensure the appropriate wire is used for 
Class 1/Division 1 hazardous applications.

Note:

If the 4-20 mA signal is not used, connect a jumper between the 4-20 
terminal and the COM terminal on the Terminal Board.

RS-485 Communication

Connect devices in a chain via the Modbus terminals. The last device in the 
chain requires end of line termination (refer to "MODBUS Termination" on 
page 6). 

Figure 4:  

Wiring

Fire Head, Junction Box and Controller

MVI
+24V
COM
4-20

Blu

W

Blk

Red

RST

+24V

COM

4-20

ISO

+24V

SIG

Com -

Shld

Fire Head
Input
to
Junction Box

Internal Ground
(Green Wire)

Cut Shiel

d

Shield

Power
Terminals

Sensor
Terminals

+24V = +24V

Sig = 4-20

n/a

COM = COM

Shld

RST = Remote Reset

+24V = Power +

COM = Power -

4-20 = Current Output

ISO = +24V isolated 4-20 power

Terminals

Modbus RTU

to PLC

A

B

COM

-

Manual Vi Test Button

Содержание MAN-0069

Страница 1: ...4 20 mA FIRE HEAD with Analog RS 485 Modbus AD CONTROLLER User Manual Part Number MAN 0069 Rev 2 May 2006...

Страница 2: ......

Страница 3: ...ed inspected and calibrated prior to shipment Failures can occur which are beyond the control of the manufacturer Failures can be minimized by adhering to the operating and maintenance instructions he...

Страница 4: ...sitions Current Output 5 MODBUS Termination 6 Figure 8 Modbus Termination Jumpers 6 Step 4 Operate 7 Figure 9 Controller Functionality 7 The Main Menu 8 Accessing the Main Menu 8 Calibration Button 8...

Страница 5: ...ps B C and D for hazardous applications It was designed for either a 1 man intrusive calibration or 2 man non intrusive calibration The Manual The manual has been designed to make installation of the...

Страница 6: ...Figure 2 Components Note Refer to the specific Fire Head manual for components LOCATE CONTROLLER FIRE HEAD Fire Head Locate Fire Heads as per the manual provided with the specific product Controller T...

Страница 7: ...eals are recommended to prevent water accumulation within the enclosure Seals should be located as close to the device as possible and not more than 18 inches 46 cm away Explosion proof installations...

Страница 8: ...be used for separations up to 2000 feet Consult the factory if a greater separation distance is required Ensure the appropriate wire is used for Class 1 Division 1 hazardous applications Note If the...

Страница 9: ...ote Unless otherwise specified all models ship with non Isolated current output Figure 7 Jumper Positions Current Output RST 24V COM 4 20 ISO Power to Monitor Supply Terminal Board Power Terminal Stri...

Страница 10: ...ad 6 MODBUS TERMINATION Devices are networked in a daisy chain The device located at the end of the chain requires end of line termination Place both jumpers over the pins as shown in Figure 8 for end...

Страница 11: ...s messages and prompts Refer to Table 4 Current Output LEDs and Display Messages on page 10 Pull Here knob unscrew the two screws and gently pull to remove faceplate Removal allows access to the PCB b...

Страница 12: ...lock position to make a selection select YES Main Menu Functionality 1 Ensure that the Controller has been turned on and no fault is present 2 Hold the magnet against the Reed Switch or press and hold...

Страница 13: ...3 Wait for the prompt New Address YES and press the Calibration Button or use the Reed Switch to select Step 4 Use the Calibration Button or Reed Switch to select each of three numbers in the new add...

Страница 14: ...u l t Start Delay 90 seconds 3 0 mA Blip S t a r t D e l a y M i l l e n n i u m Normal Operation 4 0 mA Blip N O R M Background radiation source UV 6 0 mA Flash U V P r e s e n t Background radiatio...

Страница 15: ...re specific you are regarding the problem the quicker our Service department can determine and correct the problem 3 A company name contact name and telephone number 4 A Purchase Order from your compa...

Страница 16: ...ver 2 Turn the power to the detector off 3 Unscrew both the knobs marked Pull Here 4 Lift Controller faceplate from Housing and allow to hang from ribbon cable 5 Unscrew the two metal standoffs 6 Care...

Страница 17: ...for an indefinite period of time followed by a sudden failure To eliminate potential ESD damage review the following guidelines Handle boards by metal shields taking care not to touch electronic comp...

Страница 18: ...1 09 0 63 1250 12 70 7 99 5 03 3 16 1 99 1 25 0 79 1500 15 20 9 58 6 02 3 79 2 38 1 50 0 94 1750 17 80 11 20 7 03 4 42 2 78 1 75 1 10 2000 20 30 12 80 8 03 5 05 3 18 2 00 1 26 2250 22 80 14 40 9 03 5...

Страница 19: ...at units power terminals Enclosure Material Powder coated Copper Free Cast Aluminum Certifications CSA and NRTL C certified for hazardous locations Class I Division 1 Groups B C and D Temperature T5...

Страница 20: ...Net Safety Monitoring Inc 2721 Hopewell Place NE Calgary Alberta Canada T1Y 7J7 Telephone 403 219 0688 Fax 403 219 0694 E mail netsafe net safety com www netsafety com Distributed by...

Отзывы: