5000 Series Dialler
Page 9
RING-DETECT and TEST CALL OPTIONS.
P 44 E option E
1 =
Enable Auto-Test calls when Armed
2 =
Enable Auto-Test calls when Disarmed
3 =
Enable Call-Back calls when Armed.
4 =
Enable Call-Back calla when Disarmed.
5 =
Enable Auto-Answer capability when Armed.
6 =
Enable Auto-Answer capability when Disarmed.
7 =
Enable the panel to be Armed on receipt of the Command tone. If already Armed,
the tone will be ignored unless it has been programmed to drive the Auxiliary
output as well. (See P41E option 4).
None, one or all of the above options may be chosen and the default is none.
Select both options 1 and 2 to enable Auto-Test calls always.
TIME BETWEEN AUTOMATIC TEST CALLS.
P 45 E time E
Automatic Test Calls are identified as such at the Central Station and are used to check
the integrity of the Dialler and the telephone line. To use the facility the Test alarm
(P62E) must be enabled by assigning it a channel number.
Then set the time between Test Calls using this option.
This time defaults to 168 hours but may be set from half-hourly to 250 hours.
A conversion table of hours to days is shown below.
0 = half-hourly
24 = 1 day
120 = 5 days
1 = 1 hour
48 = 2 days
144 = 6 days
2 = 2 hours
72 = 3 days
168 = 7 days
9 = 9 hours
96 = 4 days
240 = 10 days
TIME REMAINING BEFORE FIRSI' TEST CALL.
P 46 E time E
After installation, set this time to position the first Automatic Test Call at the required time.
This option defaults to 0 hours but may be set from 1 to 250 hours.
The time commences on Exit from installation Programme mode.
DOUBLE RINGS NEEDED FOR CALL-BACK.
P 47 E number E
This option defines the number of double rings needed to make the Dialler Call-Back,
ie. to make it send a Test Call immediately and hence before the time defined in P45E.
The number may be set from 1 to 13 and the default is 3 double rings.