SKS - Steam to Steam Humidifier
Installation Instructions and User Manual
20
Stage 5 – Water Drain Connection
Water Drain installation must conform to local codes and regulations.
Any installation work must be carried out by suitably qualified personnel.
Water Drain
Specification
Water Drain temperature:
+60˚C
Model
Water Drain Outlet
Connection Size
SKS-XXXX
Ø20mm
Water Drain
Installation
Water drain outlet connection must be connected to drain pipe of sufficient size.
It is recommend to use Ø20mm minimum standard copper hydraulic pipes.
Water main drain and drip pan must be kept separate to the open drain. Do not
connect the main drain and the drip pan before the open drain.
Minimum water drain pipe gradient must be 6.5mm per 300mm horizontal run.
No drain trap is required on the main drain.
(Fig. 18)
!
SKS
Ø 22mm (¾’’)
Building water drain
Ø 28mm minimum