SKS - Steam to Steam Humidifier
Installation Instructions and User Manual
11
Stage 2 – Steam Distribution Pipes Positioning & Installation
Fundamental
Design
Concepts
1.
Maximum steam velocity in a pipe must not exceed 12m/s velocity.
2.
Minimum steam pipe gradient must be 7
˚ i.e. 125mm rise in 1m run.
3.
The lowest point of any steam hose or rigid pipe must be the humidifier. A steam
separator (S trap) must be installed higher than the static pressure of the system by
at least 50mm.
4.
Total length of the steam hose or rigid pipe must not exceed 5 m.
5.
Whenever possible use rigid copper piping, flexible steam hose can be used for
short runs or for interconnecting between rigid pipe runs, ensure that there is no
kink in the flexible hose.
When using rigid copper pipe, insulation must be used to diminish condensation
build up.
(Fig. 7)
(Fig. 8)
6.
Connection pipe sizes between SKS and steam distributor in the duct must be :
108mm up to 240kg/h
133mm up to 255kg/h
7.
All SKS/CHP Humidifiers must use Multi-Steam.
8.
All Humidifiers above 240kg/h must use 2 Multi-Steam units per Air Handling Unit
(AHU) or air duct with an equal duty split to each Multi-Steam
!
Min. 7°
Correct Installation
humidifier with
Multisteam.
Static pressure
+ 50mm
SKS
Incorrect Installation
SKS