SKS - Steam to Steam Humidifier
Installation Instructions and User Manual
14
Stage 2
– Steam Distribution Pipes Positioning & Installation
SKS-667-CHP
(Fig. 13)
Two Ø125mm steam outlets to feed pipe must be connected to two Multi-Steam with
a suitable reduction at the lowest point to allow a Ø15mm condensate drain from the
main steam supply.
If the two Ø15mm condensate pipes are connected, the common condensate drain
must be Ø20mm.
Ø15mm
Static pressure
+ 50mm
Ø22mm
Min. 7° pipe slope
Insulated pipe
Air Duct
Ø133mm (x2)
Total length of steam conduit
should not exceed 5m