SKG Steam Humidifier
BACnet® Communication Module User Guide
11
SKG Humidifier Object Table
For tank 1:
type inst Object_Name
Description
range of Present_Value
W?
AI
101
Water_Temp1
Water Temperature 1
0-260 °C or 32-500 °F
AI
102
Chimney_Temp1
Chimney Temperature 1
0-260 °C or 32-500 °F
AI
103
Water_Level1
Water level 1
0-120%
AI
104
Burner_Demand1
Burner Demand 1
0.0 - 100.0%
AI
105
Op_Timer_Total1
Operation Timer 1 (Total
time)
1-1677215Hrs
AI
106
Op_Timer1
Operation Timer 1
1-5000Hrs
AI
107
Delay_Autodrain1
Delay until Auto-drain 1
1-100Hrs
AI
108
Foam_Probe_Sensr1
Foam Probe Sensor 1
0-255
AI
109
Burner_Fan_Speed1
Burner Fan Speed 1
0-1000Hz
type inst Object_Name
Description
range of Present_Value
W?
AV
101
Water_Temp_Off1
Water Temperature offset
1
±0-20 °C or ±0-40 °F
W
AV 102 Chimney_Temp_Off1 Chimney
Temperature
offset 1
±0-20 °C or ±0-40 °F
W
AV
103
Water_Level_Off1
Water Level offset 1
±0-20%
W
type inst Object_Name
Description
range of Present_Value
W?
-- -- --
Alarm
1:
-
BV
101
OverTemp_Cont_ON1
Over temperature contact
ON 1
0=Normal, 1=Alarm
W
BV
102
Bad_Fill_Tank1
Defective filling tank 1
0=Normal, 1=Alarm
W
BV 103 Bad_Refill_Tank1
Defective refill tank 1(too
long)
0=Normal, 1=Alarm
W
BV
104
Bad_Drain_Tank1
Defective draining tank 1
0=Normal, 1=Alarm
W
BV
105
Bad_Burner_Fan1
Defective Burner Fan 1
0=Normal, 1=Alarm
W
BV
106
Bad_Burner_Gas1
Defective Burner Gas
1(Locked)
0=Normal, 1=Alarm
W
BV
107
Input_Volt_Low1
Input voltage 1 too low
0=Normal, 1=Alarm
W
BV
108
Power_Fuse_Open1
Power Fuse 1 open
(24VAC)
0=Normal, 1=Alarm
W
-- -- --
Alarm
2:
-
BV
109
Tank_Sens_Bad1
Tank sensor 1 defective
0=Normal, 1=Alarm
W
BV
110
Chim_Sens_Bad1
Chimney sensor 1
defective
0=Normal, 1=Alarm
W
BV
111
H2OLvl_Prb_Bad1
Water level probe 1 defect
0=Normal, 1=Alarm
W
BV
112
Foam_Sens_ON1
Foam Sensor 1 ON
0=Normal, 1=Alarm
W
BV
113
OverFlow_DripPan1
Over Flow, Drip Pan 1
0=Normal, 1=Alarm
W
BV
114
Tank_Temp_Low1
Tank temper. 1 Too low
(freeze)
0=Normal, 1=Alarm
W
BV
115
Tank_Temp_Hi1
Tank temperature 1 too
high
0=Normal, 1=Alarm
W
BV
116
Chimney_Temp_Hi1
Chimney temperature 1
too high
0=Normal, 1=Alarm
W