background image

 

SKG Steam Humidifier 

BACnet® Communication Module User Guide

 

 

20 

Configuration 

Getting Started 

The four configurable BACnet Device Object properties have two sets of “default” settings, the factory setting 
and the configuration mode setting and are identified in the following table: 
 
 

property 

factory value 

configuration mode value 

Device_Instance 153000* 

153000* 

Object_Name “NEPSKGHumidifier153000” “NEPSKGHumidifier153000” 
Max_Master 127 

127 

MSTP_MACaddress 0 

254 

 
* Note: These values are NEP’s BACnet Vendor_Identifier*1000. 
 
Prior to the first time the NEPICSKG is powered on, you’ll have to know two things: 
 
What’s the baud rate of the MS/TP network? 
Is there already an MS/TP unit on that network with the MAC address=0 and the Device Instance=153000? 
 
Once the answer to Question 1 is known, the dip switches 2 and 3 must be set up accordingly.  
 
If the answer to Question 2 is no (there is no MS/TP MAC address 0), then you can start up the NEPICSKG with 
the dip switch 1 in the OFF (operational) position. In this mode, the factory settings are in effect and the 
NEPICSKG will be MS/TP token-passing master with a MAC address=0 and Device Instance=153000. 
 
If the answer to Question 2 is yes (there already is an MS/TP MAC address 0 and/or there already is a Device 
Instance 153000), then you will need to start up the NEPICSKG with the dip switch 1 in the ON (configuration) 
position. In this mode, the configuration mode settings are in effect and the NEPICSKG will be MS/TP non-
token-passing slave with a MAC address 254. 
Configuring in the Operational Mode 
The NEPICSKG can be configured from a BACnet client device using the BACnet WriteProperty service at any 
time, while in the operational mode. In other words, the Device_Instance, Object_Name, Max_Master and 

MSTP_MACaddress

 can be changed “hot” with the changes taking effect immediately and without having to 

restart the NEPICSKG. 

Содержание SKG Series

Страница 1: ...Gas Fired Humidifier SKG Series BACnet Communication Module User Guide SKG BACNET Rev 060803...

Страница 2: ......

Страница 3: ...t 1 Introduction BACnet Requirements 2 Introduction 2 BACnet Requirements 2 Device Object 3 Objects 4 SKG Humidifier Object Table 8 Configuration 19 Personal notes 23 Other related documents 1 Install...

Страница 4: ...hrough WriteProperty service to the device object A default MAC address of 254 shall be recognized when a configuration dip switch is set to configure mode Two other dip switches shall determine MS TP...

Страница 5: ...s unavailable and is unreliable Firmware_Revision currently 1 00 Application_Software_Version currently 1 00 Protocol_Version always 1 Protocol_Revision always 2 Max_APDU_Length_Accepted always 107 Se...

Страница 6: ...puts AI Analog Values AV 6 Binary Inputs BI 16 Binary Values BV 1 Multistate Input MSI So the number of objects vs the number of Tanks are listed in the following table Number of Tanks Number of Objec...

Страница 7: ...is set this property s value is unreliable_other otherwise it s no_fault_detected Out_of_Service Always false Units see Object Table Analog Values property value W Object_Identifier see Object Table...

Страница 8: ...no_fault_detected Out_of_Service Always normal Polarity see Object Table Active_Text see Object Table Inactive_Text see Object Table Binary Values property value W Object_Identifier see Object Table...

Страница 9: ...property s value is unreliable_other otherwise it s no_fault_detected Out_of_Service Always normal Number_of_States see Object Table Multistate Values property value W Object_Identifier see Object Ta...

Страница 10: ...dity_Off Room Humidity offset 0 10 0 RH W AV 4 Duct_Humidity Duct Humidity 0 100 RH W AV 5 Duct_Humidity_Off Duct Humidity offset 0 10 0 RH W AV 6 Outside_Temp Outside Temperature 40 40 C or 40 104 F...

Страница 11: ...VDC 0 OFF 1 ON Alarm main board BI 12 Interlock_In_Open Interlock input open 0 Normal 1 Alarm BI 13 High_Hum_In_Duct High humidity level in the duct 0 Normal 1 Alarm BI 14 Input_Voltage_Low Input volt...

Страница 12: ...ion_Mode Operation Mode 1 Set unit Off 2 Set unit On 3 Set unit in drain mode W MSV 3 Unit_Display_Lang Unit Display Language 1 English Default 2 French 3 Spanish W MSV 4 SP_Source Setpoint Source 1 L...

Страница 13: ...range of Present_Value W Alarm 1 BV 101 OverTemp_Cont_ON1 Over temperature contact ON 1 0 Normal 1 Alarm W BV 102 Bad_Fill_Tank1 Defective filling tank 1 0 Normal 1 Alarm W BV 103 Bad_Refill_Tank1 Def...

Страница 14: ...1 Burner Valve 1 0 OFF 1 ON BI 102 Burner_Fan1 Burner Fan 1 0 OFF 1 ON BI 103 Fill_Tank1 Fill Tank 1 0 OFF 1 ON BI 104 Drain_Tank1 Drain Tank 1 0 OFF 1 ON BI 105 Water_Level_OK1 Water Level 1 Okay 0 O...

Страница 15: ...range of Present_Value W Alarm 1 BV 201 OverTemp_Cont_ON2 Over temperature contact ON 2 0 Normal 1 Alarm W BV 202 Bad_Fill_Tank2 Defective filling tank 2 0 Normal 1 Alarm W BV 203 Bad_Refill_Tank2 Def...

Страница 16: ...2 Burner Valve 2 0 OFF 1 ON BI 202 Burner_Fan2 Burner Fan 2 0 OFF 1 ON BI 203 Fill_Tank2 Fill Tank 2 0 OFF 1 ON BI 204 Drain_Tank2 Drain Tank 2 0 OFF 1 ON BI 205 Water_Level_OK2 Water Level 2 Okay 0 O...

Страница 17: ...range of Present_Value W Alarm 1 BV 301 OverTemp_Cont_ON3 Over temperature contact ON 3 0 Normal 1 Alarm W BV 302 Bad_Fill_Tank3 Defective filling tank 3 0 Normal 1 Alarm W BV 303 Bad_Refill_Tank3 Def...

Страница 18: ...3 Burner Valve 3 0 OFF 1 ON BI 302 Burner_Fan3 Burner Fan 3 0 OFF 1 ON BI 303 Fill_Tank3 Fill Tank 3 0 OFF 1 ON BI 304 Drain_Tank3 Drain Tank 3 0 OFF 1 ON BI 305 Water_Level_OK3 Water Level 3 Okay 0 O...

Страница 19: ...range of Present_Value W Alarm 1 BV 401 OverTemp_Cont_ON4 Over temperature contact ON 4 0 Normal 1 Alarm W BV 402 Bad_Fill_Tank4 Defective filling tank 4 0 Normal 1 Alarm W BV 403 Bad_Refill_Tank4 Def...

Страница 20: ...4 Burner Valve 4 0 OFF 1 ON BI 402 Burner_Fan4 Burner Fan 4 0 OFF 1 ON BI 403 Fill_Tank4 Fill Tank 4 0 OFF 1 ON BI 404 Drain_Tank4 Drain Tank 4 0 OFF 1 ON BI 405 Water_Level_OK4 Water Level 4 Okay 0 O...

Страница 21: ...F 38400 OFF ON 76800 ON ON Please note that you must restart the unit in order for a change of baud rate to take effect Configurable BACnet Properties The following four BACnet properties are configur...

Страница 22: ...gly If the answer to Question 2 is no there is no MS TP MAC address 0 then you can start up the NEPICSKG with the dip switch 1 in the OFF operational position In this mode the factory settings are in...

Страница 23: ...e care must be taken in setting the MS TP MAC address and Max_Master property First the MAC address must be unique on the entire MS TP network However having a unique MAC address and a high baud rate...

Страница 24: ...finds the right one to pass the token to As a general guideline the most efficient set up for an MS TP network is one in which the units are consecutively numbered starting at MAC address 0 and all ha...

Страница 25: ...SKG Steam Humidifier BACnet Communication Module User Guide 23 Personal notes...

Страница 26: ...nal Environmental Products Ltd 400 Bd Lebeau Montreal Qc H4N 1R6 CANADA www neptronic com Toll free in North America 1 800 361 2308 Tel 1 514 333 1433 Fax 1 514 333 3163 Customer service Fax 514 333 1...

Отзывы: