background image

 

SKG Steam Humidifier 

BACnet® Communication Module User Guide

 

 

21 

Configuration 

Configuring in the Configuration Mode 

If the NEPICSKG is put into the configuration mode while it is “hot”, the NEPICSKG will be automatically reset 
with the Device_Instance, Object_Name, Max_Master and 

MSTP_MACaddress

 all containing the 

configuration 

mode values

. In this mode, the NEPICSKG will not act as an MS/TP token-passer and will be silent until it is 

addressed by a BACnet client. As a side effect, it will also not be able to respond to BACnet WhoIs services 
with Iam services, so BACnet clients will not be able to find out its Device_Instance automatically. In the 
configuration mode, any of the above properties can be changed by using either the default Device_Instance or 
the wild card Device_Instance (4194303 decimal or 0x3FFFFF hex). Use of the wild card Device_Instance 
obviates the need to know the NEPICSKG’s real Device_Instance in case it conflicts with another Device in the 
system. While in the configuration mode, only the Device Object is available to BACnet clients through the 
ReadProperty and Write Property services. All other objects (i.e. AI’s, etc) are not available. 
 
As an alternative to using the BACnet WriteProperty service to change the Device_Instance and/or the 

MSTP_MACaddress

, the SK300’s keypad can be used to change those two properties, but only while in the 

configuration mode.  
 
Changes to the Device Object, whether made by using the WriteProperty of the keypad, do not take effect until 
the NEPICSKG is restarted in the operational mode. 
 
Selecting the MS/TP MAC address and Max_Master 
Some care must be taken in setting the MS/TP MAC address and Max_Master property.  
 
First, the MAC address must be unique on the entire MS/TP network. However, having a unique MAC address 
and a high baud rate does not guarantee efficient operation of the NEPICSKG (or other MS/TP units for that 
matter) on the MS/TP network. Some MAC address and Max_Master combinations are more efficient than 
others. BACnet requires token-passing units to occasionally “poll” for other masters based on the value of MAC 
address and Max_Master. So, a “poor” combination of MAC addresses and Max_Masters can lead to slow 
networks in which there’s a lot of wasted time polling for masters that are not present and never will be. In fact, 
unless there are 126 other units on the MS/TP network, the default Max-Master=127 is most likely a poor choice 
for the NEPICSKG. Having said that, Max-Master=127 has been chosen as the default to insure that any 
master, specifically a BACnet client, can be found when the NEPICSKG is first started. 
 
So, considering the following simple two-unit examples: 

Example 1: 

 MAC=0. 

Max_Master=127 

 MAC=1, 

Max_Master=127 

 
This example is slow and inefficient because both Max_Master=127. Everytime either unit is required to find 
another master units it has to poll 126 units until it finds the right one to pass the token to. 

Example 2: 

 MAC=0. 

Max_Master=5 

 MAC=5, 

Max_Master=5 

 
This example is better but is still slower than it could be. The Max_Master is set to the most efficient value, 
however because of the gap between the two MAC addresses, each unit must poll 4 units until it finds the right 
one to pass the token to. 

Example 3: 

 MAC=0. 

Max_Master=1 

 MAC=2, 

Max_Master=2 

 
This example is actually an incorrect configuration, in that MAC=0 will never find MAC=2 because it will never 
poll for the master MAC address=2. 

Содержание SKG Series

Страница 1: ...Gas Fired Humidifier SKG Series BACnet Communication Module User Guide SKG BACNET Rev 060803...

Страница 2: ......

Страница 3: ...t 1 Introduction BACnet Requirements 2 Introduction 2 BACnet Requirements 2 Device Object 3 Objects 4 SKG Humidifier Object Table 8 Configuration 19 Personal notes 23 Other related documents 1 Install...

Страница 4: ...hrough WriteProperty service to the device object A default MAC address of 254 shall be recognized when a configuration dip switch is set to configure mode Two other dip switches shall determine MS TP...

Страница 5: ...s unavailable and is unreliable Firmware_Revision currently 1 00 Application_Software_Version currently 1 00 Protocol_Version always 1 Protocol_Revision always 2 Max_APDU_Length_Accepted always 107 Se...

Страница 6: ...puts AI Analog Values AV 6 Binary Inputs BI 16 Binary Values BV 1 Multistate Input MSI So the number of objects vs the number of Tanks are listed in the following table Number of Tanks Number of Objec...

Страница 7: ...is set this property s value is unreliable_other otherwise it s no_fault_detected Out_of_Service Always false Units see Object Table Analog Values property value W Object_Identifier see Object Table...

Страница 8: ...no_fault_detected Out_of_Service Always normal Polarity see Object Table Active_Text see Object Table Inactive_Text see Object Table Binary Values property value W Object_Identifier see Object Table...

Страница 9: ...property s value is unreliable_other otherwise it s no_fault_detected Out_of_Service Always normal Number_of_States see Object Table Multistate Values property value W Object_Identifier see Object Ta...

Страница 10: ...dity_Off Room Humidity offset 0 10 0 RH W AV 4 Duct_Humidity Duct Humidity 0 100 RH W AV 5 Duct_Humidity_Off Duct Humidity offset 0 10 0 RH W AV 6 Outside_Temp Outside Temperature 40 40 C or 40 104 F...

Страница 11: ...VDC 0 OFF 1 ON Alarm main board BI 12 Interlock_In_Open Interlock input open 0 Normal 1 Alarm BI 13 High_Hum_In_Duct High humidity level in the duct 0 Normal 1 Alarm BI 14 Input_Voltage_Low Input volt...

Страница 12: ...ion_Mode Operation Mode 1 Set unit Off 2 Set unit On 3 Set unit in drain mode W MSV 3 Unit_Display_Lang Unit Display Language 1 English Default 2 French 3 Spanish W MSV 4 SP_Source Setpoint Source 1 L...

Страница 13: ...range of Present_Value W Alarm 1 BV 101 OverTemp_Cont_ON1 Over temperature contact ON 1 0 Normal 1 Alarm W BV 102 Bad_Fill_Tank1 Defective filling tank 1 0 Normal 1 Alarm W BV 103 Bad_Refill_Tank1 Def...

Страница 14: ...1 Burner Valve 1 0 OFF 1 ON BI 102 Burner_Fan1 Burner Fan 1 0 OFF 1 ON BI 103 Fill_Tank1 Fill Tank 1 0 OFF 1 ON BI 104 Drain_Tank1 Drain Tank 1 0 OFF 1 ON BI 105 Water_Level_OK1 Water Level 1 Okay 0 O...

Страница 15: ...range of Present_Value W Alarm 1 BV 201 OverTemp_Cont_ON2 Over temperature contact ON 2 0 Normal 1 Alarm W BV 202 Bad_Fill_Tank2 Defective filling tank 2 0 Normal 1 Alarm W BV 203 Bad_Refill_Tank2 Def...

Страница 16: ...2 Burner Valve 2 0 OFF 1 ON BI 202 Burner_Fan2 Burner Fan 2 0 OFF 1 ON BI 203 Fill_Tank2 Fill Tank 2 0 OFF 1 ON BI 204 Drain_Tank2 Drain Tank 2 0 OFF 1 ON BI 205 Water_Level_OK2 Water Level 2 Okay 0 O...

Страница 17: ...range of Present_Value W Alarm 1 BV 301 OverTemp_Cont_ON3 Over temperature contact ON 3 0 Normal 1 Alarm W BV 302 Bad_Fill_Tank3 Defective filling tank 3 0 Normal 1 Alarm W BV 303 Bad_Refill_Tank3 Def...

Страница 18: ...3 Burner Valve 3 0 OFF 1 ON BI 302 Burner_Fan3 Burner Fan 3 0 OFF 1 ON BI 303 Fill_Tank3 Fill Tank 3 0 OFF 1 ON BI 304 Drain_Tank3 Drain Tank 3 0 OFF 1 ON BI 305 Water_Level_OK3 Water Level 3 Okay 0 O...

Страница 19: ...range of Present_Value W Alarm 1 BV 401 OverTemp_Cont_ON4 Over temperature contact ON 4 0 Normal 1 Alarm W BV 402 Bad_Fill_Tank4 Defective filling tank 4 0 Normal 1 Alarm W BV 403 Bad_Refill_Tank4 Def...

Страница 20: ...4 Burner Valve 4 0 OFF 1 ON BI 402 Burner_Fan4 Burner Fan 4 0 OFF 1 ON BI 403 Fill_Tank4 Fill Tank 4 0 OFF 1 ON BI 404 Drain_Tank4 Drain Tank 4 0 OFF 1 ON BI 405 Water_Level_OK4 Water Level 4 Okay 0 O...

Страница 21: ...F 38400 OFF ON 76800 ON ON Please note that you must restart the unit in order for a change of baud rate to take effect Configurable BACnet Properties The following four BACnet properties are configur...

Страница 22: ...gly If the answer to Question 2 is no there is no MS TP MAC address 0 then you can start up the NEPICSKG with the dip switch 1 in the OFF operational position In this mode the factory settings are in...

Страница 23: ...e care must be taken in setting the MS TP MAC address and Max_Master property First the MAC address must be unique on the entire MS TP network However having a unique MAC address and a high baud rate...

Страница 24: ...finds the right one to pass the token to As a general guideline the most efficient set up for an MS TP network is one in which the units are consecutively numbered starting at MAC address 0 and all ha...

Страница 25: ...SKG Steam Humidifier BACnet Communication Module User Guide 23 Personal notes...

Страница 26: ...nal Environmental Products Ltd 400 Bd Lebeau Montreal Qc H4N 1R6 CANADA www neptronic com Toll free in North America 1 800 361 2308 Tel 1 514 333 1433 Fax 1 514 333 3163 Customer service Fax 514 333 1...

Отзывы: