SKG Steam Humidifier
BACnet® Communication Module User Guide
18
SKG Humidifier Object Table
For tank 4:
type inst Object_Name
Description
range of Present_Value
W?
-
-
-
Operating Status Flags:
-
BI
401
Burner_Valve4
Burner Valve 4
0=OFF, 1=ON
BI
402
Burner_Fan4
Burner Fan 4
0=OFF, 1=ON
BI
403
Fill_Tank4
Fill Tank 4
0=OFF, 1=ON
BI
404
Drain_Tank4
Drain Tank 4
0=OFF, 1=ON
BI
405
Water_Level_OK4
Water Level 4 Okay
0=OFF, 1=ON
BI
406
Modulation Stat4
Modulation Status 4
0=OFF, 1=ON
type inst Object_Name
Description
range of Present_Value
W?
MSI
401
Unit_Size4
Unit Size 4
1-100Lbs/Hr or
2-150Lbs/Hr
3-175Lbs/Hr
4-200Lbs/Hr