background image

17 

ACTUATOR 

DIP 1  DIP 2 

FUNCTION 

 

 

INKA 356 – Max. 

Stroke 800 

OFF 

OFF 

RESET 

ON 

OFF 

STROKE 600 

OFF 

ON 

STROKE 700 

ON 

ON 

STROKE 800 

INKA 356 – Max. 

Stroke 1000 

OFF 

OFF 

RESET 

ON 

OFF 

STROKE 800 

OFF 

ON 

STROKE 900 

ON 

ON 

STROKE 1000 

After setting the stroke-end, it is recommended that you perform some test manoeuvres. 
In case of error, the setting can be repeated in order to obtain the desired stroke. If you 
need to execute the RESET procedure, see the instructions below. 

12.2. RESET  Procedure  -  Valid  for  the  single-actuator  configuration, 

Syncro³ configuration or configurations with the K-LOCK electro-lock 

This  procedure  should  be  carried  out  with  the  chain  terminal  (or  terminals,  for 
configurations with several devices) uncoupled from the window sash bracket. 

IMPORTANT:  The  dip-switch  settings  should  be  changed  to  non-powered 
actuators; after each change it is necessary to wait a few seconds (~ 5 sec) before 
restoring the power to the actuators in order for the change to become effective.

 

­

  Set  the  dip-switches  in  the  following  manner: 

DIP  1  OFF

  – 

DIP  2  OFF

.  For 

configurations with several devices (or with the K-LOCK electro-lock), the setting of 
the dip-switches as described above should only be changed for one actuator, and 
the other devices will link to it automatically. 

­

  Supply power to the actuators (either by opening or closing). The initializing phase 

will then start. 

­

  The actuator will start at once (or after about 8 seconds if there is an electro-lock) 

and  perform  a  full  closing  manoeuvre  (chain  completely  retracted)  and  then  an 
opening  manoeuvre  of  about  5  cm.  During  this  phase,  ensure  that  there  are  no 
obstacles  to  the  movement  of  the  chain  and  wait  until  the  closing  manoeuvre  is 
completed on all actuators. 

­

  When  the  operation  is  finished,  each  connected  device  gives  a  flashing  orange 

signal  to  indicate  completion  of  the  RESET  procedure.  Each  device  will  give  a 
different number of flashes to indicate that the access code is received (actuator 1 
→  1  flash  →  pause  →  1  flash  →  pause;  actuator  2  →  2  flashes  →  pause  →  2 
flashes → pause, etc.). 

­

  The  power  supply  to  the  devices  can  now  be  switched  off  and  the  dip-switches 

used to set the desired stroke on all the actuators (as shown in the table on page 
17). 

­

  Couple the chain terminal to the movable sash bracket. 

Once  the  RESET  procedure  is  executed,  at  the  next  complete  closure  the  actuator  will 
repeat the overlap acquisition operation. 
If the K-LOCK electro-lock is present, refer to the respective user and installation manual. 
 

18 

12.3. Overlap acquisition 

The operation that must be carried out to acquire the overlap (after the RESET procedure 
has already been executed) is described below: 

  Assembly of the actuator(s) on the window (as per chapter 10). 

  Electrical connection of the actuator (as per chapter 11). 

  Coupling of the chain terminal(s) to the sash bracket (as per chapter 10). 

  Execute the window closing command. 

  Wait  until  the  window  is  completely  closed.  An  orange  light  will  flash  on  the 

actuator for 3 seconds to indicate that the overlap has been successfully acquired. 

IMPORTANT:  If,  for  any  reason,  the  actuator  fails  to  complete  the  closure  of  the 
window  correctly,  stopping  before  finishing  the  stroke,  the  RESET  and  overlap 
acquisition operation will have to be repeated in that order, until the procedure is 
completed correctly. 

When the window is closed, check that the chain terminal protrudes completely from the 
actuator body by at least a couple millimeters; this ensures that the window is closed well 
and  the  seal  is  compressed  properly,  otherwise  the  window  may  not  be  completely 
closed.  Check  also  that  the  attachments  and  support  brackets  are  solidly  joined  to  the 
window and the screws are tightened properly. 
It is recommended that you avoid using self-threading or self-drilling screws on aluminum 
windows, since they can tear the profile after a few manoeuvres; use metric screws with 
threaded inserts instead 

(see instructions in paragraph 10.2)

12.4. LED Light signals 

If  there  are  any  problems  during  installation  or  operation  of  the  machines,  consult  the 
possible causes listed below: 

WITH RED LED 

Number of 

Flashes 

Type of Error 

Possible Solution 

Current error: 

The actuator has detected an 

overcurrent in the motor. 

Check that there are no obstacles preventing the 

actuator from completing its stroke. Check that the 

actuator is installed correctly. 

Communication error: 

Communication between the 

devices is interrupted, or the 

devices being used have 

undergone the RESET procedure 

separately. 

Check the condition of the connection cables, and 

repeat the RESET procedure if necessary. 

Electro-lock error 

Check the electro-lock. 

Contrasting Dip-switch settings: 

The devices connected to one 

another have conflicting Dip-switch 

settings. 

Check the settings of the various Dip-switches. 

RESET Procedure error: 

The RESET procedure was not 
completed successfully or was 
interrupted. 

Repeat the RESET procedure. 

Содержание INKA 356 Series

Страница 1: ...l units out of their reach Have installation checks performed periodically by qualified personnel from a service centre authorised by the manufacturer Do not use if repair or adjustment is required CA...

Страница 2: ...y or mental capabilities or lacking experience not allow children to play with the fixed controls and keep any remote out of their reach The actuator is destined exclusively for installation indoors F...

Страница 3: ...frame ATTENTION For safety reasons the actuator should not be assembled if dimensions are inferior to those indicated in the table below In the event that the height of the sash should be lower call...

Страница 4: ...in the chapter on TECHNICAL DATA 8 ACTUATOR DIMENSIONS The main overall dimensions of the actuator are given in the table below for bottom and awning sashes However for perfect application on the requ...

Страница 5: ...SECTION Actuator fed at 24V 110V 230V 0 50 mmq 20 m 300 m 1400 m 0 75 mmq 30 m 450 m 2100 m 1 00 mmq 40 m 600 m 2800 m 1 50 mmq 60 m 900 m 4000 m 2 50 mmq 100 m 1500 m 6800 m 4 00 mmq 160 m 2500 m 11...

Страница 6: ...x 2 QL The central dimensions QL x 2 Legend LA Window Sash Width hinges side PA Actuator Attachment Points QL Side Dimensions 10 4 Screw holes for support brackets and sash hinges Screw holes for low...

Страница 7: ...with cable manufactured in accordance with safety standards and protection against radio disturbances SPECIFIC CABLE Before performing the correspondence between the feeder cable and the tension data...

Страница 8: ...s and relax the internal mechanical parts During operation the INKA 356 actuators automatically recognize and memorize the distance between window sash and frame when the window is completely closed T...

Страница 9: ...t the overlap acquisition operation If the K LOCK electro lock is present refer to the respective user and installation manual 18 12 3 Overlap acquisition The operation that must be carried out to acq...

Страница 10: ...ducts and individual parts for 2 years the purchaser possesses proof of purcha payment 20 CHECKING FOR CORRECT ASSEMBLY Check that the window is perfectly closed at corners and that there are no obsta...

Страница 11: ...air by personnel unauthorised by the manufacture shall render the warranty null and invalid The warranty does not cover fragile parts or parts subject to natural wear and tear or corrosion overload ho...

Страница 12: ...agnetica ElectroMagnetic Compatibility Directive EMCD 2014 35 EU Direttiva Bassa Tensione Low Voltage Directive LVD 2011 65 EU Direttiva sulla restrizione dell uso di determinate sostanze pericolose n...

Отзывы: