2. FORMULAS AND RECOMMENDATIONS FOR INSTALLATION 

2.1.  Calculation of opening / closure force

Using  the  formulas  on  this  page,  approximate  calculations  can  be  made  for  the  force 
required  to  open  or  close  the  window  considering  all  the  factors  that  determine  the 
calculation.  

Symbols used for the calculation 

F (Kg) = Force for opening or closing
C (cm) = Opening stroke (actuator stroke)

 
 
 
 
 
 
 
 
 

For horizontal light domes or skylights

 
 

F = 0,54 x P 

(Eventual  weight  of  snow  or  wind  on  the 
cupola should be calculated separately)

 
The chart below shows the force executed from the actuator i
type of mounting. 

FORMULAS AND RECOMMENDATIONS FOR INSTALLATION 

Calculation of opening / closure force 

Using  the  formulas  on  this  page,  approximate  calculations  can  be  made  for  the  force 
required  to  open  or  close  the  window  considering  all  the  factors  that  determine  the 

Symbols used for the calculation  

F (Kg) = Force for opening or closing 

P (Kg)  = 

Weight of the window (mobile sash only)

C (cm) = Opening stroke (actuator stroke) 

H (cm) = Height of the mobile sash

For horizontal light domes or skylights 

(Eventual  weight  of  snow  or  wind  on  the 

calculated separately)

For vertical windows

 

TOP HUNG WINDOWS

,

 OUTWARD OPENING

 

BOTTOM HUNG WINDOWS

F = 0,54 x P x C : H

(Eventual  load  of  favourable  or  unfavourable 
wind  on  the  sash  should  be  calculated 
separately.)

 

force executed from the actuator in function of the stroke and 

FORMULAS AND RECOMMENDATIONS FOR INSTALLATION  

Using  the  formulas  on  this  page,  approximate  calculations  can  be  made  for  the  force 
required  to  open  or  close  the  window  considering  all  the  factors  that  determine  the 

Weight of the window (mobile sash only)

 

H (cm) = Height of the mobile sash 

For vertical windows 

OUTWARD OPENING

 (A) 

BOTTOM HUNG WINDOWS

 (B) 

F = 0,54 x P x C : H 

(Eventual  load  of  favourable  or  unfavourable 
wind  on  the  sash  should  be  calculated 

ction of the stroke and 

 

2.2.  Maximum opening according to height of sash 

The actuator can be recessed mounted in the frame as well as outside on the frame or on the 
sash.  In  any  case  the  actuator  stroke  is  in  accordance  with  the  height  of  the  sash  and  its 
application. Check that, during stroke, the actuator chain does not touch the profile of the sash 
and that there are no obstacles for the opening or it does not exert force on the window frame.  

A

TTENTION

.  For  safety  reasons  the  actuator  should  not  be  assembled  if  dimensions  are 

inferior to those indicated in the table below. In the event that the height of the sash should 
be lower, call on the manufacturer to check the appliance. 

Mode of installation 

Selection of actuator stroke 

300 

600 

800 

1000 

Light domes, skylights or vertical top hung windows opening 
outwards with frontal assembly 

350 

650 

900 

Top hung windows opening outwards with horizontal assembly 

350 

650 

900 

Bottom hung windows 

(motor on frame)

 

400 

800 

1200 

1350 

Bottom hung windows 

(motor on sash)

 

Consult manufacturer 

3. USE OF ACTUATOR IN SYNCRO³ VERSION 

In the 

SYNCRO

³ version the actuator has been equipped with the new system patented by 

NEKOS for coordinated  synchronisation of a  group  of actuators  (up to eight at the  same 
time).  Electronic  control  of  speed  is  completely  automatic  device  inside  the  actuator  and 
does not require any external control station: just connect the feeder cable communication 
wires to each other 

(see diagram on page 15-16)

 and carry out reset procedure.  

3.1.  Recognition 

Three elements differentiate the SYNCRO

3

 version of the actuator from other actuators in 

the INKA 356 series: 

  The technical data label with the “..… 

SYNCRO

3

” label. 

  The  SYNCRO  label  to  one  side  of  the  technical  data  label  on  the 

actuator. 

  Only for 110-230V~ version, the electrical cable with 5 wires 

(3+2)

3.2.  Use of a Syncro³-version actuator  

The Syncro³ version of the actuator is used when the window is particularly heavy or wide 

(more  than  approximately  1.2  m  wide) 

and  a  single  actuator  doesn't  allow  complete 

closure  of  the  window,  especially  in  the  corners,  therefore  making  it  necessary  to  have 
two or more retention points.  
When a group of Syncro³ actuators is used, the movement of the window sashes occurs 
in  a  synchronized  manner,  i.e.,  uniformly  without  interruptions  and/or  variations  in  the 
speeds of the actuators. If one of the actuators stops, due to mechanical obstruction or 
an electronic problem, the other actuators stop as well, thereby guaranteeing the integrity 
of the window. 
Recall that the force exerted by a group of actuators installed on the same window sash 
is  equivalent  to  the  sum  of  the  forces  exerted  by  each  actuator;  so  assembling  two 
actuators doubles the force exerted on the window. 

IMPORTANT:  when  calculating  the  dimensions  of  a  system  with  multiple  Syncro³ 
actuators,  it  is  advisable  to  consider  the  force  of  each  actuator  as  90%  of  that 
stated on the plate. 

Содержание INKA 356 Series

Страница 1: ...l units out of their reach Have installation checks performed periodically by qualified personnel from a service centre authorised by the manufacturer Do not use if repair or adjustment is required CA...

Страница 2: ...y or mental capabilities or lacking experience not allow children to play with the fixed controls and keep any remote out of their reach The actuator is destined exclusively for installation indoors F...

Страница 3: ...frame ATTENTION For safety reasons the actuator should not be assembled if dimensions are inferior to those indicated in the table below In the event that the height of the sash should be lower call...

Страница 4: ...in the chapter on TECHNICAL DATA 8 ACTUATOR DIMENSIONS The main overall dimensions of the actuator are given in the table below for bottom and awning sashes However for perfect application on the requ...

Страница 5: ...SECTION Actuator fed at 24V 110V 230V 0 50 mmq 20 m 300 m 1400 m 0 75 mmq 30 m 450 m 2100 m 1 00 mmq 40 m 600 m 2800 m 1 50 mmq 60 m 900 m 4000 m 2 50 mmq 100 m 1500 m 6800 m 4 00 mmq 160 m 2500 m 11...

Страница 6: ...x 2 QL The central dimensions QL x 2 Legend LA Window Sash Width hinges side PA Actuator Attachment Points QL Side Dimensions 10 4 Screw holes for support brackets and sash hinges Screw holes for low...

Страница 7: ...with cable manufactured in accordance with safety standards and protection against radio disturbances SPECIFIC CABLE Before performing the correspondence between the feeder cable and the tension data...

Страница 8: ...s and relax the internal mechanical parts During operation the INKA 356 actuators automatically recognize and memorize the distance between window sash and frame when the window is completely closed T...

Страница 9: ...t the overlap acquisition operation If the K LOCK electro lock is present refer to the respective user and installation manual 18 12 3 Overlap acquisition The operation that must be carried out to acq...

Страница 10: ...ducts and individual parts for 2 years the purchaser possesses proof of purcha payment 20 CHECKING FOR CORRECT ASSEMBLY Check that the window is perfectly closed at corners and that there are no obsta...

Страница 11: ...air by personnel unauthorised by the manufacture shall render the warranty null and invalid The warranty does not cover fragile parts or parts subject to natural wear and tear or corrosion overload ho...

Страница 12: ...agnetica ElectroMagnetic Compatibility Directive EMCD 2014 35 EU Direttiva Bassa Tensione Low Voltage Directive LVD 2011 65 EU Direttiva sulla restrizione dell uso di determinate sostanze pericolose n...

Отзывы: