Prior to installation
q
Round pipes:
We recommend
Internal diameter:
150 mm
(at least 120 mm).
q
Flat ducts
must have an internal crosssection
that equates to that of round pipes.
There should be no sharp bends.
ø 120 mm approx. 113 cm
2
ø 150 mm approx. 177 cm
2
q
If pipes have different diameters:
Insert seal-
ing strip.
q
For exhaust-air mode,
ensure that there is an
adequate supply of fresh air.
Connecting a Ø 150 mm exhaust-air pipe:
q
Mount the pipe directly onto the air outlet on the
hood.
Connecting a Ø 120 mm exhaust-air pipe:
q
Attach the reducing con-
nector directly to the air
pipe.
q
Attach the exhaust-air
pipe to the reducing con-
nector.
Circulating-air mode
q
With activated carbon ilter if exhaust-air mode
is not possible.
The complete installation set can
be obtained
from specialist
outlets.
The corresponding accessory numbers
can be found at the end of these oper-
ating instructions.
Electrical connection
WARNING: THIS APPLIANCE MUST BE
EARTHED
IMPORTANT: Fitting a Different Plug:
The wires in the mains lead are coloured in accord-
ance with the following code:
Green and Yellow
– Earth
Blue
– Neutral
Brown
– Live
If you it your own plug, the colours of these wires
may not correspond with the identifying marks on
the plug terminals.
This is what you have to do:
1. Connect the green and yellow (Earth) wire to
the terminal in the plug marked ‘E’ or with the
symbol ( ), or coloured green or green and yel-
low.
2. Connect the blue (Neutral) wire to the terminal
in the plug marked ‘N’ or coloured black.
3. Connect the brown (Live) wire to the terminal
marked ‘L’, or coloured red.
The extractor hood
should only be connected to an
earthed socket that has been installed according to
relevant regulations.
If possible, site the earthed socket directly behind
the chimney panelling.
q
The earthed socket should be connected via its
own circuit.
q
If the earthed socket is no longer accessible fol-
lowing installation of the extractor hood, ensure
that there is a permanently installed disconnec-
tor.
If it is necessary to wire the extractor hood di
-
rectly into the mains:
The extractor hood should only be connected to the
electricity supply by a properly qualiied electrician.
A separator must be installed in the household
circuit. A suitable separator is a switch that has a
contact gap of more than 3 mm and interrupts all
poles. Such devices include circuit breakers and
contactors.
If the connecting cable for this appliance
is damaged, the cable must be replaced by the
manufacturer or his customer service or a similarly
qualiied person in order to prevent serious injury to
the user.
Preparing the wall
q
The wall must be lat and perpendicular.
q
Ensure that the wall is capable of providing a
irm hold for mounting screws and plugs.
Weight in kg: 20.
We reserve the right to construction changes within
the context of technical development.
Содержание D96W44N0
Страница 2: ...de Seite 3 13 en page 14 24 fr page 25 35 nl pagina 36 46 it pagina 47 57 es p gina 58 68 el 69 79...
Страница 69: ...69 el q q q q q q q 4 Pa 0 04 mbar...
Страница 70: ...70 el q q q q q 2002 96 waste electrical and electronic equipment WEEE 15 di 2 15 q 5 kW Wok 2 q...
Страница 71: ...71 el q q A B C D...
Страница 72: ...72 el q 2 q q q q q...
Страница 73: ...73 el q q q q q...
Страница 74: ...74 el q q q q q inox inox q inox q inox q q q q q 1 2 3 12 Volt max 20 Watt GU4 4 5 E Nr FD...
Страница 75: ...75 el 460 mm TRGI 50 mm 460 mm...
Страница 76: ...76 el q q q 4 Pa 0 04 mbar 600 900 Min 870 Max 1195 570 600 900 Min 1000 Max 1330 570...
Страница 77: ...77 el q 150 mm 120 mm q 120 mm 113 cm2 150 mm 177 cm2 q q 150 q 120 q q q q q 3 mm 1 30 m q q kg 20 0...
Страница 79: ...79 el q 15 7 3 7 2 1 q 14 1 15 q 14 1 q 15 150 mm q 25 15 q q 7 2 1 q 4 12c q q q 2 12c...
Страница 80: ...Z5137X5...
Страница 81: ......
Страница 82: ......
Страница 83: ......