- 24 -
(2) Caution points for rack mounting
Racks that hold the Autoloader must meet the requirements described in <1> to <4> below.
Confirm this by referring to the figure below and by taking measurements.
<1> According to the EIA standard, the rack must have a 19-inch universal pitch.
<2> There must be air vents in the front and rear to enable adequate cooling of the device.
<3> The rack must have bars at the front and rear for attaching the device, as illustrated
below.
Figure 2-2 Illustration of Rack Bars
Illustration of front and rear bars
Caution:
The rack mount kit cannot be installed if the holes in the rack bars are not at least
6.5 mm in diameter.
12.7 mm
15.875 mm
15.875 mm
12.7 mm
15.875 mm
15.875 mm
1U
1U
1U
1U
450.8 mm or greater
465 mm