background image

 

EW0826A4_en - rev. A 

Oxygen detectors 

 URS20SS 

05/10/2020 

Gas detection systems for industrial environments 

4/8

 

 

Electrical Installation 

 
 

 
 
 
 
 
 

Terminal board and 
electrical connections 
 
 
 
 
 
 
 
 
 

 

Cabling:

 

 
 
 

 

Configuration: 

 
 
 
 
4…20mA Output 
reference selection: 
 
 
 
 
 

 

4...20mA signal 
operating mode 
configuration: 
 
 

 

Setting threshold limit 
values: 
 
 

CAUTION:  

 Make the area safe and make sure that the device power supply is 

off before cabling and configuration operations. 

Install the sensor in compliance with EN 60079-14. 
The cable gland provided on the housing is used for cable entry. 
Ground the sensor using the internal grounding system. 

 
Ground connection 
 

TB1 Terminal Board 

12…24Vdc 

4…20mA 

 
JP2 jumper circuit 

 

Dip-Switch S1 
  
CN4 connector for  
handheld terminal 
 
 

 

Depending  on  the  connecting  distance,  use  at  least  3-core  cable,  min.  diameter 
0.75mm

2

 up to 100m, 1mm

2

 up to 200m, 1.5mm

2

 up to 500m. 

Use shielded cable where there is a risk of electromagnetic interference.  
If a relay card is used, use multi-core cable suitable for the number of connections. 

 

Default settings of the sensor are shown in the “Technical Specifications” chapter. 
In  order  to  change  the  default  settings,  switch  off  the  power  supply,  input  the  new 
settings at the JP2 jumper  circuit or at the  S1 DIP switch as shown in the diagram, 
then power-up again; in particular: 

 

The  default  setting  for  the  4-20mA  signal  is  the  negative  power  signal.  Output 
reference selection should be made by JP2 triple of jumpers; to change this setting, 
operator has to move 

JP2

 jumpers as shown in the figure: 

Caution

:  if  the  default  settings  are  changed, 

the connections on the 

TB1

 terminal board will 

be inverted. 

     Ref. at  

-

  (default)            Ref. at    

+

 

 

To set the operating mode of the 4...20mA signal, it is necessary to use the 5th selector 
of the DIP switch at 

S1

; in particular: 

 
 

 

                                            Proportional                        Threshold mode 

 

To set the threshold limit values of the optional relay card, or of the threshold operating 
mode of the 4...20mA signal, it is necessary to use the last selector of the DIP switch 
at 

S1

 (ignore the first four selectors); in particular, the thresholds, given in percentage 

of O

2

, will be: 

 

 

 

 
(S1.8 = OFF, default): 

Pre-alarm 

1

st

 threshold alarm 

2

nd

 threshold alarm 

O

2

 excess

 

 

23% O

2

 

25% O

2

 

27% O

2

 

O

deficiency

 

 

19% O

2

 

17% O

2

 

15% O

2

 

 
(S1.8 = ON): 

Pre-alarm 

1

st

 threshold alarm 

2

nd

 threshold alarm 

 
 

22% O

2

 

23% O

2

 

24% O

2

 

 
 

20% O

2

 

19% O

2

 

18% O

2

 

Relay card

 

Sensor card 

Connection 
slot for relay 
card

 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

Содержание EsiWelma Sensigas URS20SS

Страница 1: ...eaks in hospitals laboratories welding centres and more in general where oxygen is stored Oxygen deficiency is an indirect measurement of the presence of other explosive or asphyxiant gases that deple...

Страница 2: ...umption mode applications at 1 or 2 thresholds 4 20mA Output reference selection 4mA 0 O2 20mA 30 O2 0mA no alarm 10mA 1st threshold alarm 20mA 2nd threshold alarm by jumper selectable polarity 4 20mA...

Страница 3: ...nstructions for location of the detectors The detectors must be installed 1 where accidental gas leakages are possible 2 at least 1 5m away from heat sources or from vent holes 3 not in spaces where v...

Страница 4: ...n order to change the default settings switch off the power supply input the new settings at the JP2 jumper circuit or at the S1 DIP switch as shown in the diagram then power up again in particular Th...

Страница 5: ...Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connection slot fl...

Страница 6: ...on The sensors are factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommended The detector will...

Страница 7: ...return the sensor concerned to the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 calibration kit and the TUS40 20 handheld t...

Страница 8: ...gas vapours flammable mist Ex nA nC d IIC T6 Gb Types of protection complying with EN60079 0 and EN60079 15 sensor body with type of protection d in compliance with EN60079 1 BVI 07 ATEX 0033 Type exa...

Отзывы: