Electrical installation of 
the optional relay card 

 

Selecting the type of 
contact on the terminal 
board: 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Configuring the relay 
operating mode:

 

After mechanically installing the relay card, it is necessary to configure it electrically, 
selecting the relay operating mode and the type  of contact desired on the terminal 
board (NC or NO). 

A pair of extractable terminals is available for each relay; the type of contact (NC or 
NO) to be associated with them can be selected using the 

JP1…JP4

 jumpers. 

 
NC or NO contact of pre-alarm relay 
NC or NO contact of 1

st

 THRESHOLD relay 

NC or NO contact of 2

nd

 THRESHOLD relay 

NC or NO contact of FAIL relay 

 

DL1 (yellow),   Sensor FAIL 

DL2 (red),  2

nd

 alarm THRESHOLD 

DL3 (red),  1

st

 alarm THRESHOLD

 

DL4 (red),   Pre-alarm  

 
Selecting the terminal contact: 
 
 
 

NC                         NO 

 
To  set  the  operating  mode  of  the  relays:  for  direct  (relay  energised  by  event)  or 
reverse (relay energised with no event), it is necessary to use the 6th selector of the 
DIP switch at 

S1

; in particular: 

 
 

                                              direct operating mode  

reverse operating mode 

 

Checklist after 
mechanical and 
electrical installation 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

The  sensors  are  factory  calibrated  so  they  normally  do  not  require  any  other 
calibration once installed. Still, after installation, an operational check of the sensors 
is recommended. 
The detector will enter a 2-minute warm-up phase after power-up. 
After this time, the sensor will switch to normal operating mode, but it will take about 
2 hours before it reaches top performance level. 
When the detector is operating, a gas response check should be carried out using 
the 

TUL40..

 gas calibration kit. This kit contains: 

-

  1 calibration gas cylinder: 4% of O

2

; (see kit part numbers on the specific technical 

data sheet) 

-

  pressure valve and flow regulator 

-

  sensor body adapter 

-

  about 2 metres of hose between cylinder and adapter. 

During  the  test,  check  the  output current,  the  status  of  the  LED  visible  outside  the 
enclosure on the sensor body and, if present, the status of the LEDs on the relay card 
before closing the housing 

The LED on the sensor body and the 4...20mA output have the following operating 
meaning: 
 

Sensor status 

4...20mA Output 

Status LED on sensor body 

WARM-UP 

2mA 

Flashing at 2Hz frequency 

OPERATING 

4...20mA 

0,10,20mA for 

threshold 

applications 

1 flash about every 10 sec. 

PRE-ALARM 

2 flashes about every 5 sec. 

1

st

 ALARM THRESHOLD 

3 flashes about every 5 sec. 

2

nd

 ALARM THRESHOLD 

4 flashes about every 5 sec. 

SENSOR FAIL 

22mA 

Steady 

 

  D  |  C 

 

  B  |  A 

 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

Содержание EsiWelma Sensigas URS20SS

Страница 1: ...eaks in hospitals laboratories welding centres and more in general where oxygen is stored Oxygen deficiency is an indirect measurement of the presence of other explosive or asphyxiant gases that deple...

Страница 2: ...umption mode applications at 1 or 2 thresholds 4 20mA Output reference selection 4mA 0 O2 20mA 30 O2 0mA no alarm 10mA 1st threshold alarm 20mA 2nd threshold alarm by jumper selectable polarity 4 20mA...

Страница 3: ...nstructions for location of the detectors The detectors must be installed 1 where accidental gas leakages are possible 2 at least 1 5m away from heat sources or from vent holes 3 not in spaces where v...

Страница 4: ...n order to change the default settings switch off the power supply input the new settings at the JP2 jumper circuit or at the S1 DIP switch as shown in the diagram then power up again in particular Th...

Страница 5: ...Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connection slot fl...

Страница 6: ...on The sensors are factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommended The detector will...

Страница 7: ...return the sensor concerned to the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 calibration kit and the TUS40 20 handheld t...

Страница 8: ...gas vapours flammable mist Ex nA nC d IIC T6 Gb Types of protection complying with EN60079 0 and EN60079 15 sensor body with type of protection d in compliance with EN60079 1 BVI 07 ATEX 0033 Type exa...

Отзывы: