EW0826A4_en - rev. A 

Oxygen detectors 

 URS20SS 

05/10/2020 

Gas detection systems for industrial environments 

3/8

 

 

Sensors lifetime 

Sensor average lifetime (see technical characteristics) is referred to a typical usage 
in  a  pollution-free  environment.  Presence  of  a  high  concentration  of  pollutants  can 
shorten the lifetime of the sensing element. 

Once the detection system starts up, it has to be supplied with energy during all the 
lifetime of its sensors. 

Seasonal use of the detection system is not recommended. 

 

Installation 

 

Oxygen excess 

Since oxygen weighs more or less the  same as air, unless there is forced or natural air 
circulation, it tends to spread at the point of the leak. 
So, the excess oxygen detectors must be installed near any likely leakage points, in order 
to detect the excess oxygen as quickly as possible. 

 

Oxygen deficiency 

Detection of oxygen deficiency has the purpose of indirectly detecting the presence of other 
gases  that  deplete  the  oxygen  in  the  air,  therefore  causing  asphyxiation  problems,  for 
example. 
In this case, the detectors must be located at the breathing height of the occupants in the 
premises. 

 

 

Take into consideration the following specific installation guidelines, as well as the above 
instructions, for location of the detectors. 

The detectors must be installed: 

1.  where accidental gas leakages are possible 
2.  at least 1.5m away from heat sources or from vent holes 
3.  not in spaces where ventilation is poor and where gas pockets may form 
4.  away from hindrances to natural gas flow 
5.  away from equipment that may leak gas during normal operations 
6.  in  environments  with  a  temperature  range  of  -20°C  to  50°C  and  relative  humidity 

below 90% (non-condensing) 

7.  Disconnect  equipment  from  the  power  supply  when  mounting  and  dismantling 

detectors. 

 

Environmental 
compatibility 
and disposal 

 

 

This product has been designed and constructed using materials and processes that 
take into account the environmental issue. Refer to the following notes for disposal of 
the product at the end of its working life, or when it is replaced: 

-

  for disposal purposes, this product is classified as an electric and electronic device: 

do not dispose of it with normal household waste, in particular as regards the printed 
circuit 

-

  comply with all local laws in force 

-

  as far as possible reuse basic materials to keep environmental impact to a minimum 

-

  use  local  depots  and  waste  recycling  companies,  or  contact  the  supplier  or 

manufacturer  to  return  used  products  or  to  ask  for  information  on  environmental 
compatibility and waste disposal 

the product packaging can be reused. Keep it for future use or to return the product to 
the supplier. 

Содержание EsiWelma Sensigas URS20SS

Страница 1: ...eaks in hospitals laboratories welding centres and more in general where oxygen is stored Oxygen deficiency is an indirect measurement of the presence of other explosive or asphyxiant gases that deple...

Страница 2: ...umption mode applications at 1 or 2 thresholds 4 20mA Output reference selection 4mA 0 O2 20mA 30 O2 0mA no alarm 10mA 1st threshold alarm 20mA 2nd threshold alarm by jumper selectable polarity 4 20mA...

Страница 3: ...nstructions for location of the detectors The detectors must be installed 1 where accidental gas leakages are possible 2 at least 1 5m away from heat sources or from vent holes 3 not in spaces where v...

Страница 4: ...n order to change the default settings switch off the power supply input the new settings at the JP2 jumper circuit or at the S1 DIP switch as shown in the diagram then power up again in particular Th...

Страница 5: ...Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connection slot fl...

Страница 6: ...on The sensors are factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommended The detector will...

Страница 7: ...return the sensor concerned to the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 calibration kit and the TUS40 20 handheld t...

Страница 8: ...gas vapours flammable mist Ex nA nC d IIC T6 Gb Types of protection complying with EN60079 0 and EN60079 15 sensor body with type of protection d in compliance with EN60079 1 BVI 07 ATEX 0033 Type exa...

Отзывы: