VII. Trouble Shooting
Problem
Cause
Solution
Boiler does not come up to temperature.
Green or soft wood is being used,
Use dry, hard wood
The boiler is at temperature and is
steaming
Poor water circulation (excess fittings, too
small of pipe, improper installation)
Change to a larger pump, use sweeping bends
instead of 90’s
Poor burn time
Green or soft wood is being used,
too much demand on unit,
Use dry, seasoned hard wood
lower home temperature set points, insulate home
better
Boiler is up to temperature but little to
no heat in house
Poor circulation (A simple test can be done
to determine if this is so: touch the pex line
leaving and returning to boiler. There
should be little or no temperature
difference)
Heat exchanger plugged
Improperly designed installation
Not enough insulation in building
Change to a larger pump
Clean and add a y-strainer – be sure to use
treatment!
Reduce number of 90’s & T’s used
Add insulation to structure
Boiler over heats
Air leak
Poor circulation
Water is low in boiler
Aqua-stat malfunction
Make sure loading door is sealed & adjust if
necessary, make sure ash pan is shut
Larger pump, reduce # of fittings
Add water to keep full
Replace Aqua-stat
Boiler fire does not stay lit
Not leaving some coals in burn area
No air flow,
Fire smoldering out
Leave some coals in burn area
replace blower
adjust timer relay to increase auto cycle
Good wood but does not burn. Only
smolders
Blower air way plugged,
Damper not opening
clean air way,
check controls
Boiler up to temperature but no heat in
house
Circulation pump failed
Remove screw on top of pump to see if shaft is
spinning. If not turn power off & turn shaft with
screw driver until loose. Turn power on & check
to see if shaft is spinning. If not, replace pump.
Boiler water getting rusty
Not enough or no boiler treatment
Have your dealer or Nature’s Comfort test your
water. Boiler treatment is required for warranty to
be valid. See warranty.
Blower turns on but actuator doesn’t
open damper
Loose electrical connection
DC Power supply, actuator or CR1 has
failed
Turn power off and check all wire connections
Replace failed component
Water leaking from boiler
Condensation from first start-up of boiler
Condensation from wet wood
Wait for water to come up to temperature