SCXI-1327 Installation Guide
10
ni.com
Field-wiring connectors
Screw terminals
Signal terminals........................16 (8 pairs)
Functional ground terminals.....2
Maximum wire gauge...............16 AWG
Terminal spacing ......................0.5 cm (0.2 in.) center-to-center
Dimensions of front entrance ..........1.2 by 7.3 cm (0.47 by 2.87 in.)
Solder pads
for additional components ...............None
Safety earth-ground lugs..................1
Strain relief ......................................Strain-relief bar at
terminal-block entrance
Mechanical
Dimensions .............................................17.8 by 7.94 by 3.0 cm
(7.0 by 3.125 by 1.2 in.)
Weight ....................................................200 g (7 oz)
Environmental
Operating temperature ............................0 to 50 °C
Storage temperature ................................–20 to 70 °C
Relative humidity ...................................5 to 90% noncondensing
Altitude (maximum) ...............................2000 m
Safety
Designed in accordance with IEC 61010-1, UL 3111-1, and CAN/CSA
C22.2 No. 1010.1 for electrical measuring and test equipment.
Installation category II
Pollution degree 2