Channel-to-channel
None
Channel-to-earth ground
Continuous
250 V RMS, Measurement Category II
Withstand, up to 5,000 m
3,000 V RMS, verified by a 5 s dielectric withstand test
NI-9207 with DSUB Safety Voltages
Connect only voltages that are within the following limits:
Isolation
Channel-to-channel
None
Channel-to-earth ground
Continuous
60 V DC, Measurement Category I
Withstand, up to 2,000 m
1,000 V RMS, verified by a 5 s dielectric withstand test
Withstand, up to 5,000 m
500 V RMS, verified by a 5 s dielectric withstand test
Safety Guidelines for Hazardous Locations
The NI-9207 is suitable for use in hazardous locations; , and hazardous locations;
and nonhazardous locations only. Follow these guidelines if you are installing the
NI-9207 in a potentially explosive environment. Not following these guidelines may
result in serious injury or death.
Caution
Do not disconnect I/O-side wires or connectors unless power has
been switched off or the area is known to be nonhazardous.
Caution
Do not remove modules unless power has been switched off or
the area is known to be nonhazardous.
ni.com
4
NI-9207 Getting Started
Содержание NI-9207
Страница 1: ...NI 9207 Getting Started 2022 07 01...