Caution
Substitution of components may impair suitability for Class I,
Division 2, or Zone 2.
Caution
The system must be installed in an enclosure certified for the
intended hazardous (classified) location, having a tool secured cover/door,
where a minimum protection of at least IP54 is provided.
Special Conditions for Hazardous Locations Use in Europe and
Internationally
The NI-9207 with spring terminal has been evaluated as equipment under DEMKO
ATEX and is IECEx certified. The NI-9207 with DSUB has been evaluated as
equipment under DEMKO ATEX and is IECEx certified. Each NI-9207 is marked and is
suitable for use in Zone 2 hazardous locations, in ambient temperatures of -40 °C ≤
Ta ≤ 70 °C. If you are using the NI-9207 in Gas Group IIC hazardous locations, you
must use the device in an NI chassis that has been evaluated as Ex nC IIC T4, Ex IIC
T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.
Caution
Transient protection shall be provided that is set at a level not
exceeding 140% of the peak rated voltage value of 85 V at the supply
terminals to the equipment.
Caution
The system shall only be used in an area of not more than
Pollution Degree 2, as defined in IEC/EN 60664-1.
Caution
The system shall be mounted in an ATEX/IECEx-certified
enclosure with a minimum ingress protection rating of at least IP54 as
defined in IEC/EN 60079-15.
Caution
The enclosure must have a door or cover accessible only by the
use of a tool.