Power Requirements
Power supply range . . . . . . . . . . . . . . 11–30 VDC
Recommended power supply
FP-20
xx with up to 5 modules . 15 W (FP-PS-4 or equivalent)
FP-20
xx with 6 to 9 modules . . 20 W
Power consumption . . . . . . . . . . . . . . 4.5 W + 1.1(
I/O module power requirements)
Physical Characteristics
Screw-terminal wiring . . . . . . . . . . . . 16–26 AWG copper conductor wire with 7 mm
(0.28 in.) of insulation stripped from the end
Torque for screw terminals . . . . . . . . 0.5–0.6 N
·
m (4.4–5.3 lb
·
in.)
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . 278 g (9.8 oz)
Environmental
FieldPoint modules are intended for indoor use only. For outdoor use, they must be
installed in a suitable sealed enclosure.
Operating temperature. . . . . . . . . . . . –25 to 55 °C
Storage temperature . . . . . . . . . . . . . –55 to 85 °C
Humidity . . . . . . . . . . . . . . . . . . . . . . . . 10 to 90% RH, noncondensing
Maximum altitude . . . . . . . . . . . . . . . . 2,000 m
Pollution Degree . . . . . . . . . . . . . . . . . 2
FP-20xx Quick Start Guide
16
ni.com
322759e.qxp 4/22/2004 4:00 PM Page 16