background image

cFP-2200/2210/2220

6

ni.com

Mounting the Backplane on a DIN Rail

The DIN rail mounting kit is NI part number 778614-01. You need one kit 
to mount the cFP-BP-4 on a standard 35 mm DIN rail. Complete the 
following steps to mount the backplane on a DIN rail.

1.

Fasten the DIN rail clip to the cFP-BP-4 using a number 2 Phillips 
screwdriver and the 8-32 

×

 5/16 in. countersink screws shipped with 

the mounting kit.

Figure 7.  

Installing the DIN Rail Clip on the cFP-BP-4

Caution

Do not use screws longer than 5/16 in. to fasten the DIN rail clip to the backplane.

2.

Insert one edge of the DIN rail into the deeper opening of the DIN rail 
clip, as shown in Figure 8.

Figure 8.  

One Edge of DIN Rail Inserted in Clip

1

DIN Rail Clip

2

DIN Rail Spring

3

DIN Rail

 NA

TIO

NA

INS

TR

UM

EN

TS

2

1

3

Содержание Fieldpoint CFP-2200

Страница 1: ...ovable Compact Flash cFP 2220 Only 4 Status LED 5 Power LED 6 User Configurable LEDs 7 DIP Switches 8 USB Port cFP 2220 Only 9 RJ 45 Ethernet Port 2 cFP 2220 Only 10 Reset Button 11 Power Connector 12 Digital Input Output Terminals cFP 2220 Only 13 RS 485 Serial Port cFP 2220 Only 14 RS 232 Serial Port cFP 2220 Only 15 RS 232 Serial Port cFP 2210 and cFP 2220 Only 3 4 6 7 8 9 10 12 13 14 15 11 5 2...

Страница 2: ...y Number 2 Phillips screwdriver 14 AWG 1 6 mm wire with ring lug to fit 8 screw 11 30 VDC Power supply PC running Windows FieldPoint software 6 0 1 or later LabVIEW Real Time Module 8 5 1 or later Mounting the Compact FieldPoint Backplane You can mount the cFP BP x backplane on a 35 mm DIN rail on a panel or in a standard 19 in rack NI recommends DIN rail mounting for the cFP BP 4 only Use panel m...

Страница 3: ...ug to the backplane PE ground terminal To ensure maximum cooling efficiency mount the Compact FieldPoint so that the I O module vents are at the top and bottom as shown in the following figure Figure 2 cFP 22xx Installed on cFP BP 4 Mounted Upright Caution Your installation must meet the following requirements for space and cabling clearance Allow at least 51 mm 2 in all around the backplane for a...

Страница 4: ...on cFP BP 4 Front View with Dimensions Cabling Clearance 4 slots 246 mm 9 68 in 8 slots 441 mm 17 4 in Cooling Outline 51 mm 2 in Cooling Outline 51 mm 2 in Min 182 mm 7 18 in 106 mm 4 18 in Cabling Clearance Cooling Outline 51 mm 2 in All Around 4 slots 246 mm 9 68 in 8 slots 441 mm 17 4 in 127 mm 5 00 in Min 165 mm 6 50 in ...

Страница 5: ...I O modules are in the backplane before mounting it 104 78 mm 4 1 in 63 50 mm 2 5 in 22 23 mm 0 9 in 33 15 mm 1 3 in 129 54 mm 5 1 in 311 40 mm 12 3 in 387 60 mm 15 3 in 407 80 mm 16 1 in 127 00 mm 5 0 in 440 94 mm 17 4 in 104 74 mm 4 1 in 63 46 mm 2 5 in 127 00 mm 5 0 in 22 19 mm 0 9 in 34 04 mm 1 3 in 84 84 mm 3 3 in 161 04 mm 6 3 in 211 84 mm 8 3 in 245 87 mm 9 6 in ...

Страница 6: ...he cFP BP 4 using a number 2 Phillips screwdriver and the 8 32 5 16 in countersink screws shipped with the mounting kit Figure 7 Installing the DIN Rail Clip on the cFP BP 4 Caution Do not use screws longer than 5 16 in to fasten the DIN rail clip to the backplane 2 Insert one edge of the DIN rail into the deeper opening of the DIN rail clip as shown in Figure 8 Figure 8 One Edge of DIN Rail Inser...

Страница 7: ...as mounting holes on the sides of the backplane and is NI part number 778616 01 The vertical panel mount kit has mounting holes on the top and bottom of the backplane and is NI part number 778688 01 Complete the following steps to mount the system on a flat surface 1 Fasten the panel mount plates to the back of the cFP BP x using a number 2 Phillips screwdriver and the 8 32 5 16 in countersink scr...

Страница 8: ...unt Kit Installed Front View with Dimensions Figure 11 cFP BP 8 with Horizontal Panel Mount Kit Installed Front View with Dimensions Figure 12 Installing the Vertical Panel Mount Kit on the cFP BP 4 260 mm 10 25 in 102 mm 4 in 102 mm 4 in 457 mm 18 in NATIONAL INSTRUMENTS ...

Страница 9: ...nsions 2 Bolt or screw the plates to a panel 3 Connect the PE ground terminal on the cFP BP x to safety ground Caution Disconnect power and make sure that no I O modules are in the backplane before removing it from the panel 178 mm 7 in 152 mm 6 in 246 mm 9 7 in 178 mm 7 0 in 34 0 mm 1 34 in 7 6 mm 0 30 in 17 8 mm 0 70 in 457 mm 18 in 374 mm 14 7 in 178 mm 7 in 152 mm 6 in 33 1 mm 1 31 in 7 6 mm 0...

Страница 10: ... 4 Radius 2 29 mm 0 090 in 444 5 mm 17 500 in 2 29 mm 0 090 in 8 Diameter 374 65 mm 14 750 in 278 89 mm 10 980 in 177 8 mm 7 000 in 25 4 mm 1 000 in 66 29 mm 2 610 in 37 69 mm 1 484 in 37 72 mm 1 485 in 152 15 mm 5 990 in 76 2 mm 3 000 in 152 4 mm 6 000 in 33 15 mm 1 305 in 132 56 mm 5 219 in 82 52 mm 3 249 in 38 1 mm 1 500 in 2 34 93 mm 1 375 in 2 Radius 25 4 mm 1 000 in 50 8 mm 2 00 in 0 003 in ...

Страница 11: ...truments Corporation 11 cFP 2200 2210 2220 Figure 16 Installing the Rack Mount Bracket on the cFP BP 4 Figure 17 Installing the Rack Mount Bracket on the cFP BP 8 NA TION AL INST RU MEN TS NA TION AL INST RU MEN TS ...

Страница 12: ...r supply such as the PS 5 The captive 10 32 nuts on the rack mount kit make it easy to attach a DIN rail Use two 10 32 screws of 3 8 in length as shown in Figure 18 If you want to install flat washers under the screw heads use a slightly longer screw up to 1 2 in length If you need more DIN rail space you can install an 18 in rail in a second rack mount kit using four 10 32 screws Figure 18 Instal...

Страница 13: ...op and align the captive screws on the controller with the holes on the backplane 3 Seat the card edge at the back of the controller in the card edge connector on the backplane 4 Press the controller firmly to seat it on the backplane Figure 19 Installing the Controller on the Backplane 5 Using a number 2 Phillips screwdriver with a shank of at least 64 mm 2 5 in length tighten the captive screws ...

Страница 14: ...e backplane 2 Press firmly to seat the I O module on the backplane 3 Using a number 2 Phillips screwdriver with a shank of at least 64 mm 2 5 in length tighten the captive screws to 1 1 N m 10 lb in of torque 4 Repeat this procedure to install additional I O modules on the backplane Figure 20 Installing an I O Module on the Backplane ...

Страница 15: ...right of each I O module socket Caution Do not insert or remove connector blocks or other connectivity accessories while power is applied to them 1 Wire signals or loads as described in the I O module and connector block operating instructions Caution Hazardous voltage wiring should be performed by qualified personnel and in accordance with local electrical standards 2 Align the captive screws on ...

Страница 16: ...Connector Block on the Backplane 4 Using a number 2 Phillips screwdriver with a shank of at least 64 mm 2 5 in length tighten the captive screws to 1 1 N m 10 lb in of torque 5 Repeat this procedure to install additional connector blocks on the backplane ...

Страница 17: ...er the host computer nor the controller is connected to a network you can connect the two directly using a crossover cable If you want to use the controller on a subnet other than the one the host computer is on first connect the controller on the same subnet as the host computer Use DHCP to assign an IP address or reassign a static IP address for the subnet where you want to use the controller an...

Страница 18: ...r has one layer of reverse voltage protection Caution In order to comply with standards and laws governing electromagnetic emissions and compatibility you must install the ferrite shipped with the controller If you decide to connect an optional second power supply you must install a second similar ferrite You can order the ferrite from ni com The ferrite is NI part number 711849 01 Complete the fo...

Страница 19: ... to one of the C terminals of the COMBICON connector 5 Optionally connect the positive lead of another power supply to the V2 terminal and the negative lead to one of the C terminals of the COMBICON connector 6 Install the COMBICON connector on the front panel of the cFP 22xx Note The controller draws power from either V1 or V2 depending on which terminal has a higher voltage It does not draw powe...

Страница 20: ... connected to earth ground Caution Do not tighten or loosen the terminal screws on the power connector while the power connector is plugged into the controller or while the power supply is on Powering On the cFP 22xx When you apply power to the cFP 22xx the controller runs a power on self test POST During the POST the Power and Status LEDs turn on The Status LED turns off indicating that the POST ...

Страница 21: ...P 2210 and cFP 2220 Only COM 2 is an RS 232 DTE serial port with a 10 position modular jack The Serial VIs access COM 2 as port 1 Refer to Figure 26 and Table 2 for pin locations and signal descriptions COM 3 cFP 2220 Only COM 3 is an RS 232 DTE serial port with a 10 position modular jack The Serial VIs access COM 3 as port 2 Refer to Figure 26 and Table 2 for pin locations and signal descriptions...

Страница 22: ...lator if your application requires more isolation Refer to Figure 26 and Table 2 for pin locations and signal descriptions Figure 26 10 Position Modular Jack Pin Locations Table 2 10 Position Modular Jack Pin Descriptions 10 Position Modular Jack Pin RS 232 Signal RS 485 Signal 10 DCD GND 9 RXD CTS HSI 8 TXD RTS HSO 7 DTR RXD 6 GND RXD 5 DSR CTS HSI 4 RTS RTS HSO 3 CTS TXD 2 RI TXD 1 No Connect No...

Страница 23: ...can use to connect termination resistors to COM 4 The adapter is part number 778674 01 Cable adapters for the 10 position modular jacks are available from NI Part numbers 182845 01 02 and 03 are 1 2 and 3 m cable adapters for connecting the 10 position modular jack to a 9 position D SUB plug External Digital Inputs and Outputs cFP 2220 Only The cFP 2220 has two digital inputs and two digital outpu...

Страница 24: ...Flash drives You can connect USB mass storage devices to the cFP 2220 while the controller is operating USB devices are mapped to the U drive in LabVIEW The cFP 2220 does not support other types of USB devices Refer to the LabVIEW Real Time Module Help for more information Caution Do not hotswap USB devices while the Compact FieldPoint system is in a hazardous location or connected to high voltage...

Страница 25: ...ed in MAX SAFE MODE Switch The position of the SAFE MODE switch determines whether the embedded LabVIEW Real Time engine launches at startup If the switch is in the OFF position the LabVIEW Real Time engine launches Keep this switch in the OFF position during normal operation If the switch is in the ON position at startup the cFP 22xx launches only the essential services required for updating its ...

Страница 26: ...ONS OUT Switch With a serial port terminal program you can use the CONS OUT switch to read the IP address and firmware version of the controller Use a null modem cable to connect the serial port to a computer Push the switch to the ON position Make sure that the serial port terminal program is configured to the following settings 9 600 bits per second Eight data bits No parity One stop bit No flow...

Страница 27: ...n about configuring the controller in MAX 2 The controller has detected an error in its software This can occur when an attempt to upgrade the software is interrupted Refer to the Measurement Automation Explorer Help for information about reinstalling software on the controller 3 The controller is in safe mode Refer to the Configuring DIP Switches section for information about the Safe Mode DIP sw...

Страница 28: ...ble CompactFlash point the VI to the D drive on the controller Caution You must power down the controller before installing or removing a CompactFlash Removing the CompactFlash without powering down the controller can cause data corruption In order to get data from the CompactFlash while the controller is operating use an FTP client to download the data from the D drive on the controller File Tran...

Страница 29: ...use the IP RESET switch to manually restore the controller to the factory network settings When you restore the controller to the factory network settings the IP address subnet mask DNS address gateway and Time Server IP are set to 0 0 0 0 Power on defaults watchdog settings and VIs are unaffected Complete the following steps to reset the network configuration 1 Move the IP RESET DIP switch to the...

Страница 30: ...lit when controller is in normal mode Cannot detect controller in MAX unless it is in safe mode After you set the IP address the controller reboots unconfigured or with the old IP address Green status LED error code greater than 3 Green status LED error code 2 during normal operation Controller incorrectly reports that the disk is full I O module ready LEDs off in normal mode but on in safe mode U...

Страница 31: ... negotiated Maximum cabling distance 100 m segment Memory cFP 2200 128 MB nonvolatile 128 MB DRAM cFP 2210 128 MB nonvolatile 256 MB DRAM cFP 2220 256 MB nonvolatile 256 MB DRAM Memory lifetime nonvolatile 100 000 writes per block For information about the amount of memory used by the LabVIEW Real Time Module and the operating system go to ni com info and enter rdfpec Serial Ports cFP 2200 One RS ...

Страница 32: ... control XON XOFF Wire mode 4 wire Isolation voltage port to earth ground Continuous 100 Vrms Dielectric withstand 740 Vrms verified by 5 s test USB Port cFP 2220 Only Maximum data rate 12 Mb s Maximum current 500 mA Power Requirements Caution You must use a National Electric Code NEC UL Listed Class 2 power supply with the cFP 22xx Power supply input voltage range 11 to 30 VDC Recommended minimum...

Страница 33: ...S voltage MAINS is a hazardous live electrical supply system that powers equipment This category is for measurements of voltages from specially protected secondary circuits Such voltage measurements include signal levels special equipment limited energy parts of equipment circuits powered by regulated low voltage sources and electronics Caution Do not connect the system to signals or use for measu...

Страница 34: ...riate link in the Certification column Environmental Management National Instruments is committed to designing and manufacturing products in an environmentally responsible manner NI recognizes that eliminating certain hazardous substances from our products is beneficial not only to the environment but also to NI customers For additional environmental information refer to the NI and the Environment...

Страница 35: ... 60068 2 56 5 to 95 RH noncondensing Maximum altitude 2 000 m Pollution Degree IEC 60664 2 Shock and Vibration To meet these specifications you must panel mount the Compact FieldPoint system and affix ferrules to the ends of the power terminal wires Operating shock IEC 60068 2 27 30 g 11 ms half sine 50 g 3 ms half sine 18 shocks at 6 orientations Operating vibration random IEC 60068 2 64 5 grms 1...

Страница 36: ...le 4 Ethernet Cable Wiring Connections Pin Connector 1 Connector 2 Normal Connector 2 Crossover 1 white orange white orange white green 2 orange orange green 3 white green white green white orange 4 blue blue blue 5 white blue white blue white blue 6 green green orange 7 white brown white brown white brown 8 brown brown brown Connector 1 Connector 2 Pin 1 Pin 1 Pin 8 Pin 8 ...

Страница 37: ...ephone support outside the United States contact your local branch office Australia 1800 300 800 Austria 43 662 457990 0 Belgium 32 0 2 757 0020 Brazil 55 11 3262 3599 Canada 800 433 3488 China 86 21 5050 9800 Czech Republic 420 224 235 774 Denmark 45 45 76 26 00 Finland 358 0 9 725 72511 France 01 57 66 24 24 Germany 49 89 7413130 India 91 80 41190000 Israel 972 3 6393737 Italy 39 02 41309277 Jap...

Страница 38: ...onal Instruments trademarks Other product and company names mentioned herein are trademarks or trade names of their respective companies For patents covering National Instruments products refer to the appropriate location Help Patents in your software the patents txt file on your CD or ni com patents 2008 National Instruments Corporation All rights reserved 374708A 01 Mar08 ...