Table 11.
POWER LED Indicators
LED Pattern
Indication
Solid
The cRIO-9063 is powered on.
Off
The cRIO-9063 is powered off.
STATUS LED Indicators
The following table describes the STATUS LED indicators.
Table 12.
STATUS LED Indicators
LED Pattern
Indication
Blinks twice and
pauses
The cRIO-9063 is in safe mode. Software is not installed, which is the factory
default state, or software has been improperly installed on the cRIO-9063.
An error can occur when an attempt to upgrade the software is interrupted.
Reinstall software on the cRIO-9063. Refer to the Measurement &
Automation Explorer (MAX) Help for information about installing software
on the cRIO-9063.
Blinks three times
and pauses
The cRIO-9063 is in user-directed safe mode, or the cRIO-9063 is in install
mode to indicate that software is currently being installed.
This pattern may also indicate that the user has forced the cRIO-9063 to boot
into safe mode by pressing the reset button for longer than five seconds or
by enabling safe mode in MAX. Refer to the Measurement & Automation
Explorer (MAX) Help for information about safe mode.
Blinks four times
and pauses
The cRIO-9063 is in safe mode. The software has crashed twice without
rebooting or cycling power between crashes.
Continuously
blinks
The cRIO-9063 has not booted into NI Linux Real-Time. The cRIO-9063 either
booted into an unsupported operating system, was interrupted during the
boot process, or detected an unrecoverable software error.
On momentarily
The cRIO-9063 is booting. No action required.
Off
The cRIO-9063 is in run mode. Software is installed and the operating system
is running.
User LEDs
You can define the USER1 and USER FPGA1 LEDs to meet the needs of your
application. The following table lists the USER1 and USER FPGA1 LED indicators.
ni.com
14
cRIO-9063 Features
Содержание cRIO-9063
Страница 1: ...cRIO 9063 Features 2022 06 30...