Installation and Connections
Chapter 5
SC-207X Series User Manual
5-2
© National Instruments Corporation
Warning:
The SC-207X Series boards have not been designed for use with high voltage.
Although the open component positions are configured so that voltage dividers can be
installed to reduce a high input voltage to within the DAQ device's
±
10 V input range,
the maximum safe input voltage at any point on the SC-207X Series boards is 42 V
peak. Input voltages larger than 42 V, even if attenuated by a voltage divider on the
SC-207X Series board, can result in damage to the SC-207X Series board, the DAQ
device, or the host computer. High voltage can also cause an electric shock hazard to
you. National Instruments is
NOT
liable for damages or injuries resulting from these
connections.
Hardware Installation for the SC-2072
The following are general instructions for installing your SC-2072 board in your computer DAQ
system. Consult your computer’s user manual or technical reference manual for specific instructions
and warnings.
Caution: Turn the host computer off before making any connections.
1.
Mount the SC-2072 board into a 19-in. rack (optional).
2.
Connect the SC-2072 board to the DAQ device using a 50-pin ribbon cable. (If an SC-205X
Series board is used with the SC-2072 board, install and mount the SC-205X Series board as
instructed in the SC-205X Series User Manual, then connect the SC-2072 board to the SC-205X
Series board using the 50-pin cable and connect the SC-205X Series board to the DAQ device.)
3.
Connect field signals to the SC-2072 board at the screw terminals.
4.
Attach the appropriate cover to the rack mount (optional).
5.
Turn the computer on.
6.
When finished, turn off any powered external signals to the SC-2072 board before turning off the
computer.
Warning:
The SC-207X Series boards have not been designed for use with high voltage. Input
voltages larger than 42 V can result in damage to the SC-2072, the DAQ device, or the
host computer. High voltage can also cause an electric shock hazard to you. National
Instruments is
NOT
liable for damages or injuries resulting from these connections.
Installing the SC-205X Series Cable Adapter Boards
Consult the SC-205X Series User Manual for instructions on installing your SC-205X Series board if
any of these boards are being used.
Содержание SC-207 Series
Страница 15: ......