19
cFP-20xx Quick Start Guide
©
National Instruments Corporation
S
Sa
avviin
ng
g H
Ha
arrd
dw
wa
arre
e C
Co
on
nffiig
gu
urra
attiio
on
n a
ass P
Po
ow
we
err--U
Up
p S
Stta
atte
e
When you are satisfied with the hardware configuration of the FieldPoint system, you can
save this configuration as the new power-up state for the system.
A. Right-click the cFP-20
xx controller in the left pane of FieldPoint Explorer, and select
E
Ed
diitt
tth
hiiss d
de
evviic
ce
e
.
B. Clear the factory configuration checkbox.
C. Specify the power-up settings with either of the following options:
• If you want only the range and attribute settings you configured to be saved as
power-up states, click
O
OK
K
. These settings are written to the nonvolatile memory of
the controller.
• If you want to save power-up values for the range and attribute settings and also all
the current output states of the output channels, click
S
Sn
na
ap
pssh
ho
ott
. This stores the
current ranges, attributes, and output values of the bank to the nonvolatile memory of
the network module. Click
O
OK
K
when you are finished.
Refer to the user manual for more information about configuring and changing the power-up
values and configuring a network watchdog to guard against network failures.
11
C
CA
AU
UT
TIIO
ON
N
Using the Snapshot feature overwrites any power-up values you have
specified for individual channels in the Channel Configuration dialog box.
Содержание FieldPoint cFP-20 Series
Страница 18: ...18 cFP 20xx Quick Start Guide ni com ...