background image

Installation Guide for NHPA Split-System Heat Pumps

12

Ounces & Pounds of R410A required for line sets

Weight

Tubing Size

10’

15’

20’

25’

30’

35’

40’

45’

50’

Ounces

3/8” - 3/4” 

0

3.5

7

10.5

14

17.5

21

24.5

28

Pounds

3/8” - 3/4”

0

0.21875 0.4375 0.65625

0.875

1.09375 1.3125 1.53125

1.75

Refrigerant Charging

The  heat  pump  comes  from  the  factory  pre-charged 

recommended  evaporator  coil,  and  the  10  feet  of  refrigerant 

lines. If the actual line length is greater or less than 10 feet, add 

or remove refrigerant at the rate of 0.6 ounces per foot.
If  the  heat  pump  charge  was  lost  for  any  reason,  add  factory 

refrigerant  charge  listed  on  heat  pump  data  plate,  plus 

adjustments  described  above.  If  the  unit  is  operating  during 

charge adjustment, the access panel must be in place to prevent 

high head pressure which would shut down the unit.

Note: The 10ft. of tubing included in the nameplate charge 

has been accounted for, use actual linear length with the table 

below.

When  replacing  a  R-22  system,  it  is  recommended,  that  new 

Line Sets be used. If the old line sets are to be used, they MUST 

be flushed with a commercial flushing agent. R410A refrigerant 

oil,  is  not  compatible  with  R-22  oil.  The  indoor  coil  MUST  be 

replaced and a TXV MUST be used.

Important: The outdoor unit is fully charged 

at the factory for the recommended model 

of indoor unit. With other models of indoor 

units the charge must be adjusted. Be sure 

both service valves are closed during tubing 

installation and leak checking to avoid loss of 

charge. A Bi-Flow liquid line filter drier must be 

installed (SPORLAN #HPC103-S or similar). 

!

CAUTION

Low Suction Pressure Operation! Compressor Damage!

Do not

 operate with a restricted suction. 

Do not

 operate with the low-pressure cut-out bridged. Do not operate compressor 

without enough system charge to maintain at least 0.5 bar suction pressure. 

Allowing pressure to drop below 0.5 bar for 

more than a few seconds may overheat scrolls and cause early drive bearing damage.

The system should be liquid-charged through the liquid-receiver shut-off valve or through a valve in the liquid line. The 

use of a filter drier in the charging line is highly recommended. Because R410A and R407C are blends and scrolls have 

discharge check valves, systems should be liquid-charged on both high and low sides simultaneously to ensure a positive 

refrigerant pressure is present in the compressor before it runs. The majority of the charge should be placed in the high 

side of the system to prevent bearing washout during first-time start on the assembly line.                                 

14299884

1. Connect the charging cylinder to the manifold gauge set. Open 

the charging cylinder valve and bleed air out of the charging hose 

at the manifold gauge set connection.
2. Tighten the manifold gauge set charging connection. Open the 

main manifold gauge set valve and introduce refrigerant into the 

system.  

NOTE

: Oil charge is polyester 32bce.

3. When the correct refrigerant charge level is obtained, remove 

the manifold gauge set.
4. Replace the gauge port caps.

Permanently stamp the unit data plate with the total amount of 

refrigerant in the system. For coils equipped with TXV’s charge 

to  sub-cooling,  15-19°  at  service  valve;  superheat,  12-18°  at 

service valve.

Note: All information based on the following 

Air Flow Chart. Recommended superheat is  

12 - 18° at service valve. Superheat temperature 

measurements should be taken within 3 feet of 

the compressor suction line connection.

Содержание NHPA 3000 Series

Страница 1: ...lation National Comfort Products A Division of National Refrigeration Air Conditioning Products Inc 539 Dunksferry Road Bensalem PA 19020 215 244 1400 1 800 523 7138 Fax 215 639 1674 HEATING A C EQUIP...

Страница 2: ...Leak Checking Page 8 Evacuation Electrical Connections Page 9 High Voltage and Power Supply Page 10 Start Up Sequence of Operations Page 10 Refrigerant Charging Page 12 Maintenance Checkout Procedure...

Страница 3: ...y grounded Failure to do so can cause electrical shock resulting in severe personal injury or death WARNING These instructions are intended as an aid to qualified licensed service personnel for proper...

Страница 4: ...uctions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should further information be desired or should particular proble...

Страница 5: ...ved by NCP to maintain unit performance and warranty Care must be taken to locate coil intake side of unit away from loose debris that may clog intake 7 If the unit is mounted behind a decorative gril...

Страница 6: ...ted Isolate lines from all ductwork Minimize the number of 90 turns Maximum Allowable Liquid Line Pressure Drop 50 PSI Subtract 43 PSI for each foot of Liquid Lift if any Do Not Exceed this value when...

Страница 7: ...he heat pump should not block access to major components Refrigerant lines should not be in direct contact with the floor or ceiling joists Use insulated or suspension type hangers When refrigerant li...

Страница 8: ...valent length of refrigerant lines exceeds 50 ft Leak Checking Leak checking of refrigerant line braze joints and evaporator unit using dry nitrogen 1 Install service port cap of the vapor line servic...

Страница 9: ...onnected Electrical Connections NOTE Make certain that the volts hertz and phase correspond to that specified on the unit rating plate and that the service provided by the utility is sufficient to han...

Страница 10: ...l stop On a call for heating the room heat pump thermostat makes circuits R G and R Y Circuit R G energizes the indoor blower motor relay Circuit R Y energizes the contactor starting the compressor an...

Страница 11: ...nder the coil must be piped per item number 12 under the Unit Location Considerations section of this manual System Charge Adjustment Temperature Measurements Check the outdoor temperatures Subcooling...

Страница 12: ...Operation Compressor Damage Do not operate with a restricted suction Do not operate with the low pressure cut out bridged Do not operate compressor without enough system charge to maintain at least 0...

Страница 13: ...ng for leaks and suction line insulation Improper insulation can cause condensate water damage 6 Pressure and temperature readings of high and low side of system should be checked for proper super hea...

Страница 14: ...Reading between Terminals C R __________ 5 Compressor Winding OHM Reading between Terminals R S __________ 6 Compressor Winding OHM Reading between Terminals C Ground __________ 7 Compressor Winding O...

Страница 15: ...Installation Guide for NHPA Split System Heat Pumps 15...

Страница 16: ...00 19 000 ELECTRICAL 208 230 60 1 12 13 78 20 208 230 60 1 10 16 8 25 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 9 0 56 3 10 9 62 9 RLA Amps LRA Amps FAN MOTOR 0 25 1500 1 4 0...

Страница 17: ...5 HP 1500 RPM 14270049 14270049 10 14 Prop Fan 14214033 14214033 11 Motor Mount 14270102 14270102 12 Access Panel 3000 14256780 14256780 13 Top Panel 3000 14256303 14256303 14 Right Side Panel 1425631...

Страница 18: ...ndard AHRI 270 2008 As an option we offer an Insulated Sound Cover for installation over the inside cover of the unit Sound Without Indoor Cover 70 4 dba Standard AHRI 350 2008 Sound With Indoor Cover...

Страница 19: ...all other warranties express or implied arising by operation of law or otherwise including without limitation merchantability and fitness for a particular purpose whether or not the purpose or use has...

Страница 20: ...ial number whichever occurs first then Customer may take the compressor to any Authorized Copeland Distributor for replacement of said compressor If the defect is reported to National Comfort after on...

Страница 21: ...ta Limitations All installations should factor a proper building heat gain along with appropriate duct sizing and electrical supply wiring to be figured by a professional engineer familiar with local...

Страница 22: ...____________________ ________________________________________________________________________ ________________________________________________________________________ _________________________________...

Страница 23: ...____________________ ________________________________________________________________________ ________________________________________________________________________ _________________________________...

Страница 24: ...Installation Guide NHPA Heat Pump 14299144 7 2016 National Comfort Products 539 Dunksferry Road Bensalem PA 19020 5908 800 523 7138 Fax 215 638 1674 HEATING A C EQUIPMENT NATIONAL COMFORT PRODUCTS...

Отзывы: