background image

Installation Guide for NHPA Split-System Heat Pumps

11

Installers Notes:

• Condenser door must be in place while adjusting subcooling

• Ambient temperature must be between 65

F-95

F

• Indoor return air temperature must be above 70

F

•  Allow  10  to  20  minutes  of  run  time  at  premium  conditions 

before adjusting charge

•  Driving rain against the condenser coil can affect setting proper 

subcooling

• Add charge to increase subcooling

• Remove charge to decrease subcooling

•  Indoor units must be equipped with a thermal expansion valve 

(TXV)

in  the  pan.  The  condensate  pan  under  the  coil  must  be  piped 

per item number 12 under the “Unit Location Considerations” 

section of this manual.

System Charge Adjustment

Temperature Measurements

Check the outdoor temperatures. Subcooling (in cooling mode) is 

the only recommended method of charging above 55º F ambient 

outdoor  temperature.  For  best  results  the  indoor  temperature 

should be kept between 70º F to 80º F. 

Note:

  It  is  important  to  return  in  the  spring  or  summer  to 

accurately charge the system in the cooling mode when outdoor 

ambient temperature is above 55º F.
Stabilize the system by operating for a minimum of 20 minutes. 

At startup, or whenever charge is removed or added, the system 

must  be  operated  for  a  minimum  of  20  minutes  to  stabilize 

before accurate measurements can be made.

Содержание NHPA 3000 Series

Страница 1: ...lation National Comfort Products A Division of National Refrigeration Air Conditioning Products Inc 539 Dunksferry Road Bensalem PA 19020 215 244 1400 1 800 523 7138 Fax 215 639 1674 HEATING A C EQUIP...

Страница 2: ...Leak Checking Page 8 Evacuation Electrical Connections Page 9 High Voltage and Power Supply Page 10 Start Up Sequence of Operations Page 10 Refrigerant Charging Page 12 Maintenance Checkout Procedure...

Страница 3: ...y grounded Failure to do so can cause electrical shock resulting in severe personal injury or death WARNING These instructions are intended as an aid to qualified licensed service personnel for proper...

Страница 4: ...uctions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should further information be desired or should particular proble...

Страница 5: ...ved by NCP to maintain unit performance and warranty Care must be taken to locate coil intake side of unit away from loose debris that may clog intake 7 If the unit is mounted behind a decorative gril...

Страница 6: ...ted Isolate lines from all ductwork Minimize the number of 90 turns Maximum Allowable Liquid Line Pressure Drop 50 PSI Subtract 43 PSI for each foot of Liquid Lift if any Do Not Exceed this value when...

Страница 7: ...he heat pump should not block access to major components Refrigerant lines should not be in direct contact with the floor or ceiling joists Use insulated or suspension type hangers When refrigerant li...

Страница 8: ...valent length of refrigerant lines exceeds 50 ft Leak Checking Leak checking of refrigerant line braze joints and evaporator unit using dry nitrogen 1 Install service port cap of the vapor line servic...

Страница 9: ...onnected Electrical Connections NOTE Make certain that the volts hertz and phase correspond to that specified on the unit rating plate and that the service provided by the utility is sufficient to han...

Страница 10: ...l stop On a call for heating the room heat pump thermostat makes circuits R G and R Y Circuit R G energizes the indoor blower motor relay Circuit R Y energizes the contactor starting the compressor an...

Страница 11: ...nder the coil must be piped per item number 12 under the Unit Location Considerations section of this manual System Charge Adjustment Temperature Measurements Check the outdoor temperatures Subcooling...

Страница 12: ...Operation Compressor Damage Do not operate with a restricted suction Do not operate with the low pressure cut out bridged Do not operate compressor without enough system charge to maintain at least 0...

Страница 13: ...ng for leaks and suction line insulation Improper insulation can cause condensate water damage 6 Pressure and temperature readings of high and low side of system should be checked for proper super hea...

Страница 14: ...Reading between Terminals C R __________ 5 Compressor Winding OHM Reading between Terminals R S __________ 6 Compressor Winding OHM Reading between Terminals C Ground __________ 7 Compressor Winding O...

Страница 15: ...Installation Guide for NHPA Split System Heat Pumps 15...

Страница 16: ...00 19 000 ELECTRICAL 208 230 60 1 12 13 78 20 208 230 60 1 10 16 8 25 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 9 0 56 3 10 9 62 9 RLA Amps LRA Amps FAN MOTOR 0 25 1500 1 4 0...

Страница 17: ...5 HP 1500 RPM 14270049 14270049 10 14 Prop Fan 14214033 14214033 11 Motor Mount 14270102 14270102 12 Access Panel 3000 14256780 14256780 13 Top Panel 3000 14256303 14256303 14 Right Side Panel 1425631...

Страница 18: ...ndard AHRI 270 2008 As an option we offer an Insulated Sound Cover for installation over the inside cover of the unit Sound Without Indoor Cover 70 4 dba Standard AHRI 350 2008 Sound With Indoor Cover...

Страница 19: ...all other warranties express or implied arising by operation of law or otherwise including without limitation merchantability and fitness for a particular purpose whether or not the purpose or use has...

Страница 20: ...ial number whichever occurs first then Customer may take the compressor to any Authorized Copeland Distributor for replacement of said compressor If the defect is reported to National Comfort after on...

Страница 21: ...ta Limitations All installations should factor a proper building heat gain along with appropriate duct sizing and electrical supply wiring to be figured by a professional engineer familiar with local...

Страница 22: ...____________________ ________________________________________________________________________ ________________________________________________________________________ _________________________________...

Страница 23: ...____________________ ________________________________________________________________________ ________________________________________________________________________ _________________________________...

Страница 24: ...Installation Guide NHPA Heat Pump 14299144 7 2016 National Comfort Products 539 Dunksferry Road Bensalem PA 19020 5908 800 523 7138 Fax 215 638 1674 HEATING A C EQUIPMENT NATIONAL COMFORT PRODUCTS...

Отзывы: