background image

Installation Guide for NHPA Split-System Heat Pumps

9

Evacuation

1.

 Connect the vacuum pump to the service ports of the liquid 

line and the vapor line service valves. If the vacuum pump lines 

do  not  contain  shut-off  valves,  hook  up  the  vacuum  pump 

through a manifold gauge set, as the vacuum pump lines must 

be closed for step 4 below.
         a.  If the evacuation is being performed on a new system 

installation, the heat pump service valves should be kept 

in  the  closed  position.  The  vacuum  pump  will  then  be 

able to evacuate the refrigerant lines and evaporator coil. 

         b.  If the evacuation is being performed on an installation 

where the heat pump factory charge has been lost, the 

service valves should be opened.

2.

  Following  the  vacuum  pump  manufacturer’s  instructions, 

allow the pump to operate until the system has been evacuated 

down to 300 microns.

NOTE: Check for leaks if unable to get to 300 microns.

3.

 Allow the pump to continue running an additional 15 minutes. 

Turn  off  the  pump  and  leave  connections  secured.  After  10 

minutes if system fails to hold 500 microns or less, check all 

connections for tight fit and repeat evacuation procedure.

4.

 Isolate the vacuum pump by closing the shut-off valves on 

vacuum pump lines or test gauge manifold. 

5.

 Open the service valves. Opening the service valves will allow 

the refrigerant in the heat pump to enter the refrigerant lines and 

evaporator coil. The vacuum pump can now be disconnected.

Electrical Connections

NOTE:

 Make certain that the volts, hertz, and phase correspond 

to  that  specified  on  the  unit  rating  plate,  and  that  the  service 

provided by the utility is sufficient to handle the additional load 

imposed by this equipment. 
Make all electrical connections in accordance with the National 

Electrical  Code  and  any  pertinent  local  codes  or  ordinances. 

Use  a  separate  branch  electrical  circuit  for  this  unit.  Locate  a 

disconnecting means within sight of and readily accessible to 

the unit.
         a. Line Voltage Connections
        b.  Connect the single phase power supply to unit contactor 

terminal L1 and L2

        c. Connect ground wire to lug
        d. Low Voltage Connections
Consult the indoor unit installation instructions for thermostat 

connections. 

Use a 5-wire thermostat cable between the units.

When locating the room thermostat, it should be in the natural 

circulating path of room air. Avoid locations where the thermostat 

would be exposed to cold air infiltration; drafts from windows, 

doors or other openings leading to the outside; exposure to air 

currents from warm-or-cold air registers or to exposure where 

the natural circulation of the air is cut off, such as behind doors, 

above or below mantels, shelves, etc.

Electrical - Low Voltage

Low Voltage Maximum Wire Length

Table defines the maximum total length of low voltage wiring 

from the condenser to the indoor unit and to the thermostat.

24 VOLTS

WIRE SIZE

MAX. WIRE 

LENGTH

18 AWG

150 Ft.

16 AWG

225 Ft.

14 AWG

300 Ft.

 

Electrical - High Voltage

n

i

NOMINAL 

VOLTAGE

MINIMUM 

VOLTAGE

MAXIMUM 

VOLTAGE

208-230

197

253

Please refer to pages 15 for proper capacitor 

sizing.

Содержание NHPA 3000 Series

Страница 1: ...lation National Comfort Products A Division of National Refrigeration Air Conditioning Products Inc 539 Dunksferry Road Bensalem PA 19020 215 244 1400 1 800 523 7138 Fax 215 639 1674 HEATING A C EQUIP...

Страница 2: ...Leak Checking Page 8 Evacuation Electrical Connections Page 9 High Voltage and Power Supply Page 10 Start Up Sequence of Operations Page 10 Refrigerant Charging Page 12 Maintenance Checkout Procedure...

Страница 3: ...y grounded Failure to do so can cause electrical shock resulting in severe personal injury or death WARNING These instructions are intended as an aid to qualified licensed service personnel for proper...

Страница 4: ...uctions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should further information be desired or should particular proble...

Страница 5: ...ved by NCP to maintain unit performance and warranty Care must be taken to locate coil intake side of unit away from loose debris that may clog intake 7 If the unit is mounted behind a decorative gril...

Страница 6: ...ted Isolate lines from all ductwork Minimize the number of 90 turns Maximum Allowable Liquid Line Pressure Drop 50 PSI Subtract 43 PSI for each foot of Liquid Lift if any Do Not Exceed this value when...

Страница 7: ...he heat pump should not block access to major components Refrigerant lines should not be in direct contact with the floor or ceiling joists Use insulated or suspension type hangers When refrigerant li...

Страница 8: ...valent length of refrigerant lines exceeds 50 ft Leak Checking Leak checking of refrigerant line braze joints and evaporator unit using dry nitrogen 1 Install service port cap of the vapor line servic...

Страница 9: ...onnected Electrical Connections NOTE Make certain that the volts hertz and phase correspond to that specified on the unit rating plate and that the service provided by the utility is sufficient to han...

Страница 10: ...l stop On a call for heating the room heat pump thermostat makes circuits R G and R Y Circuit R G energizes the indoor blower motor relay Circuit R Y energizes the contactor starting the compressor an...

Страница 11: ...nder the coil must be piped per item number 12 under the Unit Location Considerations section of this manual System Charge Adjustment Temperature Measurements Check the outdoor temperatures Subcooling...

Страница 12: ...Operation Compressor Damage Do not operate with a restricted suction Do not operate with the low pressure cut out bridged Do not operate compressor without enough system charge to maintain at least 0...

Страница 13: ...ng for leaks and suction line insulation Improper insulation can cause condensate water damage 6 Pressure and temperature readings of high and low side of system should be checked for proper super hea...

Страница 14: ...Reading between Terminals C R __________ 5 Compressor Winding OHM Reading between Terminals R S __________ 6 Compressor Winding OHM Reading between Terminals C Ground __________ 7 Compressor Winding O...

Страница 15: ...Installation Guide for NHPA Split System Heat Pumps 15...

Страница 16: ...00 19 000 ELECTRICAL 208 230 60 1 12 13 78 20 208 230 60 1 10 16 8 25 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 9 0 56 3 10 9 62 9 RLA Amps LRA Amps FAN MOTOR 0 25 1500 1 4 0...

Страница 17: ...5 HP 1500 RPM 14270049 14270049 10 14 Prop Fan 14214033 14214033 11 Motor Mount 14270102 14270102 12 Access Panel 3000 14256780 14256780 13 Top Panel 3000 14256303 14256303 14 Right Side Panel 1425631...

Страница 18: ...ndard AHRI 270 2008 As an option we offer an Insulated Sound Cover for installation over the inside cover of the unit Sound Without Indoor Cover 70 4 dba Standard AHRI 350 2008 Sound With Indoor Cover...

Страница 19: ...all other warranties express or implied arising by operation of law or otherwise including without limitation merchantability and fitness for a particular purpose whether or not the purpose or use has...

Страница 20: ...ial number whichever occurs first then Customer may take the compressor to any Authorized Copeland Distributor for replacement of said compressor If the defect is reported to National Comfort after on...

Страница 21: ...ta Limitations All installations should factor a proper building heat gain along with appropriate duct sizing and electrical supply wiring to be figured by a professional engineer familiar with local...

Страница 22: ...____________________ ________________________________________________________________________ ________________________________________________________________________ _________________________________...

Страница 23: ...____________________ ________________________________________________________________________ ________________________________________________________________________ _________________________________...

Страница 24: ...Installation Guide NHPA Heat Pump 14299144 7 2016 National Comfort Products 539 Dunksferry Road Bensalem PA 19020 5908 800 523 7138 Fax 215 638 1674 HEATING A C EQUIPMENT NATIONAL COMFORT PRODUCTS...

Отзывы: