EMC
L/L1
N/L2
F+
F-
AN1
AN2
AN3
AN4
+15
0V
+10
0V
IN1
IN2
IN3
IN4
COMBO
G
S1+
S1-
LINE
G
S2+
S2-
MODBUS
ST
A
TUS
ALARM
NO1 COM1 NC1
NO2 COM2 NC2
Control connections for size 2 devices
IN4
IN3
IN2
IN1
0V
+15V
0V
+15V
0V
+10V
AN4
AN3
AN4
AN3
MODBUS
COMBO
G
S1-
S1+
G
S2-
S2+
ALARM
NO1
COM1 NC1
ST
A
TUS
NO2
COM2 NC2
Type
Description
Functionality
Comments
Analog inputs
AN1
4-20 mA
Sensor 1
-
AN2
4-20 mA
Sensor 2
-
AN3
0-10 V
External set value
AN4
0-10 V
External frequency
External set value 2
Power Supply
+15V
15 VDC, max 100 mA
Power supply for 4-20 mA ana-
log inputs
Do not use as a power supply for
the digital inputs!
Power Supply
+10V
10 VDC, max 3 mA
Power supply for 0-10 V analog
inputs
Do not use as a power supply for
the digital inputs!
Signal GND
0V
Insulated
Signal GND for analog and digi-
tal inputs
-
Digital inputs
IN1
Active low
Motor start and stop
Programmable as Normally Open
or Normally Closed.
IN2
Active low
Motor start and stop
Switching of set value 1 and 2
Switching of work frequency 1
and 2
Programmable as Normally Open
or Normally Closed.
IN3
Active low
Motor start and stop
Switching of sensors 1 and 2
Programmable as Normally Open
or Normally Closed.