![Nastec MIDA 203 Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/nastec/mida-203/mida-203_installation-use-and-maintenance-handbook_707879020.webp)
7. Electrical installation
WARNING
Read the safety chapter carefully before continuing.
7.1. Grounding
DANGER
Make sure that the device and the loads connected to it are properly grounded with the appropriate
connection terminals before commissioning.
Ensure that the grounding system is compliant and refer to local regulations for grounding devices.
Each load must be fitted with its own earthing cable, the length of which must be as short as
possible. Do not make interconnected grounding connections.
Leakage currents may exceed 3.5 mA. It is recommended to use the reinforced ground connection if
necessary.
Use the following minimum cross-sections for ground cables:
• cross-section equal to the mains power cable cross-section up 16 mm
2
. (6 AWG)
• 16 mm2 (6 AWG) for mains power cable cross-section between 16 mm
2
(6 AWG) and 35 mm
2
(1 AWG).
• cross-section equal to half the cross-section of the power supply cable when the latter is greater than 35 mm
2
(1
AWG).
7.2. Protection devices
DANGER
It is recommended to install the appropriate protection devices upstream of the device, such as a
circuit breakers, fuses and a residual current device (RCD).
Fuses and switches.
The control device can protect the motor from overloads by digitally controlling the absorbed current against the set
rated current.
It is therefore not necessary to install any overload protection device between the inverter and the motor.
Instead, it is necessary to install overcurrent and short-circuit protection devices, such as fuses and circuit break-
ers, upstream of the device. These trigger in the event of failure of a component inside the device.
Supply voltage
Model
Recommended fuse
gC
Recommended circuit breaker
ABB MCB S200
1 x 230 VAC
MIDA 203
10
S201-C10
1 x 230 VAC
MIDA 205
10
S201-C10
1 x 230 VAC
MIDA 207
16
S201-C16
3 x 230 VAC
MIDA 304
10
S203-C10
3 x 230 VAC
MIDA 306
10
S203-C10
3 x 230 VAC
MIDA 309
16
S203-C16
3 x 230 VAC
MIDA 314
20
S203-C20
3 x 230 VAC
MIDA 318
25
S203-C25
3 x 230 VAC
MIDA 325
30
S203-C32
3 x 230 VAC
MIDA 330
35
S203-C40
3 x 230 VAC
MIDA 338
50
S203-C50
3 x 230 VAC
MIDA 344
63
S203-C63
3 x 380 - 460 VAC
MIDA 404
10
S203-C10
3 x 380 - 460 VAC
MIDA 406
10
S203-C10
3 x 380 - 460 VAC
MIDA 409
16
S203-C16
3 x 380 - 460 VAC
MIDA 414
20
S203-C20
3 x 380 - 460 VAC
MIDA 418
25
S203-C25
MIDA
20
Содержание MIDA 203