Napoleon Madison GD80NT Скачать руководство пользователя страница 5

5

W415-0695 / 05.12.08

THIS GAS FIREPLACE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER

  to conform with local codes. Installa-

tion practices vary from region to region and  it is important to know the specifi cs that apply to your area, 
For example: in Massachusetts State:
•   The fi replace damper must be removed or welded in the open position prior to installation of a fi replace insert or gas log.
•   The appliance off valve must be a “T” handle gas cock.
•   The fl exible connector must not be longer than 36“.
•   The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed combustion product.
•  

WARNING:

 This product must be installed by a licensed plumber or gas fi tter when installed within the commonwealth of 

 Massachusetts.
In absence of local codes, install to the current CAN/CGA -B149 Installation Code in Canada or to the National Fuel Gas Code, ANSI 
Z223.1, and NFPA 54 in the United States. Suitable for mobile home installation if installed in accordance with the current standard CAN/
CSA Z240MH Series, for gas equipped mobile homes, in Canada or ANSI Z223.1 and NFPA 54 in the United States.
The fi replace and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that 
system at test pressures in excess of 1/2 psig (3.5 kPa). The fi replace must be isolated from the gas supply piping system by closing its 
individual manual shutoff valve during any pressure testing of the gas supply piping  system at test pressures equal to or less than 1/2 
psig (3.5 kPa).
When the fi replace is installed directly on carpeting, vinyl tile or other combustible material other than wood fl ooring, the fi replace shall be 
installed on a metal or wood panel extending the full width and depth.
The optional heat circulating blower is supplied with a cord. If installed, the junction box must be electrically connected and grounded in 
accordance with local codes. In the absence of local codes, use the current CSA C22.1 CANADIAN ELECTRICAL CODE in Canada or 
the ANSI/NFPA 70  NATIONAL ELECTRICAL CODE in the United States. 

Under extreme vent configurations, allow several minutes (5-15) for the flame to stabilize after ignition. 

Provide adequate ventilation and combustion air. Provide adequate accessibility clearance for servicing and operating the fireplace. 
Never obstruct the front opening of the fireplace.

Objects placed in front of  the fireplace must be kept a minimum of  48” from the front face of  the unit.

Minimum clearance to combustible construction from fireplace and vent surfaces:

 

Non combustible framing:
Top 

                  

0” to stand-offs. 

Combustible framing:
Sides, back, bottom of the unit               

0” to stand-offs

Non combustible fi nishing:
Top 

         

18” to top of fi replace opening

Sides 

            

5 3/8” to sides of fi replace opening

Combustible fi nishing:
Bottom 

                 

0” to bottom edge of fi replace

Enclosure top 

                 

72” from the bottom of fi replace

Recessed depth 

                 

29 1/4”

Vent pipe

**

 

                 

2” all around

Ceiling 

                 

90” from bottom of unit

**

HORIZONTAL VENT SECTIONS:

 A minimum clearance of 2" all around the vent pipe on all horizontal runs to combustibles is required 

except for clearances in fi replace enclosures. Use fi restop spacer W010-1800 (supplied).

**

VERTICAL VENT SECTIONS:

 A minimum of 1" all around the vent pipe on all vertical runs to combustibles is required except for clear-

ances in fi replace enclosures. Use fi restop spacer W500-0367 (not supplied). 

FOR YOUR SATISFACTION, THIS FIREPLACE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND QUALITY!

  Maximum input 

is 43,000 BTU/hr for both natural gas and propane. When the fi replace is installed at elevations above 4,500ft,  and in the absence of 
specifi c recommendations from the local authority having jurisdiction, the certifi ed high altitude input rating shall be reduced at the rate of 
4% for each additional 1,000ft. Maximum output for natural gas is 33,540 BTU/hr at an effi ciency of 78%; and 34,000 BTU/hr for propane 
at an effi ciency of 79%. Minimum inlet gas supply pressure is 4.5“ water column for natural gas and 11“ water column for propane. Maxi-
mum inlet gas pressure is 7“ water column for natural gas and 13“ water column for propane. Manifold pressure under fl ow conditions is 
3.5“ water column for natural gas and 10“ water column for propane. 
This fi replace is approved for bathroom, bedroom and bed-sitting room installations and is suitable for mobile home installation. 

GENERAL INSTRUCTIONS

GENERAL INFORMATION

This fi replace is certifi ed to be installed in an aftermarket permanently 
located, manufactured (mobile) home, where not prohibited by local 
codes.
This fi replace is only for use with the type of gas indicated on the 
rating plate. This fi replace is not convertible for use with other gases, 
unless a certifi ed kit is used.

Expansion / contraction noises during heating up and cooling down 
cycles are normal and are to be expected. Change in fl ame ap-
pearance from “HI” to “LO” is more evident in natural gas than in 
propane.

Содержание Madison GD80NT

Страница 1: ...1 W415 0695 05 12 08 10 00 W415 0695 05 12 08...

Страница 2: ...Clothing or other flammable material should not be placed on or near the fireplace Due to high temperatures the fireplace should be located out of traffic and away from furniture and draperies Ensure...

Страница 3: ...y This limited warranty further does not cover any scratches dents corrosion or discoloring caused by excessive heat abrasive and chemical cleaners nor chip ping on porcelain enamel parts mechanical b...

Страница 4: ...4 W415 0695 05 12 08 FIGURE 1 INSTALLATION OVERVIEW FIREPLACE DIMENSIONS FIGURE 2...

Страница 5: ...r obstruct the front opening of the fireplace Objects placed in front of the fireplace must be kept a minimum of 48 from the front face of the unit Minimum clearance to combustible construction from f...

Страница 6: ...WALL TERMINAL KIT GD422R or 1 12 TO 7 12 PITCH ROOF TERMINAL KIT GD410 8 12 TO 12 12 ROOF TERMINAL KIT GD411 FLAT ROOF TERMINAL KIT GD412 or PERISCOPE KIT GD401 for wall penetration below grade With e...

Страница 7: ...nch up on horizontal or vertical runs and elbows Keep it pulled tight A 1 air gap between the inner and outer liner all around is required for safe operation Vent lengths that pass through unheated sp...

Страница 8: ...T VT 40 feet 20 9 40 Since both formulas are met this vent con guration is acceptable FIGURE 5 90 H1 V2 H2 V1 HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT The shaded area within the lines represents acc...

Страница 9: ...1 HT 4 2 VT Formula 2 HT VT 24 75 feet Example 2 Example 3 V1 4 ft V2 1 5 ft VT V1 V2 4 1 5 5 5 ft H1 2 ft H2 1 ft H3 1 ft H4 1 5 ft HR H1 H2 H3 H4 2 1 1 1 5 5 5 ft HO 03 four 90 elbows 90 03 360 90 8...

Страница 10: ...Formula 1 HT VT Formula 2 HT VT 40 feet Simple venting con gurations See graph to determine the required vertical rise VT for the required horizontal run HT VERTICAL TERMINATION V1 5 ft V2 10 ft VT V1...

Страница 11: ...8 8 1 16 1 ft HT VT 16 1 4 5 20 6 ft Formula 1 HT 3VT 3VT 3 x 4 5 13 5 ft 16 1 13 5 Since this formula is not met this vent con guration is unacceptable Formula 2 HT VT 40 feet 20 6 40 Since only form...

Страница 12: ...12 W415 0695 05 12 08 MINIMUM AIR TERMINAL LOCATION CLEARANCES GD 301 FIGURE 13...

Страница 13: ...upport 2 Apply a bead of caulking not supplied to the framework or to the Wolf Steel vent pipe shield plate or equivalent in the case of a nished ceiling and secure over the opening in the ceiling A r...

Страница 14: ...ion air collar and secure with 3 8 screws 7 If more liner needs to be used to reach the replace couple them together as illustrated The vent system must be supported approximately every 3 feet for bot...

Страница 15: ...s properly centred within the ashing giving a 3 4 margin all around Fasten to the roof Do not nail through the lower portion of the ashing Make weather tight by sealing with caulking Where possible co...

Страница 16: ...c The air terminal must be located vertically and plumb 6 Remove nails from the shingles above and to the sides of the chimney Place the ashing over the air terminal and slide it underneath the sides...

Страница 17: ...d air exhaust slots onto the air terminal Tighten securely Attach the rain cap 8 Continue adding rigid venting sections sealing and securing as above Attach a 5 collapsed telescopic pipe to the last s...

Страница 18: ...arance to combustibles is maintained within the cavity It is not necessary to install a hearth extension but the replace should be raised to be ush with either the hearth or the nished oor When roughi...

Страница 19: ...72 MINIMUM ENCLOSURE HEIGHT Do not build into this area it must be left clear to provide adequate clearance for the vent in this 14 wide area centered along the front of the fireplace No combustibles...

Страница 20: ...such as cement board ceramic tile marble etc when nishing to the replace DO NOT USE WOOD OR DRYWALL Facing and or nishing material must never overhang into the replace opening Do not distort or force...

Страница 21: ...W415 0695 05 12 08 FIGURE 40a Combustible mantel clearance can vary according to the mantel depth Use the graph to help evaluate the clear ance needed FIGURE 40b MINIMUM MANTEL AND ENCLOSURE CLEARANC...

Страница 22: ...be re installed before operating the unit It is necessary to hard wire this fireplace Permanently framing the replace with an enclosure requires the replace junction box to be hardwired This replace m...

Страница 23: ...ht left and centre hearth bricks into the rebox as illustrated The hearth should appear seamless across the front Ensure that a space exists between the hearth bricks and the perimeter of the burner 5...

Страница 24: ...he PHAZERAMIC burner 2 Position log 2 onto the locators on the PHAZERAMIC burner 3 Position the slot on the bottom of log 3 onto the bracket shown with the charred face of the log to the front LOG PLA...

Страница 25: ...ended The burner has been designed to achieve maximum glow without embers Charcoal provided could be randomly placed on the bre hearth on both sides of the burner and across the front especially at th...

Страница 26: ...ng Lift the hearth strip up and away from the front of the replace The glass door is secured to the top front edge of the rebox Pull the handle of the latch forward then lift the hook out from the slo...

Страница 27: ...ower The blower is pre wired and is controlled by the remote control supplied with the unit For control details see operation Drywall dust will penetrate into the blower bearings caus ing irreparable...

Страница 28: ...n away from magnet catch 2 Remove the hearth strip by lifting up and away from unit 3 Remove the receiver by pulling the left side of the plate away from the bracket 4 Once disengaged pull the wiring...

Страница 29: ...ansmitter The system is now initialized TEMPERATURE DISPLAY 1 Press the ON OFF key on the transmitter The transmitter display will show all active icons on the screen At the same time the receiver con...

Страница 30: ...evels With the system on and the ame level at the maximum press the Down Arrow Key once and it will reduce the ame height by one step until the ame is turned off The Up Arrow Key will increase the ame...

Страница 31: ...function to control the replace during a power failure If the receiver is not equipped with back up batteries the blower and night light features will not operate during a power failure The receiver...

Страница 32: ...der water Warning if you do not follow these instructions exactly a re or explosion may result causing property damage personal injury or loss of life Initial lighting of the pilot and main burners mu...

Страница 33: ...can cause improper and dangerous operation Verify proper operation after servicing This replace and its venting system should be inspected before use and at least annually by a quali ed service person...

Страница 34: ...60 W175 0260 CONVERSION KIT NG TO LP 61 W175 0261 CONVERSION KIT LP TO NG 62 FK80 R FRAMING KIT RECTANGULAR 63 FK80 A FRAMING KIT ARCHED 64 DK80A HC DECORATIVE DOORS HAMMERED COPPER ARCHED 65 DK80R H...

Страница 35: ...35 W415 0695 05 12 08...

Страница 36: ...ed as required Incorrect installation refer to Figure 13 to ensure correct location of storm collars Flames are con sistently too large or too small Carboning occurs check pressure readings Inlet pres...

Страница 37: ...ve Reconnect replace thermopile valve Remote wall switch wire is too long too much resistance in the system shorten wire to correct length or wire gauge Faulty thermostat or switch replace Pilot will...

Страница 38: ...38 W415 0695 05 12 08 Wolf Steel Fireplace Service History This fireplace must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name...

Страница 39: ...39 W415 0695 05 12 08 NOTES...

Страница 40: ...40 W415 0695 05 12 08 NOTES...

Отзывы: