W415-0616 / C / 06.04.08
12
Figure 6
MOBILE HOME
The heater must be grounded to the steel chassis of the mobile home (Some states do not
require this; check with your local building department).
Figure 5
Installation into a manufactured home or mobile home should be installed in accordance with the Manufactured Home
Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States or the Mobile Home Standard, CAN/CSA
Z240 MH Series, in Canada.
GENERAL VENTING
Must be an approved 3" or 4" Diameter Type "L" or "PL" vent, vented to the outside or connect the vent to a factory built
type "A" chimney using an adaptor; and/or stainless steel chimney liner for masonry fi replace installations. Use 4" diam-
eter vent if vent or liner height is over 15' or if installation is over 4,000' above sea level.
TYPE OF VENT
MAXIMUM VENTING:
Maximum venting height is 33'. Maximum horizontal offset is 10'. Use no more than
180° of elbows (two 90' elbows, or two 45' elbows and one 90' elbow, etc), plus
termination.
PELLET VENT MUST MAINTAIN A MINIMUM 3" CLEARANCE TO ANY COMBUSTIBLE
(install vent at clearances
specifi ed by the vent manufacturer).
DO NOT CONNECT THE PELLET VENT TO A VENT OR CHIMNEY SERVING ANY OTHER APPLIANCE OR HEATER.
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.
INSTALLING THE PELLET VENT
The vent must have a support bracket every 5' when on the exterior wall.
To achieve optimum performance, keep vent runs as short as possible, especially
on horizontal installations.
VENT INSTALLATION:
Termination must exhaust above the air inlet elevation, and parallel or above the
exhaust output of the pellet appliance. It is recommended that at least 3' of vertical
pipe be installed to create some natural draft. This is to help prevent the possibility
of smoke or odour during the appliance shut down or in the event of a power out-
age.
Horizontal sections must have a 1/4" rise every 12" of travel if longer than 3'.
The pellet vent connections must be sealed with HI-Temp RTV Silicone and
screwed together with at least 3 3/8" long stainless steel screws.
Seal each vent section by injecting a liberal amount of 500°F
(260°C) RTV silicone sealant into the gap. We recommend sealing
the outside of the vent connections to permit easier access when
servicing.
Do not install in a sleeping room.
The structural integrity of the manufactured home fl oor, wall, and ceiling roof
must be maintained.
!
WARNING
Содержание Auburn NPS40
Страница 1: ...W415 0616 C 06 04 08 1 10 00 W415 0616 C 06 04 08...
Страница 4: ...W415 0616 C 06 04 08 4 WARNINGS AND SAFETY PRECAUTIONS...
Страница 5: ...W415 0616 C 06 04 08 5 WARNINGS AND SAFETY PRECAUTIONS...
Страница 7: ...W415 0616 C 06 04 08 7 DIMENSIONS Figures 1a b NPI40 with NI800 Flashing Shown NPS40 Figures 2a c...
Страница 33: ...W415 0616 C 06 04 08 33 Figure 49 NORMAL OPERATING SOUNDS...
Страница 34: ...W415 0616 C 06 04 08 34 WIRING DIAGRAM Figure 51...
Страница 36: ...W415 0616 C 06 04 08 36 COMMON REPLACEMENTS PARTS...
Страница 37: ...W415 0616 C 06 04 08 37 NPS40 REPLACEMENTS PARTS 57 38 61 44 63 65 57 64 56 58 59 60 66 15 31 39 54 40 53...
Страница 38: ...W415 0616 C 06 04 08 38 NPI40 REPLACEMENTS PARTS...
Страница 39: ...W415 0616 C 06 04 08 39 NPI40 ACCESSORY PARTS COMMON ACCESSORY PARTS...
Страница 44: ...W415 0616 C 06 04 08 44 NOTES...