background image

W415-0616 / C / 06.04.08

42

TROUBLESHOOTING CONTINUED

SYMPTOM

TEST SOLUTION

The 200°F (93°)
high limit tem-
perature sensor 
has tripped 

The heater will 
not turn off

The heater keeps 
going out

Excessive carbon 
build up in the 
fi rebox, low heat 
out put

Unit is burning 
dirty and lazy

- Reset the sensor and determine whether it was the convection blower or 160°F (71°C) 
  temperature sensor failure. Bypass the 160°F (71°C) sensor. Does the convection 
  blower not come on high? If no than replace the blower.

- Disconnect one of the brown wires from the exhaust temperature sensor and if the unit 
  continues to operate, contact your local dealer for service.
- Compare the wiring diagram to the start control module and the connections to the 
  140°F (60°C) temperature sensor. Check the connections.
- Remove one of the brown wires from the 140°F (60°C) temperature sensor. The heater
  should be shut down right away as long as the start button was not pressed within 15 
  minutes of this test. If the heater shuts down within 15 minutes, replace the 140°F 
  (60°C) sensor. If the heater does not shut down in 15 minutes, test the switch.
- The heater must be cold to test the switch. Pull the plug, then plug the heater back in. If 
  the heater fails to start, replace the switch.

- Due to different installation set ups, length and size of venting and fuel quality, the low 
  feed setting from the factory will not always be correct. It may be necessary to 
  experiment with feed rate vs air control. (For example, #2 may be your lowest setting). 
- If the heater goes out and leaves fresh unburned pellets or cigarette-like ashes in the 
  burn pot, the fi re is going out before the heater shuts off. 
- Check to see if the air control rod is in the correct position. 
- Turn the feed rate up slightly (poor quality pellets will require slightly higher settings).
- Check to see if the heater needs a more complete cleaning as well as the burn pot, 
  venting, etc...
- Was there a power failure?
- Contact your local dealer for service
- If the heater goes out and there are no pellets in the liner, the auger is stopping.
- See "The auger motor will not function normally" and "The exhaust blower will not 
  function normally".

- Check quality of pellets. Even pellets from the same manufacturer can vary in quality 
  since the materials they use to form pellets may also vary.
- Moisture content of pellets too high. Pellets must be stored in a dry place. Areas such     
  as a garage are too damp causing pellets to absorb moisture. 

- Check that all exhaust and intake pathways are clear of any obstructions.
- Burn pot is clean.
- Pellets are dry.
- Venting and terminal are clear of obstructions.
- Exhaust blower is operation and is clean.

Содержание Auburn NPS40

Страница 1: ...W415 0616 C 06 04 08 1 10 00 W415 0616 C 06 04 08...

Страница 2: ...stallation 17 22 NPI40 INSTALLATIONS Minimum Clearance to Combustibles Minimum Mantle Clearances Rear or Top Vent Conversion Instructions Installation Overview Installation into a Masonry Fireplace Pr...

Страница 3: ...warranty extends to the repair or replacement of warranted parts which are defective in material or workmanship provided that the product has been operated in accordance with the operation instructio...

Страница 4: ...W415 0616 C 06 04 08 4 WARNINGS AND SAFETY PRECAUTIONS...

Страница 5: ...W415 0616 C 06 04 08 5 WARNINGS AND SAFETY PRECAUTIONS...

Страница 6: ...STANDARDS If the fuel does not comply to this standard the unit may not operate as designed We recommend the use of premium grade 1 ash content for longer stove life and less frequent cleaning Fines n...

Страница 7: ...W415 0616 C 06 04 08 7 DIMENSIONS Figures 1a b NPI40 with NI800 Flashing Shown NPS40 Figures 2a c...

Страница 8: ...W415 0616 C 06 04 08 8 DIMENSIONS CONTINUED Figures 3a c NPI40 with AK9 Adapter and CISK Flashing Shown...

Страница 9: ...W415 0616 C 06 04 08 9 DIMENSIONS CONTINUED Figures 4a c NPI40 with AK8 Adapter and GICSK Flashing Shown...

Страница 10: ...injury or even death Check with local building of cials for any permits required for installation of this pellet heater and notify your insurance company before proceeding with installation Before in...

Страница 11: ...ough the heater and shut down the pellet feed This lack of ow could be caused by a blocked vent POWER FAILURE In the event of a power failure the heater will shut down Once power is restored the heate...

Страница 12: ...ent manufacturer DO NOT CONNECT THE PELLET VENT TO A VENT OR CHIMNEY SERVING ANY OTHER APPLIANCE OR HEATER DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT INSTALLING THE PELLET...

Страница 13: ...ermination is located on a windy side of the house a shield is recommended to prevent soot from building up on the side of the house Horizontal terminations must protrude 12 from the wall vertical ter...

Страница 14: ...inside combustible corner wall or protruding combustible ob structions vent chase etc Clearance to a non mechanical air supply inlet to the building or a combustion air inlet to any other appliance C...

Страница 15: ...pellet vent is used the clearance to the back wall is determined by the upward turning elbow or Tee It will vary in depth depending on the brand of pellet vent used it is approximately 5 Before placi...

Страница 16: ...W415 0616 C 06 04 08 16 VENTING INSTALLATION EXAMPLES Figure 13 THROUGH WALL WITH VERTICAL RISE AND HORIZONTAL TERMINATION INSTALLATION Figure 14 HORIZONTAL EXHAUST THROUGH WALL INSTALLATION...

Страница 17: ...maintain 3 clearance to combus tibles Vertical Cap Roof Flashing Storm Collar Floor Protection 3 2 Class A Chimney Ceiling Support Outside air Recommended Installation showing inlet of out side air in...

Страница 18: ...ole sized for the pellet liner to lie directly below the replace ue opening Allow two inches of material for a ange on all sides and cut to these measurements Bend down the anges If you have never don...

Страница 19: ...NT CONVERSION INSTRUCTIONS NOTE The insert is factory shipped in a rear vent con guration 1 To vent exit vertically remove the two screws holding the exhaust cover NOTE Be careful not to damage the ga...

Страница 20: ...INIMUM MANTEL CLEARANCES Drywall or other combustible material See the sections GENERAL VENTING and INSTALLATION See the section MINIMUM FRAM ING DIMENSIONS Side Wall See the section MINIMUM CLEARANCE...

Страница 21: ...ommended to do so at this time 2 A hole must be made in the back of the replace to accommodate the pellet vent Connect the pellet vent to the back of the stove and position in place Refer to manufactu...

Страница 22: ...A non combustible hearth must cover the ooring underneath as well as extend a minimum of six in front and to both sides of the heater Install oor protection if necessary PRIOR TO INSTALLATION INSTALLA...

Страница 23: ...he insert into a built in combustible enclosure 1 Install oor protection 2 Frame structure maintaining minimum clearances Locate and frame openings for both the exhaust and outside air Outside air is...

Страница 24: ...the rear using the four 8 32 x 3 8 screws washers and nuts FIGURE 29 6 The three pieces of trim are assembled in the same manner as a picture frame Place the corner brackets with screw loosened into t...

Страница 25: ...the bag may come in contact with the heater causing the bag to melt and the pellets to spill DO NOT load pellets into the hopper if they have been exposed to moisture Moisture can cause pellets to sw...

Страница 26: ...RT switch 2 Rotate the Pellet feed dial rate to optimum 3 Adjust the air control rod to the preferred setting this position will vary depending on venting con guration and fuel quality 4 If the heater...

Страница 27: ...or well away from combustible materials pending nal disposal If ashes are disposed of by burial in soil or otherwise locally dispersed they should be retained in the closed container until all cinders...

Страница 28: ...3 The burn pot requires cleaning 4 The exhaust system requires cleaning 5 The heater requires adjustment 6 Poor pellet quality MAKE SURE PELLETS ARE NOT PILING UP Figure 39 With the heater cool or wea...

Страница 29: ...ot Make certain that all openings are clear of any build up of ash from the ledge below the burn pot CLEANING THE BURN POT Re install the burn pot ensuring it sits level in the heater Also must ensure...

Страница 30: ...acuum out the entire hopper The dust and any other debris near the bottom should be removed to prevent excessive build up VACUUM HOPPER Figure 44 Cleaning the Optional Plated Surfaces Fingerprints or...

Страница 31: ...h exhaust port located on either side of the re box Remove the exhaust port doors and set aside on a non combustible surface SEMI ANNUALLY OR EVERY TWO TONS OF PELLET Figure 47 CLEAN THE EXHAUST BLOWE...

Страница 32: ...paper can be easily slid out air may be leaking around the door seal Carefully inspect the door gasket and door catch Inspect the door gasket to make sure it is fully attached Heater gasket cement can...

Страница 33: ...W415 0616 C 06 04 08 33 Figure 49 NORMAL OPERATING SOUNDS...

Страница 34: ...W415 0616 C 06 04 08 34 WIRING DIAGRAM Figure 51...

Страница 35: ...l parts can be or dered through your Authorized dealer or distributor When ordering replacement parts always give the following in formation 1 Model and Serial Number of the replace 2 Installation Dat...

Страница 36: ...W415 0616 C 06 04 08 36 COMMON REPLACEMENTS PARTS...

Страница 37: ...W415 0616 C 06 04 08 37 NPS40 REPLACEMENTS PARTS 57 38 61 44 63 65 57 64 56 58 59 60 66 15 31 39 54 40 53...

Страница 38: ...W415 0616 C 06 04 08 38 NPI40 REPLACEMENTS PARTS...

Страница 39: ...W415 0616 C 06 04 08 39 NPI40 ACCESSORY PARTS COMMON ACCESSORY PARTS...

Страница 40: ...run replace the blower If the motor runs have a dealer check the wire harness See The heater will not operate when hot section Contact your local dealer or a certi ed technician for service Push the...

Страница 41: ...lower controller replace the sensor If the motor is still on high re connect the sensor and replace the convection blower controller General Check the hopper for fuel Incorrect air damper setting may...

Страница 42: ...art replace the switch Due to different installation set ups length and size of venting and fuel quality the low feed setting from the factory will not always be correct It may be necessary to experim...

Страница 43: ...SERVICE AND MAINTENANCE LOG Dealer s Name Dealer s Address City State Province Zip Code Postal Code Serial Number Date of Purchase Date Installed Notes OWNERSHIP RECORDS SERVICE DATE SERVICE TECHNICI...

Страница 44: ...W415 0616 C 06 04 08 44 NOTES...

Отзывы: