19
[66]Ambush Report Code
Program a 2-digit report code for Ambush.
To send an ambush report, program a User
Code for User 4, Program report User 4 as
Ambush [20-4] and Select reporting for Telco
1 [36-2] and/or Telco 3 [56-2].
(QKDQFHG &RPPXQLFDWRU )HDWXUHV
[67]Telephone Number 1
(1) Opening After Alarm (Cancel Code) -
When enabled, all users that are not se-
lected to report on
Opening/Closing [39] will
report an Opening only
when opening after
an alarm has occurred.
(2) Conditional Closing Telephone 1 -
When enabled, all users that are not se-
lected to report an Opening/Closing ([39],
[59]) will report a Closing only
when zones
have been bypassed. The Zone Trouble
Code [62-2] is used to report zones that have
been bypassed at the time of the closing
report.
(3) Reserved
(4) Reserved
[68]Telephone Number 3
(1) Opening after Alarm (Cancel Code) -
see [67-1].
(2) Conditional Closing Telco 3 - see
[67-1].
(3) Reserved
(4) Reserved
:LUHOHVV
Up to two receivers can be wired to the
XP-400. Each wireless transmitter can be
mapped to a zone. Only 1 wireless device
is permitted per zone, however, the use of
both hardwired and wireless on a zone is
permitted.
To Map a transmitter to a zone:
1. Enter the Programming Block Number
that the transmitter is to be mapped to.
2. Enter the 7-digit RF ID number directly,
just as it is shown on the device label.
After the 7th digit is entered the keypad
will beep.
A transmitter will send a transmission every
time it is tripped. The transmitter also sends
a supervisory transmission about once every
hour. If the receiver does not receive a
signal from a transmitter in the time pro-
grammed in Wireless Supervisory Timer, a
system trouble ’RF Supervisory Failure' will
be indicated at the keypad.
Program Wireless Supervisory Timer [16] to
change the supervisory time from the default
of 12 hours.
The Signal strength of a transmitter can be
checked at the keypad (see
Fault
Find Mode).
Wi853c
page 19
Tuesday, September 16, 1997 10:42