6.  Install Smoke Sensors (cont'd)

 

A smoke alarm should be 

 

located between the sleeping 

area and the rest of the family 

living unit.

 

In family living units with more 

than one sleeping area, a smoke 

alarm should be provided for 

each separate sleeping area.

 

Indicates required smoke detector 

 

Indicates optional smoke detector if 

door is not provided between Living 

and Recreation rooms. 

A smoke detector should be 

located on each story 

NFPA STANDARD FOR SMOKE

-

DETECTOR LOCATION

 

The ISEC-SMOKE should be installed in accordance with the National Fire Protec-

tion Association (NFPA) Standard 72.  For your information, the National Fire Protection 
Association's Standard 72, reads as follows: 

11.5.1  One- and Two-Family Dwelling Units. 

11.5.1.1  Smoke Detection Where required by applicable laws, codes, or standards 

for the specified occupancy, approved single- and multiple-station smoke alarms shall 
be installed as follows:  (1) In all sleeping rooms.  Exception:  Smoke alarms shall not be 
required in sleeping rooms in existing one- and two- family dwelling units.  (2) Outside of 
each separate sleeping area, in immediate vicinity of the sleeping rooms.  (3) On each 
level of the dwelling unit, including basements.  Exception:  In existing one- and two-
family dwelling units, approved smoke alarms powered by batteries are permitted. 

11.8.3  Are  More  Smoke  Detectors  Desirable?    The  required  number  of  smoke 

detectors might not provide reliable early warning protection for those areas separated 
by a door from the areas protected by the required smoke detectors.  For this reason, it 
is recommended that the householder consider the use of additional smoke detectors 
for those areas for increased protection.  The additional areas include the basement, 
bedrooms, dining room, furnace room, utility room, and hallways not protected by the 
required  smoke  detectors.    The  installation  of  smoke  detectors  in  kitchens,  attics 
(finished or unfinished), or garages is not normally recommended, as these locations 
occasionally experience conditions that can result in improper operation. 

There exist certain situations where the presence of a smoke alarm is not effective, 

such as smoking in bed, the testing of gas leaks with a flame or for warning against the 
existence of high carbon monoxide levels inside a family living unit.  Current studies 
have shown smoke alarms may not awaken all sleeping individuals; it is therefore the 
responsibility of individuals in the household that are capable of assisting others to pro-
vide assistance to those who may not be awakened by the alarm sound and to provide 
assistance to those who may be incapable of safely evacuating the area unassisted.   

For family living units with one or more split levels (i.e., adjacent levels with less than 

one  full  story  separation  between  levels),  a  smoke  detector  required  as  above  shall 
suffice for an adjacent lower level, including basements.  Exception: Where there is an 

intervening door between one level and the adjacent lower level, a smoke detector shall 
be installed on the lower level. 

• 

Ceiling-mounted smoke alarms should be located in the center of the room or hall, 
or not less than 4 inches from any wall.  When the detector is mounted on a wall, 
the top of the detector should be 4 to 12 inches from the ceiling. 

• 

Do not install smoke alarms where normal ambient temperatures are above 100°F 
(37.8°C), below 40°F (4.4°C) or greater than 92% humidity unless the alarm has 
been determined to be capable of being used at installation points with higher or 
lower ambient temperatures.  Also, do not locate alarm in front of air conditioners, 
heating registers, or other locations where normal air circulation will keep smoke 
from entering the detector.  Installing smoke detectors in kitchens, garages or fur-
nace rooms is NOT recommended. 
All installation wiring must be in accordance with the provisions of Article 210 of the 

National Electrical Code, ANSI / NFPA 70.  All protected premises fire alarm systems 
shall be maintained and tested (at least once every month) in accordance with NFPA 
72. 

FIRE PREVENTION AND ESCAPE

 

The purpose of an early warning smoke alarm is to detect the presence of fire in its 

early stages, and sound an alarm giving the occupants more time to exit the premise 
before the smoke reaches a dangerous concentration level. 

Fires start even with the best of housekeeping and fire-prevention procedures.  Fire 

is an unexpected event.  Early warning detection alerts occupants in time to act. 

 

KNOW  FIRE  HAZARDS

.  No detection device can protect life in all situations.  

Therefore, safeguards should be taken to avoid such potentially dangerous situations as 
smoking in bed, leaving children home alone, cleaning with flammable liquids such as 
gasoline.  The best fire protection is minimizing fire hazards through proper storage of 
materials and general good housekeeping techniques.  A cluttered basement, attic, or 
other storage area is an open invitation to fire. 

Careless use of combustible materials and electrical appliances, or overloading of 

electrical outlets are other prime causes in starting fires.   

It is most important that explosive and/or fast-burning materials be eliminated from 

the home if at all possible.  Even after proper precautions have been taken, fires can 
start.  Be prepared. 

 

IN  CASE  OF  FIRE

.  Leave immediately.  Don’t stop to pack or search for valua-

bles.  In heavy smoke, hold your breath and stay low -- crawl if necessary.  The clearest 
air is usually at the floor. 

If you have to go through a closed door, carefully feel the door and door knob to see 

if undue heat is present.  If they seem relatively cool, brace your foot against the bottom 
of the door with your hip against the door and one hand against the top edge.  Open it 
slightly.  If a rush of hot air is felt, slam the door quickly and latch it.  Unvented fire tends 
to build up considerable pressure.  Be sure all the household realizes and understands 
this danger. 

Use your neighbor’s phone or a street fire alarm box.  The job of extinguishing the 

fire should be left to the professionals.  Too many unforeseen things can occur when 
inexperienced people try to extinguish afire. 

 

BE  PREPARED

.  Perform fire drills regularly.  Use them to assure recognition 

of an alarm signal.  For your protection, simulate different circumstances (smoke in hall, 
in living room, etc.).  Then have everyone react to the situation. 

Draw a floor plan and show two exits from each room.  Frequently, a knotted rope 

or ladder from a window will serve this purpose.  It is important that children be instruct-
ed carefully, because they tend to hide in times of crisis. 

It  is  imperative  that  one  meeting  place  outside  the  home  be  established.    You 

should insist that everyone meet there during an alarm.  This will eliminate the tragedy of 
someone reentering the house for a missing member who is actually safe.   

If you have children and/or invalids residing in your household, you can help your 

fire department.  Most fire departments have window decals available for use in chil-

dren’s or invalid’s bedrooms.  Properly used, these decals will quickly identify sleeping 

quarters of these individuals and show the department where to look first for members of 
your household.

 

Additional information on Household Fire Warning is available at nominal cost from The 
National  Fire  Protection  Agency,  Batterymarch  Park,  Quincy,  MA  02269.    Request 
Standard No. NFPA 72. 

Содержание iSecure

Страница 1: ...Napco iSecure Security System All technical manuals are available in PDF format at tech napcosecurity com 1 NAPCO 2021 WI2240ALF 6 21...

Страница 2: ...It is subject to change without notice Companies names and data used in examples herein are fictitious unless otherwise noted Napco assumes no responsibility for incor rect information this manual ma...

Страница 3: ...Install the ISEC ZWAVE 40 Install the ISEC EXTANT KIT optional 41 Go Anywhere Smart Hub Icons 43 PROGRAMMING Programming Keypads Touchscreens 44 Programming Motion Sensors 45 Programming Glass Break S...

Страница 4: ...382LF Hub tamper in stallation instructions included All Kits support up to six 6 ISEC WL KEYPADs and or ISEC WL TOUCHs combined When the Go Anywhere Hub is connected to a network with a Wi Fi access...

Страница 5: ...gin Refer to the OI404LF card and enter your Dealer User ID Password and Radio ID iSecure LTE ID Click Submit D Click General Settings and in the Master Security Code field enter the Master Code also...

Страница 6: ...within 15 minutes of checkout With iSecure a new subscriber account will automatically be created A Dealer User ID and temporary Password will be emailed to you the dealer upon activation This tempora...

Страница 7: ...r the first time In the confirmation popup click Yes download to send all changes to the Go Anywhere Smart Hub Network MAC Unique Media Ac cess Control identifier assigned to the integral network inte...

Страница 8: ...to enable the IP path of the integral dual path radio communicator this selection is available depending on plan purchased Configuration Type Click the Configuration Type pull down to select the re po...

Страница 9: ...e iSecure Cloud Web Portal Note Radio will reboot after the successful download of new IP configurations IMPORTANT Some police and or fire departments require alarm permits contact each department do...

Страница 10: ...or 5AH battery not supplied observing polarity secure battery with Velcro strap 7 Remove the plastic protective film from the face of the Go Anywhere Hub STAND ALONE INSTALLATIONS If placing on a she...

Страница 11: ...s speakers or a mechanical bells this terminal and BELL Any self contained external siren requiring a 12V supply can be connected When connecting a mechanical bell it must be supervised using a 2 2k O...

Страница 12: ...o place 4 Drill the two keypad mounting holes four holes with the IBR TOUCH WL in the mounting surface When mounting to hollow drywall or similar surface we recommend using wall anchors or similar har...

Страница 13: ...security system keypad tap Keypad Only jump to step 6 To include video camera and Z Wave functions tap Full Functionality 4 5 Add the IBR TOUCH WL Tablet Kit 3 Only The steps below are the only steps...

Страница 14: ...dministrator account User ID and Password and tap Finish 10 Upon connection to the Internet based ac count for the iSecure system the resulting keypad shown in step 12 will be configured for the payme...

Страница 15: ...ON The ISEC MOTION is an advanced PIR sensor designed for use with Napco s wireless receivers The unit is powered by two sup plied 3 volt lithium batteries estimated battery life 3 years If bat tery v...

Страница 16: ...as a template to mark mounting holes on the wall The sensor must be in direct line of sight of all windows being protected Reliable detection cannot be expected around cor ners in other rooms etc For...

Страница 17: ...ector is mounted on the same wall as the glass point the tester at the opposite wall If the LED on the detector comes on for about 4 seconds when the tester is triggered the glass is within detection...

Страница 18: ...DESCRIPTION The ISEC DW XMITTER is a low profile window door transmitter designed for use in Napco iSecure wireless systems Used with the supplied magnet the transmitter functions as a window door se...

Страница 19: ...location to mount the ISEC SMOKE Note Mounting the ISEC SMOKE on foil backed wallpaper is NOT recommended because the radio range will be reduced The ISEC SMOKE is a high quality photoelectric smoke...

Страница 20: ...e correct zone on the Hub and that the correct report is sent to the central sta tion NOTE Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found s...

Страница 21: ...utomatically exit this mode after 5 minutes Note If smoke is still present in the chamber after exiting Silence mode the detector will go into alarm again IMPORTANT Use proper polarity when installing...

Страница 22: ...eratures Also do not locate alarm in front of air conditioners heating registers or other locations where normal air circulation will keep smoke from entering the detector Installing smoke detectors i...

Страница 23: ...onitor and annunciate low battery Coding switches are not required or used in the ISEC HEAT Each transmitter is assigned a unique identification code number at the factory The transmitter is powered b...

Страница 24: ...ystem Test system with unit mounted If the system is monitored notify the central station of the impending test The rate of rise feature may be tested by a quick applica tion of heat from any convenie...

Страница 25: ...ta or Sanyo type 123A battery in its compart ment observing correct polarity Enroll the ISEC CARBON MON into the Hub before mounting During power up and status initialization both the green and red LE...

Страница 26: ...ss and hold the re cessed TEST button for approximately 2 seconds The detector will temporarily go into alarm and the red LED will illuminate b Within a few seconds the green LED will start to blink r...

Страница 27: ...e equipment manufacturer s doc umentation or contact the manufacturer s directly for more information about how the equipment can leak carbon monoxide into the premises Ensure all motor vehicles are n...

Страница 28: ...installation instructions in their entirety be fore installing the ISEC CARBON MON detector Leave these instructions with the owner user of the detector The ISEC CARBON MON is intended for use in ind...

Страница 29: ...detector indicates an end of life condi tion whichever comes first CO detectors are not a substi tute for designated life safety devices Napco does not war rant or imply in any way that a CO detector...

Страница 30: ...uit board no more than 45 degrees see Figures 1 and 2 to allow removal of batteries from the bottom circuit board 3 Slide the bottom battery out and away from the circuit board Figure 3 Top View of Bo...

Страница 31: ...to which transmitter is applicable The 6 digit RF ID code with checksum digit printed on the transmitter enter all numbers and or letters including lead ing zeros if any Aux 1 option and Aux 2 option...

Страница 32: ...t 3 Use the supplied double backed tape to secure the Tamper Magnet to the wall do NOT use any screws near electrical wiring that runs inside walls 4 At the wall outlet remove the wall cover plate scr...

Страница 33: ...on If RESET is not pressed the battery trouble will self restore in 4 hours if the battery voltage always remains above the minimum level during this time TERMINAL DESCRIPTIONS Configure all inputs an...

Страница 34: ...through JP12 for ZONE 8 Each zone 1 8 is assigned to terminals Z1 through Z8 respectively Notice each jumper block labeled JP5 through JP12 contains vertical 4 pins FIRE top two pins Selected zone rep...

Страница 35: ...UMPER ZONE 1 FIRE CO BURG SET JUMPER ZONE 7 FIRE CO BURG SET JUMPER ZONE 8 FIRE CO BURG P2 1 2 3 4 5 6 BAT BAT DC DC 12 18VAC TRANSFORMER Control panel power or auxiliary power supply FIRE CO BURG ZON...

Страница 36: ...zone 7 FIRE PR Connects to the positive terminal of the two wire smoke sensor Z8 Connects to the negative terminal of the two wire smoke sensor zone 8 Connect the 2 wire smoke detectors to the Go Anyw...

Страница 37: ...MOD INSTALLATION If the Go Anywhere Smart Hub enclosure is not already open open the enclosure as directed on page 10 step 3 Remove all A C and battery power and install the ISEC 2WF MOD into the iSe...

Страница 38: ...t secure the Go Anywhere Hub motherboard PCB to the front housing See the arrows in Fig 2 for screw locations 8 With the ISEC WIFI PC board in hand connect the small Antenna Board plug to the ISEC WIF...

Страница 39: ...orks pull down find and select the SSID name of the customer s network Upon selection the Security Type and Selected Network fields will automatically populate Type the Password of the customer s Wi F...

Страница 40: ...our body or clothing Use a grounded wrist strap or touch an unpainted grounded metal object If replacing an older version of the ISEC ZWAVE first down load the latest version of the Z Wave firmware at...

Страница 41: ...e front LED Faceplate to the front housing 4 Remove the LED Faceplate From the front of the housing pull out the LED Faceplate to remove 5 On the inside of the LED Faceplate remove the screw that secu...

Страница 42: ...lose the two parts of the Hub housing routing the cable out the rear access door see Fig 9 Be sure not to crimp the wire between the PCB and the housing Closing the two parts of the Hub housing will r...

Страница 43: ...Receiver trouble due to excessive radio noise in area Try relocating the Smart Hub Otherwise call for service Rapid Flicker Transmissions in progress Flashing 900MHZ peripheral download Status Off No...

Страница 44: ...he ISEC WL TOUCH press and hold the appropriate FIRE AUX or PANIC button respectively see the User s Guide for details By default Emergency Buttons are ena bled for all keypads to disallow their use s...

Страница 45: ...R FUNCTION Select Instant or Interior When armed STAY usually when sleeping and you want the motion to ignore movement within the home select Interior If you want the sensor to immediately trigger an...

Страница 46: ...it sensor ID for the device 4 DESCRIPTION Type the sensor descrip tion you wish to appear on the keypad display AREA Default 1 See the key pad Operating Guide for the definition of Area SENSOR FUNCTIO...

Страница 47: ...or For example use for an interior door that will be in use when armed STAY but protected when armed AWAY Instant Allows for an immediate alarm when activated providing instant protection while you or...

Страница 48: ...N Type the sensor descrip tion you wish to appear on the keypad display SENSOR TYPE Select Smoke Sensor SENSOR FUNCTION Smoke is au tomatically se lected when Smoke Sen sor is selected as the SENSOR T...

Страница 49: ...on the keypad display SENSOR TYPE Select Heat Sensor SENSOR FUNCTION Heat is auto matically select ed when Heat Sensor is se lected as the SENSOR TYPE SENSOR ID Type in the 7 digit sen sor ID for the...

Страница 50: ...or DESCRIPTION Type the sensor descrip tion you wish to appear on the keypad display SENSOR TYPE Select Carbon Monoxide SENSOR FUNCTION CO Alarm is automatically selected when Carbon Mon oxide is sele...

Страница 51: ...the following Instant Allows for an immediate alarm when the panic button is pressed providing instant protection 24Hr Zone Audible Provides protection at all times whether or not the system is armed...

Страница 52: ...e Select to disable the designated key Key 3 and or Key 4 Panic Pressing the designated key causes the siren to sound and sends a panic report to the central station Instant Pressing the designated ke...

Страница 53: ...in any Area ISEC WL SIREN Wireless Siren TYPE Sirens can be powered by an AC power supply plugged into a 120VAC unswitched wall outlet or with batteries Select the power type used by your siren NAME...

Страница 54: ...ired zone to the RF ID of the supervised 900MHz wireless zone up to 8 zones for each ISEC WL MODULE In the TAKEOVER screen shown below for the Takeover Module added previously program each column as d...

Страница 55: ...umn 3 To add a new Code click in a blank USER CODES field and enter the new User Code up to 6 digits To erase or change an existing Code simply clear or re enter the User Code 4 Add a check to either...

Страница 56: ...ng to establish a connection if this code is forgotten the Master Security Code of the particular Go Anywhere Hub can be used in its place Dealer Keypad Programming Code This code is left blank in the...

Страница 57: ...at you wish to be used in text and email notification messages to help you identify the iSecure system installation Video Security Z Wave Remote Access Check to enable access to each service from the...

Страница 58: ...can also be configured to allow Wi Fi con nections to only specific MAC Addresses Displays the MAC Address of the Go Anywhere Hub in an easy to copy field should it be needed Users Displays the USER I...

Страница 59: ...sor within the Go Anywhere Hub that controls the radio communications between the Hub and the wireless de vice s Other iSecure Cloud Web Portal Screens cont d RadioHardware Version refers to the versi...

Страница 60: ...relocate the Go Anywhere Smart Hub or the device so they are in closer proximity E 05 NN Transmitter Low Battery When an RF device has a weak battery an error E 05 appears The NN is a two digit number...

Страница 61: ...top as shown in the image Note Never use the jumper position N A Use hearing protection siren is rated at 85dBA Do not apply AC power when rear cover is open 1 Remove AC and batteries 2 Remove jumper...

Страница 62: ...h the same type as specified above Use of other types may present a risk of fire or explosion Nev er recharge or disassemble a battery or dispose of in fire E06 NN Receiver Response Failure Call insta...

Страница 63: ...TER When the test is initiated data is transferred back and forth be tween the keypad and Hub When finished the signal levels of both the keypad and Hub are displayed and a beep is heard in the sequen...

Страница 64: ...Secure system might be interfering with the system to be installed the ISEC WL KEYPAD can be used as a scanner to scan for the presence of other nearby iSecure radio signals and determine if the nearb...

Страница 65: ...unication link between the Hub and the ISEC WL TOUCH keypad was interrupted If Out of System this field will count down AutoEnroll This feature is a quick and easy way to enroll wireless devices into...

Страница 66: ...w E02 00 will appear in the display indicating a low battery condition Allow 24 hours for the battery to recharge DISPLAY SYS TRBL Displays all system error codes troubles LOW BAT TERY AC POWER LOSS e...

Страница 67: ...pertinent information where necessary depending upon the event TO ARM IN 1 4 HRS Use this function to a delay programmed auto arming up to 4 hours 15 minutes or b initiate auto arming in 4 hours 15 mi...

Страница 68: ...scribed below tap Config ure otherwise tap Continue to App to return to the Home Screen or Test Again to repeat the test See page 13 for step by step instructions to help guide you through the Wiz ard...

Страница 69: ...1 3 5 7 10 15 and 20 minutes BSSID used to LOCKDOWN IBRIDGE Tap to enter a new broadcast SSID named BSSID in this menu to be stored in the touchscreen s memory to be used by default when the touchscre...

Страница 70: ...then connect power to the camera Do you wish to proceed with Wire less Camera Configuration 1 The camera must be powered and wirelessly con nected to the network before proceeding 2 Tap Yes to procee...

Страница 71: ...wish to disallow customer changes to the home automation Z Wave system unchecking disabling this setting disables the User Settings menu feature named Automation Management z wave Converse ly check t...

Страница 72: ...hours with network connection 32 hours ISEC KIT2 Battery Standby Hours 12V 4AH battery No network connection 25 hours with network connection 24 hours 12V 5AH battery No network connection 32 hours w...

Страница 73: ...RT HUB In cludes up to 80 wireless zones in 1 or 2 discrete Areas with keypad bus and other optional con nections Kits with the suffix V use the Verizon network A use the AT T network IBR TOUCH WL Sma...

Страница 74: ...s re ceivers The ISEC MOTION is powered by two supplied 3 volt lithium batteries estimated battery life 3 years When battery voltage drops below normal a low battery report will be sent to the re ceiv...

Страница 75: ...Wireless Siren Mounting Template Slide Screw Use with battery powered units only Magnet 1 5 8 Align this centerline with Wall Socket 7 16 Magnet Screws 2 Use with battery powered units only Center Lin...

Страница 76: ...76 All technical manuals are available in PDF format at tech napcosecurity com Napco iSecure Security System Notes...

Страница 77: ...rews 2 Use with battery powered units only Center Line of Wall Socket 5 1 4 Screw Hole Tab Align this centerline with Wall Socket This template shows the unit plugged into the bottom receptacle but ei...

Страница 78: ...78 All technical manuals are available in PDF format at tech napcosecurity com Napco iSecure Security System ISEC WL MODULE Takeover Module Wiring Diagram...

Страница 79: ...Napco iSecure Security System All technical manuals are available in PDF format at tech napcosecurity com 79 iSecure Hub Wiring Diagram LA3550A3...

Страница 80: ...he product Seller s warranty as hereinabove set forth shall not be enlarged diminished or affected by and no obligation or liability shall arise or grow out of Seller s rendering of technical advice o...

Отзывы: