9 Description of the object dictionary
Access
read / write
PDO mapping
no
Allowed values
Preset value
00000001
h
Description
Each subindex of the object stands for a certain memory class. By reading out the entry, it is possible to
determine whether (value "1") or not (value="0") this memory category can be saved.
To start the save process of a memory category, value "65766173
h
" must be written in the corresponding
subindex. This corresponds to the decimal of 1702257011
d
or the ASCII string
save
. As soon as the saving
process is completed, the save command is again overwritten with the value "1", since saving is possible
again.
For a detailed description, see chapter Saving objects.
1011h Restore Default Parameters
Function
This object can be used to reset all or part of the object dictionary to the default values.
Object description
Index
1011
h
Object name
Restore Default Parameters
Object Code
ARRAY
Data type
UNSIGNED32
Savable
no
Firmware version
FIR-v1426
Change history
Firmware version FIR-v1436: "Object Name" entry changed from
"Restore Default Parameter" to "Restore Default Parameters".
Firmware version FIR-v1436: The number of entries was changed
from 2 to 4.
Firmware version FIR-v1512: The number of entries was changed
from 4 to 5.
Firmware version FIR-v1512: "Name" entry changed from "Restore
The Comm Default Parameters" to "Restore Communication Default
Parameters".
Firmware version FIR-v1512: "Name" entry changed from "Restore
The Application Default Parameters" to "Restore Application Default
Parameters".
Firmware version FIR-v1540: The number of entries was changed
from 5 to 7.
Value description
Subindex
00
h
Name
Highest Sub-index Supported
Version: 2.0.1 / FIR-v1650
115