background image

  

11 of 31

www.NabcoEntrances.com 

GT1175 Slide Door Opus Control Wiring and Programming Manual

Rev. 8-11-21 

P/N C-00391

SECTION 6.2: Resetting a Type 2 Control back to a Type 1 Control

Note:  When resseting to default the control BA is N.C. and sim pair setting is Single door.

There can never be (2) Master Controls, or (2) Slave Controls. There must always be (1) Master Control, and (1) Slave Control.

1. Go to the Control without activation devices connected to it. This will be the Slave Control (Type 1). Perform a Factory Reset.

1. Press down on the Rotary Dial until the next screen is displayed.
2. Turn the Rotary Dial clockwise to highlight (Reset to Default Set). 
3. Briefly press down on the Rotary Dial. Enter the passcode: 0045.

1. Turn the Rotary Dial clockwise to highlight a preferred number, then briefly press down. 

2. Repeat until the passcode is complete.

4. Briefly press down on the Rotary Dial to display the (Setting Category) Screen.

DN 2428

Passcode

Reset to Default Set

Stroke Learning

Yes   No

Reset to Default Set

0

If you don’t know

the passcode, 

Keep Pushing Switch, 

Return to normal mode

11

20

10

12

Type: 1

GT1175 Opus Slide

Status:

Fully Closed

Error:

-----

Ac va on: IN EXT

Posi on:

> > > > > > > > >

Other:

BA  6B  SWL

Push and Hold Dial

Go to Se  ng Mode

Copy Data (SimPair)?

               Yes    

No

11

20

10

12

Type: 2

GT1175 Opus Slide

Status:

Fully Closed

Error:

-----

Ac va on: IN EXT

Posi on:

> > > > > > > > >

Other:

BA  6B  SWL

Push and Hold Dial

Go to Se  ng Mode

Figure 8 

Reset Control

2. Turn the Rotary Dial to highlght (Optional Setting). Briefly press down on the Rotary Dial. Turn the Rotary Dial to highlight 

(Simpair Setting). Briefly press down on the Rotary Dial to select.

3. Turn the Rotary Dial to highlight the desired Paired Setting. Briefly press down on the Rotary Dial to select.
4. Press and hold the Rotary Dial until the (Setting Category) screen is displayed.     
5. Press and hold the Rotary Dial until the (Copy Data) Screen is displayed. 
6. Turn the Rotary Dial to select (NO). 
7. Briefly press down on the Rotary Dial. The Type 2 (Master Control) will automatically reset to the Type 1 (Slave Control).

SECTION 6.3: Customized Programming/Settings for (1) Control only

Note:  Customized Programming/Settings can be done for (1) Control without losing data previously saved for (2) Controls.

Sometimes Programming/Settings need to change for (1) Control only. For example, Door (1) needs to open faster than Door (2).

1. Go to the Type 1 (Slave Control) or Type 2 (Master Control). Program any/all new settings.
2. Press and hold the Rotary Dial until the (Copy data) Screen is displayed. 
3. Turn the Rotary Dial to select (NO).

a.  Customized Programming/Settings will only be saved to (1) Control.

Copy Data (SimPair)?

               Yes    

No

DN 2313

Figure 9 

Programming/Settings for (1) Control

Содержание GYRO TECH GT-1175

Страница 1: ...into the myNABCO portal 4 SECTION 2 4 QR Code Links 4 CHAPTER 3 GETTING STARTED 4 SECTION 3 1 Features 4 SECTION 3 2 Wiring 5 SECTION 3 3 General Specifications 5 SECTION 3 4 Electrical Specifications...

Страница 2: ...LIDE DOOR WIRING DIAGRAMS 19 SECTION 11 1 Single Slide Door with Acusensor M and Holding Beam w monitoring 19 SECTION 11 2 Telescopic Slide Door with Acusensor M and Holding Beam w monitoring 20 SECTI...

Страница 3: ...t all power to the junction box prior to making any electrical connections Failure to do so may result in serious personal or fatal injury When uncertain whether power supply is disconnected always ve...

Страница 4: ...ting sliding doors using U01 U19 controls Contact Customer Service at 1 888 679 3319 to purchase Retrofit kits SECTION 2 3 Request a User Name Password to gain access into the myNABCO portal To gain a...

Страница 5: ...O factory utilizes Underwriters Laboratories UL recognized component wire terminals and connector housings to manufacture all Automatic Door systems Table 1 Power Draw Common Accessories Sensor Part N...

Страница 6: ...2 clicks to advance through each menu item Clockwise To scroll forward through screens and programming options Counterclockwise To scroll backward through screens and programming options DN 2429 Type...

Страница 7: ...Range Open Timer Reac on Power Open Recycle Sens Close Recycle Sens A er Open Recycle Op onal Se ng Hold Close Force Power Close Range Manual Open Func on Manual Open Sens Manual Open Timer BCHK Lock...

Страница 8: ...ions Displays the current status of all of the Input Output lines of the terminal strip SECTION 4 2 Level Two Access Screen Note The Activate Passcode option is only displayed in the event 0045 had no...

Страница 9: ...g History Data LEVEL 3 Low Energy or Full Low Full Rotate Dial LEVEL 4 LEVEL 2 Long Push Long Push CHAPTER 5 STROKE LEARNING DN 2314 11 20 10 12 Type 1 GT1175 Opus Slide Status Slow Closing Error Ac v...

Страница 10: ...at the top Opus Controls are labeled Type 1 or Type 2 Type 1 should be considered the Slave Control Type 2 should be considered the Master Control X All Activation Devices and main harness are connect...

Страница 11: ...ta SimPair Yes No 11 20 10 12 Type 2 GT1175 Opus Slide Status Fully Closed Error Ac va on IN EXT Posi on Other BA 6B SWL Push and Hold Dial Go to Se ng Mode Figure 8 Reset Control 2 Turn the Rotary Di...

Страница 12: ...d ATTENTION Bi Parts are set up as Left Hand Left Right Left From the Exterior Side of Building determine which Handing to enter Left or Right RIGHT HANDING DN 1326 LEFT HANDING EXTERIOR SIDE OF BUILD...

Страница 13: ...ormal Sim Pair If selected before returning to last screen option to copy settings to other Control is given Double Egress The Activation signal only is shared between doors All other signals are inde...

Страница 14: ...nality N C Air lock Set for Air lock functionality Breakout Pass through Output closes when breakout occurs TrmnL H PassThrough Output changes state when input H changes state Door Sequencing Provisio...

Страница 15: ...ds door in open position Asia Only Do Not Use ANSI does not allow Activation Sensor to be mounted on the swing side of door If activated Opus will ignore the Activation Sensor while d oor is moving Th...

Страница 16: ...ettings are OFF by default except when used as 1175 Opus Slide in which case standard settings have monitoring enabled SECTION 8 6 History Setting History Data Parameter Description Operation Cnt Indi...

Страница 17: ...justment 11 20 10 12 Short Push Rotary Dial SECTION 9 2 Recycle Count Reset Opera on Cnt 0 cnt Open Recycle Cnt 0 cnt Close Recycle Cnt 0 cnt Latest Rcycl Posi on C1 0 Op 0 Clear Recycle Cnt 0 If you...

Страница 18: ...eep sufficient spacing between high voltage and low voltage wiring 120 VAC Power wires must be routed separate from other wiring located near the top of inside Header Ensure that incomming electrical...

Страница 19: ...40 P N M 01070 15 Breakout Jumper P N A 00385 BROWN GREY BLACK WHITE YELLOW RED GREEN BLUE ACUSENSOR M HARNESS P N A 01292 INTERIOR ACUSENSOR M P N V 00741 EXTERIOR ACUSENSOR M P N V 00741 OPTEX Hold...

Страница 20: ...eakout Jumper P N A 00385 BROWN GREY BLACK WHITE YELLOW RED GREEN BLUE ACUSENSOR M HARNESS P N A 01292 INTERIOR ACUSENSOR M P N V 00741 EXTERIOR ACUSENSOR M P N V 00741 OPTEX Holding Beam Controller P...

Страница 21: ...at the NABCO Factory Check to ensure both Opus Controls are programmed Under Op onal Se ngs Sim Pair Se ng is set to Normal Sim Pair For each Opus Control perform Stroke Learn Opus Control Types Type...

Страница 22: ...Terminal 3 4 Breakout connector is removed from main harness and blue wires are connected diretly to the breakout beam control OTHER WIRING NOT SHOWN FOR SIMPLICITY BLUE GREEN ORANGE ORG WHT RED BROW...

Страница 23: ...P N M 02043 Breakout Switch P N A 00758 Full Open P N A 00387 Fixed Sidelite BN BK Y RD Rocker Switch Extension 36 P N A 00967 BN BK Y RD Sensor 12 VD Ac va on Monitoring Common Control Main Harness B...

Страница 24: ...N A 01192 ACUSENSOR M P N V 00741 NOTES ON AN 1175 INPUT SWL IS SET TO SLOW OPEN BY DEFAULT IN THIS CASE THE DOOR WILL OPEN SLOWLY WHEN ACTIVATED DURING SIDELITE DETECTION IF INPUT SWL IS SET TO CONT...

Страница 25: ...RELAY OUTPUT 3 ELECTRIC STRIKE LOCK OUTPUT TIMER 1 5 1 5 seconds OPUS Assembly Single P N A 01418 Telescopic P N A 01420 GREEN Ground Power Switch OPUS Power Connector 1175 OPUS Electric Lock Harness...

Страница 26: ...TPUT TIMER 1 5 1 5 seconds BLACK Hot WHITE Neutral GREEN Ground OPUS Power Connector WHITE WHITE BLACK BLACK 1175 OPUS Electric Lock Harness Set P N M 02044 Power Supply P N V 00022 Magne c Lock GREEN...

Страница 27: ...r Switches with Key Switches 1 Replace the Rocker Switch with the Key Switch 2 Keep the Key Switch in 2 Way 3 Connect the Remote Switch to the Opus Control Terminals 11 and 14 for 1 Way Terminals 12 a...

Страница 28: ...CONTROLLER P N A 00129 Terminal 6 Terminal 1 Power Power Signal Signal Monitor Monitor SET TO MODE B 2 FLASHES 1 2 3 4 6 5 7 8 9 10 12 11 13 14 Optex OS 12C T Controller Terminal 7 Terminal 14 HOLDIN...

Страница 29: ...gnal to the door control to hold the door open until the threshold is clear and the beam is restored DN 1879 SINGLE SLIDE DOOR BI PART SLIDE DOOR Emit Rcvr Emit Rcvr Floor 21 inches 54 inches Floor 21...

Страница 30: ...atus should now show Fully Closed Must navigate back to the main screen as shown at right for an activation signal to work Hard to manually open door Software Revision up to and including 18 Re enter...

Страница 31: ...and adjust the recycle sensitivity and Open Close speed No Load No load error Check operator gear cracked belt skipped Electrical Lock Electrical lock error Check lock settings and wiring Ensure lock...

Отзывы: