background image

393230C

Bulletin B1594       Code Version 1.x

RIBWxxxB-EN2 Application Manual

Building Automation Applications

Bi-directional Control and Status: RIBWxxxB-EN2 installed at controller to RIBWxxxB-EN2 installed at load

• Transmits ON command when dry contact input is closed and OFF command when dry contact input is opened.
• Retransmits dry contact input state every 70-140 seconds.
• Relay output state is saved at power loss. Relay output is restored when power is recovered. (See *note at end of document)
• In this mode, one RIB can only be paired with one other RIB and no other devices.
• Dry contact input closure on RIB1 will activate relay output of RIB2. Dry contact input opening on RIB1 will deactivate relay output of RIB2. RIB2 controls RIB1 in same manner.
• Optional modes: Repeater (see page 5)

Load

60Hz A/C Power

DO

DI

BAS Panel

BAS C

on

tr

oller

O

rg

Ye

l

Wht/Red and Wht/Blu

Wht/Blu

Wht/Red

Yel

Org

Blk

Wht or Red

RIBWxxxB-EN2

RIBWxxxB-EN2

RIBX Series

(not included)

Bi-directional Relay Output and Dry Contact Sensor Input: Controller with Enocean Gateway [Enocean Equipment 
Profile A5-38-08] to RIBWxxxB-EN2 [Enocean Equipment Profile A5-30-02] installed at load

Bi-directional Learn Procedure
1. Apply power to both RIB’s.
2. Press and hold CLR button on RIB1 for 3 seconds until LED begins to flash.
3. LED will blink slowly.
4. Press and hold LRN button on RIB2 for 3 seconds to transmit teach telegram.

5. LED on RIB1 will stay ON for 4 seconds indicating telegram reception.
6. RIB2 will automatically listen for corresponding teach telegram which is automatically sent  
    from RIB1.
7. LED on RIB2 will turn ON for 4 seconds to indicate reception of teach telegram.

• Transmits on opening and closing of dry contact input and retransmits status every 70-140 seconds.
• Relay output state is stored at power loss. Relay output initiates in last stored state when power is restored. (See *note at end of document)
• In this mode, one RIB can only be paired with one PHC Gateway and no other devices.
• RIBWxxxB-EN2 only responds to Switching Command telegram from PHC Gateway (DB3 = 0x01). DB0.0 = 0 deactivates relay output and DB0.0 = 1 activates relay output. 
• Optional modes: Repeater (see page 5)

Load

60Hz A/C Power

BAS Panel

BAS Controller

with EnOcean®

Gateway

Wht/Blu

Wht/Red

Yel

Org

Blk

Wht or Red

RIBWxxxB-EN2

RIBX Series

(not included)

Bi-directional Learn Procedure
1. Apply power to RIB.
2. Press and hold CLR button on RIB for 3 seconds until LED begins to flash.
3. LED will blink slowly.
4. Follow instruction from PHC Gateway manufacturer to send teach telegram.

5. LED on RIB will stay ON for 4 seconds indicating telegram reception.
6. PHC Gateway should automatically listen for corresponding teach telegram which is  
     automatically sent from RIB.

page 1

Содержание RIBW B-EN2 Series

Страница 1: ...nds until LED begins to flash 3 LED will blink slowly 4 Press and hold LRN button on RIB2 for 3 seconds to transmit teach telegram 5 LED on RIB1 will stay ON for 4 seconds indicating telegram reception 6 RIB2 will automatically listen for corresponding teach telegram which is automatically sent from RIB1 7 LED on RIB2 will turn ON for 4 seconds to indicate reception of teach telegram Transmits on ...

Страница 2: ...its ON status every 70 140 seconds when current is above 3 Amps OFF command is only transmitted once when current is not present Relay output state is stored at power loss Relay output initiates in last stored state when power is restored See note at end of document Optional modes Repeater see page 5 Alarm see page 5 Delay see page 5 Learn Procedure 1 Apply power to RIBWxxxB EN2 and run current gr...

Страница 3: ...changes again 7 LED pattern will be FLASH FLASH FLASH OFF 3 flashes 8 Press and release the button on the switch you are learning three times quickly 9 LED on RIB will stay ON for 4 seconds indicating telegram reception 10 To learn another switch repeat steps 2 9 Occupancy Detection A Manual ON Auto OFF Occupancy Sensor Enocean Equipment Profile A5 07 01 and WST EN to RIBWxxxB EN2 Relay activates ...

Страница 4: ... unit with RIBWxxxB EN2 in Hotel Room Energy Control Mode RIBWxxxB EN2 in Momentary Mode with SWSK EN Wired through J Box Hotel Room Energy Control SWSDS EN and SWSK EN to RIBWxxxB EN2 Relay controls HVAC unit in hotel room If occupant removes keycard from SWSK EN or opens patio door the relay will shut down the HVAC unit or put it into setback mode if HVAC unit has that feature HVAC unit will be ...

Страница 5: ...y 4 Press and hold LRN button on RIB for 3 seconds until LED pattern changes 5 LED pattern will be FLASH FLASH OFF 2 flashes 6 Press and hold LRN button on RIB for 3 seconds until LED pattern changes again 7 LED pattern will be FLASH FLASH FLASH OFF 3 flashes 8 Press and hold the CLR button for 3 seconds until LED blinks twice indicating delay mode is enabled Disabling Delay Mode 1 Apply power to ...

Отзывы: