GT20 Wire and Programming Manual 

www.NabcoEntrances.com

P/N C-00140 

Rev 5-7-18

Element

Unit Type Default

Value

Description

FWind Full & Low

OFF

OFF

X

X

Obstacle detection optimized for exterior doors (wind loads).

X

X

Assuming that a gust of wind is not a hard obstacle which will stop the door, 

the motor current will rise “slowly”. In this case the GT20 Control will provide 

additional power to continue the door movement. 

X

X

When FWind is turned ON, Nabco strongly recommends the use of door 

mounted sensors to stop or re-open the door if an obstacle is detected during 

the door cycle.

OPEN

CLOSE

BOTH

Fo

Full Power

4

0...9

X

X

Opening force (force open) when an obstacle is detected during Open/Close 

cycle or both.

X

X

In standard mode Obstacle Detection can not be switched On/Off. It can be 

adjusted with parameters “Fo” = Opening force (force open) and v “Fc” = 

close force (force close). To make Obstacle Detection least sensitive: set both 

parameters on max. (= step 9). To make Obstacle Detection most sensitive: set 

both parameters on min. = 0 (caution this can allow the drive to react to small 

changes in wind).

Low Energy

9

0...9

Fc

Full Power

4

0...9

Low Energy

9

0...9

Foh

Full & Low

4

0...9

Hold-open force (force open hold)

Fch

Full & Low

0.0A

0.0A...3.5A

X

X

Interlocking Force (force close hold): automatically programs FLock and FDelay 

if these settings are set at 0.

X

X

If there is no electric lock and the Interlocking Force Fch is not adjusted, Error 

14/02 will be displayed as a warning after the Teach1 procedure and the Door 

Panel will endlessly re-open.

LowEn Low Energy

OFF

OFF

Door Panel is Full Power in both directions

ON

X

X

Door Panel is Low Energy in both directions

X

X

Door Panel is activated by a Knowing Act

Width

Full & Low

48

30...63

Door Panel width

Weight Full & Low

200

100...550 Door Panel height

Ao

Full & Low

95°

20°...190° Opening angle of the door (angle open)

Teach must be activated after this setting has been changed.

Rod

Full & Low

STD-PH

STD-PH

Outswing Arm and Arm Shoe

Push Function = Right Hand
Motor Cable Connector: X = Orange

SLI-PL

Inswing Arm with Track and Roller

Pull Function = Left Hand
Motor Cable Connector: Y = Green

SLI-PH

Outswing with Inswing Track and Roller Push Function = Right Hand

Motor Cable Connector: X = Orange

DO NOT USE

WIN-PH

Not Available

Not Available

DIR-PH

Outswing Arm and Track; Not Available

Push Function = Right Hand
Motor Cable Connector: X = Orange

DIR-PL

Outswing Arm and Track; Not Available

Pull Function = Left Hand
Motor Cable Connector: Y = Green

OHC-PH

Overhead Concealed

Push Function = Right Hand
Motor Cable Connector: X = Orange

OHC-PL

Overhead Concealed

Pull Function = Left Hand
Motor Cable Connector: Y = Green

Rod

Full & Low

STD-PH

X

X

If panic breakout latch is installed and the motor is plugged in backwards or the wrong arms 

are chosen during programming, there is a possibility the door can burst open unexpectedly 

towards the installer once TEACH mode is initiated.

X

X

Teach must be activated after this setting has been changed.

Содержание GT20

Страница 1: ...erator Manual P N C 00171 GT20 Owners Manual P N C 00170 for Decal Installation NABCO Price Book P N 16 9244 30 for Sensors Switches and Accessories Turn OFF all power to the Automatic Door if a Safet...

Страница 2: ...Procedure 22 SECTION 8 3 Reset Back to Factory Default 25 CHAPTER 9 PROGRAMMING 25 Table 5 The Four Levels of Menu Navigation 25 SECTION 9 1 The Home Page 26 Table 6 Door Panel Position 26 Table 7 Do...

Страница 3: ...ROUBLESHOOTING 37 SECTION 12 1 Malfunction with Error No 37 Table 20 Drive Mechanism Table 38 Table 21 Operating Table 39 Table 22 Safety Sensors Table 39 Table 23 Power Table 40 Table 24 Option 40 Ta...

Страница 4: ...and understand the General Safety Recommendations Warning Labels contained in this manual Failure to do so may result in bodily injury or property damage Read study and understand the installation and...

Страница 5: ...e installer and purchaser with the proper installation and operation of this system It is essential that this equipment be properly installed and operational before the door is used by the public It i...

Страница 6: ...andard for Power Limited Circuit Cables UL 13 or b Other cables with equivalent or better electrical mechanical and flammability ratings Attention Depending upon the installation the Power Switch Prog...

Страница 7: ...tomatic X X Door Panel is opened by an Activation Device or a Knowing Act X X Door Panel is closed upon expiration of the adjustable hold open time Night Door Panel can only be opened by an Activation...

Страница 8: ...a voltmeter DN 1209 Table 2 Terminals 1 13 Terminals 1 13 Description Description Description 1 Power Program Selector Switch 7 Reference Switch Connection 13 Joystick 2 Connection Terminals 8 Potenti...

Страница 9: ...SE Stop 16 SE Test 17 GND X106 Jumper N A N A X107 Safety Element Reverse 18 SE 24V 19 SE Rev 20 SE Test 21 GND X108 Motor or Electric Lock 27 EL 24V 28 GND 29 EL COM 30 EL NO 31 EL NC 32 EL Fb X110...

Страница 10: ...on the circuit Note It is recommended for the Installer to house all Incoming 120 VAC wires within an Electrical Conduit SECTION 7 1 Activation Devices DN 1261 Power Ac va on Devices Sensors Card Rea...

Страница 11: ...Safety element gn bl ge 5V OK max min 32 gn gn PG PO PI PU CG CH CL X117 SG X111 BG BU BD 14 15 17 18 19 21 COM N C PWR PWR COM N C PWR PWR Swing Side Door Mounted Sensor Approach Side Door Mounted S...

Страница 12: ...min 32 green green PG PO PI PU CG CH CL X117 SG X111 BG BU BD ERROR E Lock Relay red white 14 15 17 19 OUT 1 COM OUT 1 N C PWR PWR WARNING When Any Door Mounted Sensor Input is not Used A Jumper Must...

Страница 13: ...ND and 32 EL Fb Jumper provided by NABCO is needed between Terminals 28 GND and 29 EL COM Power for Lock 24 VDC 800mA max FAIL SECURE LOCK POWERED BY OTHER SOURCE FAIL SAFE and MAG Locks are wired to...

Страница 14: ...External Program Selector Motor Lock or Electric Lock Optionally Feedback signal Motor Lock or Electric Lock Softswitch El Fb NO NC Safety Element Reversing Swing Door Mounted Sensor Opening command i...

Страница 15: ...xternal Program Selector Motor Lock or Electric Lock for Master Optionally Feedback signal Motor Lock or Electric Lock Softswitch El Fb NO NC Safety Element Reversing Swing Door Mounted Sensor Opening...

Страница 16: ...ogram Selector Motor Lock or Electric Lock for Master Optionally Feedback signal Motor Lock or Electric Lock Softswitch El Fb NO NC Safety Element Reversing Swing Door Mounted Sensor Opening command i...

Страница 17: ...BUS External Program Selector Motor Lock or Electric Lock for Master Optionally Feedback signal Motor Lock or Electric Lock Softswitch El Fb NO NC Safety Element Reversing Swing Door Mounted Sensor Op...

Страница 18: ...nal Program Selector Motor Lock or Electric Lock for Master Optionally Feedback signal Motor Lock or Electric Lock Softswitch El Fb NO NC Safety Element Reversing Swing Door Mounted Sensor Opening com...

Страница 19: ...PU CG CH CL X117 SG X111 BG BU BD WARNING Total Power Consumption Of All Sensors And Powered Activation Devices Must Not Exceed 1 2 Amps To Other GT20 Control sim pair astragal sequenced doors GND COM...

Страница 20: ...tive Safety element gn bl ge 5V OK max min 32 gn gn PG PO PI PU CG CH CL X117 SG X111 BG BU BD 14 15 17 18 19 21 COM N C PWR PWR COM N C PWR PWR Swing Side Door Mounted Sensor Approach Side Door Mount...

Страница 21: ...r if used COM N O PWR PWR PG PO 16 20 PI PU 11 12 13 COM N O PWR PWR Activation Sensor WARNING When Any Door Mounted Sensor Input is not Used A Jumper Must Be In Place At Input Terminals 15 16 and 19...

Страница 22: ...e a Value Briefly push down on the Joystick to OK selection The Value will stop blinking indicating that the new Value has been entered Move the Joystick Down to select another Element Value option Up...

Страница 23: ...yed dAxis 2 8 in 7 Briefly push down on the Joystick The Value will start to blink on the lower half of the screen 8 Move the Joystick to the Right or to the Left to select 1 of the following Values 0...

Страница 24: ...on the lower half of the screen 26 Move the Joystick to the Right or to the Left to select 1 of the following Values 0 14 27 Move the Joystick Down to until the Element Inverse OFF is displayed Inver...

Страница 25: ...d begin to close normally While the door is closing about way through the cycle the control will bring the door to an abrupt stop for about three seconds then it will continue to allow the door to clo...

Страница 26: ...ounted sensor Approach Side Safety Signal OEI Interior activation sensor Interior Activation Signal SEF Door mounted sensor for obstacle detection Recycle Sensitivity KEY Activation device for NIGHT m...

Страница 27: ...locity closed Low Energy 9 0 9 TOEx Full Power 3s 0 60s TOEx sets the hold open time resulting from activation signals from devices connected to terminals 9 10 for exterior activation and terminals 12...

Страница 28: ...k and the Interlocking Force Fch is not adjusted Error 14 02 will be displayed as a warning after the Teach1 procedure and the Door Panel will endlessly re open LowEn Low Energy OFF OFF Door Panel is...

Страница 29: ...atically set to Ao ASER 0 0 60 Lock out angle Angle at which push side door mounted sensor is ignored just before closing inac ve DN 1188 closed ASES closed SES open A S E R SER inac ve Element Defaul...

Страница 30: ...ning OPEN Relay switches when the Door Panel is fully open CLOSING Relay switches when the Door Panel is closing ERROR Relay switches if the GT20 Control detects an Error s PSAUTO Relay switches when...

Страница 31: ...Print on the first and second line X X Current minimum and maximum temperature since the last reset system OK will reset any all stored Min Max Values SimulateKey Key Command that opens the Door Pane...

Страница 32: ...BLOC To unlock the Joystick Press OK for 2 seconds The Display shows temporarily UBLOC BlockD When the Joystick is blocked the Home display shows BLOCKD if the Joystick is operated Table 18 Update Sof...

Страница 33: ...l is independent from each other It is possible to select a different setting range if deemed necessary For example Master Vo 4 seconds Slave Vo 5 seconds 4 Select the Parameter AoSeq Delay angle for...

Страница 34: ...ontrol Select the Parameter EMY IN Select the Setting Range Open 3 Go to the Slave GT20 Control Select the Parameter EMY IN Select the Setting Range Open 4 Go to the Master GT20 Control Select the fol...

Страница 35: ...mmand to the Control of the Exterior door A The Exterior door must not be able to open CHAPTER 11 RELAY PRINT X X The Relay PCB Board is strictly used for monitoring purposes and is optional only For...

Страница 36: ...nk on the lower half of the screen 7 Move the Joystick to the Right or to the Left to select 1 the appropriate Value 8 Repeat steps 5 thru 7 until all Relay PCBs are programmed within the GT20 Control...

Страница 37: ...ed RO R1 FP RP Displays what the Door Panel is doing RO Address for Relay Board RC 0 R1 N A FP N A RP N A Status Symbol Identified and ready for operation Neither identified nor registered e Defective...

Страница 38: ...witch the Drive Unit to MANUAL Operating Mode Then carefully check if the door closes in a cushioned manner X X If Not Replace Hardware X X If Yes Check correct the friction of the Door Panel and the...

Страница 39: ...ng Too many successive obstacles have occured X X Examine the installation X X Remove the obstacle X X Move the Door panel to the target position Permanent H A Restart after 60 s 02 Obstacle during cl...

Страница 40: ...ternal power supply CAN Table 24 Option No Description Cause Elimination Checking Time Reaction 60 00 Relay PCB 0 Option PCB has been removed its address changed or became defective X X Check if the o...

Страница 41: ...en Table 28 Closing Sequence Interlock Function Erroneous Behavior Analysis Possible Causes Remedy Drive unit fails to react X X No automatic opening X X No activation from sensors Power Mode Switch b...

Страница 42: ...he Activation Sensor Check the operating mode The operating mode OPEN is active Change the operating mode The Operating Mode cannot be changed Program selection keys on the side on the side cover are...

Страница 43: ...7 Push the Joystick to the 3 times to the Left and 3 times to the Right LLLRRR 8 The LED display should black out and then a blue light should begin flashing The new Software version will then display...

Отзывы: