Status Screen
The status screen shows a snapshot of all the
relay control inputs temperatures
and
output
state
for each relay. It is accessed by entering an
‘s’
at anytime. It shows the controlling
variables and any overtemp / under-temp status states. As an example below the R1: Root
Cellar Mode,
O
utside and
C
ellar temps (O/C) are shown, the calculated deltaT, and output relay
is OFF.
Across the top it shows current temperature
readings of all inputs. From there is shows the
relay control rules configured mode, controlling
input values, and relay output state at the end.
If an under or over temp state is overriding the
control rule it will show which one. On R6 a reset
control rule is setup and MINT value indicates
that the minimum temperature is being violating
and forcing the output on. The RSP value is the
reset setpoint calculated and being used based
on the ambient temperature and slope you have
selected. This value is bounded by the Min
Temperature and Max temperatures you
configured for the rule.
You will see a trigger one shot status with
amount of time left if you do a one shot trigger on
any of the outputs in this display as well.
MAXDTC-BT User Manual - Rev A
www.mydtcstore.com