Mydax, Inc. 

1M150W 

Water Cooled Chiller 

 

 

Designed for Lockheed Martin   

CAUTION: DO NOT USE AUTOMOTIVE ANTIFREEZE, residue build up will cause damage the 
unit's critical components. 

 
 

PUSH RESET BUTTON

 

 

The RESET button, located below the front panel, must be pushed after an error in the interlock circuit occurs 
prior to restarting the system.  This resets the power safety interlock loop, which protects the operator and 
electrical circuitry.   

 

EXTERNAL "FLOW-OK" RELAY CONTACTS

 

 

This unit is equipped with a normally-open relay for an external flow indication. Located on the rear panel 
is a BNC connector, labeled "Flow-OK"; the outer shield is common, inner pin is the normally-open 
contact.  When an adequate flow condition is satisfied, the relay will close the contacts. This feature's trip-
point is settable from 5 to 20 GPM on Test Panel 6; see description in the DIAGNOSTIC DISPLAYS 
section of this manual, under TEST PANEL 6. 
 

 

OUTPUT FLOW ADJUSTMENT VALVE

 

 

To adjust the flow and pressure of the recirculation loop, adjust the valve on the rear of the unit labeled "Water 
Flow Adjustment Valve". The 100 PSI “Output Pressure” gauge, located on the rear bulkhead, will indicate the 
output pressure after the valve. The pressure gauge labeled “Pump Pressure” indicates the internal pump 
pressure. The flow rate is visible on the front LCD display panel. 

 
BYPASS VALVE

 

 

To divert the recirculation flow from the output path back to the tank, first open the Bypass valve, then close the 
output flow adjustment valve. To return from this mode, reverse the procedure; always keeping adequate flow 
through the flowmeter. If the flowmeter sees less than 10 GPM flow, the chiller will shut

 

down to protect the 

pump.  
 
An integrated pressure switch will shut down the chiller at an output pressure of 65 psi; if the backpressure is 
near 60 psi, this bypass valve should be opened when starting the pump to prevent the switch from kicking out. 

 
DEIONIZATION FILTER

 

 

The system is equipped with a deionizing filter; water flow through the filter is controlled by the 
microprocessor to maintain the water resistivity between 300K and 500K ohms. On a yearly basis, or if the 
unit is unable to maintain resistivity to acceptable level, replace with Mydax part# F1003. This mixed-ion 
resin cartridge filter is only available from Mydax. 
 

25 MICRON PARTICLE FILTERS

 

 

On the rear of the chiller is two 20 inch particle filters; the two filters are plumbed in parallel to reduce the 
pressure drop at the designed high flow volume. Maintenance of these filters shall be to replace them with 
like type (DGD-2501-20) when or if the available flow and/or pressure becomes unacceptable. This time 
period will depend on the application and usage, as well as the cleanliness of the system. 
 
 

BNC       "Flow-OK" Relay 

Normally Open

Common

Содержание 1M150W

Страница 1: ...vanced temperature control technology MYDAX INC INSTRUCTION OPERATION MANUAL 1M150W WATER COOLED CHILLER MYDAX INC 12260 Shale Ridge Road Auburn CA 95602 530 888 6662 FAX 530 888 0962 http www mydax c...

Страница 2: ...YSTEM OVERVIEW 4 INSTALLATION 6 FRONT PANEL CONTROLS 8 ALARM ERROR MESSAGES 10 DIAGNOSTIC DISPLAYS 11 SERVICE WARRANTY 14 SHIPPING STORAGE PROCEDURE 15 DRAWINGS PARTS LIST FRAME DRAWING FLUID DIAGRAM...

Страница 3: ...70 F 7 Gpm 40 F 20 PSI differential Electrical Service 460 480 VAC 60 Hz 3 phase 50 amp service Physical Parameters 65 H x 36 W x 58 D 1000 lbs dry weight STANDARD FEATURES This chiller is complete wi...

Страница 4: ...reas where potentially harmful conditions exist and in this manual to bring attention to such conditions This chiller uses materials that are subject to environmental regulations be sure to familiariz...

Страница 5: ...mpressor is hermetically sealed and no service should be required In the event that cleanup is necessary absorb oil with oil absorbent material and dispose of as a hazardous waste Follow approved clea...

Страница 6: ...TD s resistance temperature devices located about the circuit The drawing shows RTD s at the discharge line leading from the recirculating pump at the return line leading to the reservoir between the...

Страница 7: ...one power relay coil and a relay pole RL1 B The RESET switch serves to feed power to the relay which energizes the contactor When energized the contactor feeds power back to the relay so the RESET swi...

Страница 8: ...e starting to allow the crankcase heater to separate the refrigerant from the oil CONDENSER FLOW The condenser inlet and outlet fittings are 1 stainless steel female pipe thread fittings FPT Plumb the...

Страница 9: ...ow rate is visible on the front LCD display panel BYPASS VALVE To divert the recirculation flow from the output path back to the tank first open the Bypass valve then close the output flow adjustment...

Страница 10: ...ition is eliminated or the MUTE ALARM switch is depressed again Pressing MUTE ALARM when no alarm is active causes the alarm to sound once and the TEST ALARM display to appear SET Enables SET TEMPERAT...

Страница 11: ...decrements toggles tank temperature setpoint temperature and evaporator data view modes for multiple channel systems DECIMAL Display shows model number and software revision date and copyright RUN PU...

Страница 12: ...s too close to freezing 4 C The microprocessor shuts down the system with a fatal alarm Push Reset Indicates that a fatal alarm in the interlock circuit has occurred and the operator must push the Res...

Страница 13: ...a direct indicator of condenser temperature and pressure The microprocessor sends the CONDENSER HOT error message if the condenser temperature exceeds 54 C TEST PANEL 3 The first 3 sets of 4 digit nu...

Страница 14: ...e the Flow OK relay below the selected GPM The output of the relay is wired to a BNC connector labeled Flow OK located on the rear panel of the unit The shield and center pin are the normally open con...

Страница 15: ...setpoint temperatures of whichever recirculating channel was last selected at the Main Display and the system wide alarm history The second line indicates which recirculating channel was last selecte...

Страница 16: ...use of a torch In particular service of Mydax refrigeration circuits requires attention to the following 1 Use caution to protect components from heat damage 2 Prevent any moisture from entering the...

Страница 17: ...en run with water ethylene glycol should be added to the recirculating loop Verify that the concentration of ethylene glycol approaches 50 measure with a hydrometer in the recirculating loop before dr...

Отзывы: